The bill of material is checked, the ratings are stated, the scope is defined, and the open questions are written down before the request reaches you.
A request package as it arrives.
Parts Check (sample), all 20 lines
| Line | Tag | Qty / panel | Total | Part number | Description | Flag | Alternate |
|---|---|---|---|---|---|---|---|
| 1 | Main breaker | 1 | 1 | Schneider Electric (Square D) HDL36060 | Square D PowerPacT H-frame (150 A) molded case circuit breaker, 3-pole, 60 A, 600 Vac, D interrupting (25 kA @ 240 Vac, 18 kA @ 480 Vac, 14 kA @ 600 Vac), thermal-magnetic, lugs both ends, standard (80%) ratedLug / terminal kit: included | —Published short-circuit rating on its own: 18 kA at 480 V | ABB XT2NU3060AFF000XXXNearest available, differs on interrupting rating (higher)equivalent for your team to approve, see A1Lead time: Potential lead time issue based on stock levels |
| 2 | VFD, pump 1 | 1 | 1 | Siemens 6SL3210-5BE21-5UV0 | Siemens SINAMICS V20 basic converter 6SL3210-5BE21-5UV0, 1.5 kW / 2 hp, IL 4.1/4.1 A, IH 4.1/4.1 A, 380…480 V 3-phase AC, frame FSA, without integrated line filterdiscontinued | Discontinueddiscontinued; Siemens publishes 6SL3210-5BE21-5UV1 as the successor | Siemens 6SL3210-5BE21-5UV1published successor, see A2Lead time: Potential lead time issue based on stock levels |
| 3 | Contactor, pump 2 | 1 | 1 | Schneider Electric (Square D) LC1D25G7 | Schneider Electric TeSys Deca contactor, 3-pole (3 NO), 25 A AC-3, 40 A AC-1, coil 120 V AC 50/60 Hz, screw terminals | — | Siemens 3RT2026-1NF30Nearest available, differs on coil voltage and type (wider range)equivalent for your team to approve, see A3Lead time: Potential lead time issue based on stock levels |
| 4 | Overload, pump 2 | 1 | 1 | Siemens 3RU2116-1JB0 | Siemens SIRIUS 3RU21 thermal overload relay 3RU2116-1JB0, size S00, 7–10 A, CLASS 10, 1 NO + 1 NC, screw terminals, direct mount | — | Schneider Electric (Square D) LRD14Exact matchequivalent for your team to approve, see A4 |
| 5 | Motor protector, pump 2 | 1 | 1 | Siemens 3RV2011-1JA10 | Siemens SIRIUS 3RV20 motor starter protector 3RV2011-1JA10, size S00, 7–10 A, CLASS 10, screw terminals, no auxiliary switch | — | No cross on file: cannot confirm — we haven't confirmed your part's interrupting rating against the catalog page (decoded from its catalog number: 65 kA @480Y/277 V); confirm it with Siemens before using it for SCCR |
| 6 | Control transformer 480/120V 250VA | 1 | 1 | Siemens MT0250A | Siemens Class MT industrial control power transformer, 250 VA, primary 240x480 / 230x460 / 220x440 V, secondary 120/115/110 V, 50/60 Hz, touch-safe terminals | — | No cross on file |
| 7 | Control circuit fuses | 2 | 2 | Eaton Bussmann LP-CC-10 | Eaton Bussmann series Low-Peak LP-CC Class CC time-delay rejection fuse 10 A, 600 Vac, 150 Vdc, IR 200 kA AC / 20 kA DC | — | Littelfuse KLDR010Nearest available, differs on DC voltage rating (higher)equivalent for your team to approve, see A5Lead time: Potential lead time issue based on stock levels |
| 8 | 24VDC power supply | 1 | 1 | Phoenix Contact 2904601 | Phoenix Contact QUINT4-PS/1AC/24DC/10 — QUINT POWER, 1~, 24 V / 10 A, input 85 V AC … 264 V AC 90 V DC … 350 V DC, 50 x 130 x 125 mm | — | No cross on file |
| 9 | Pump run lights | 3 | 3 | Schneider Electric (Square D) XB4BVB3 | Schneider Electric Harmony XB4 (metal) complete pilot light, Protected LED, green, 24 Vac/Vdc, screw clamp terminalsContact block / light unit: included | —No manufacturer given — found as Schneider Electric | Allen-Bradley 800FD-P3N3Exact matchequivalent for your team to approve, see A6Stock not published |
| 10 | Hand-Off-Auto selector | 2 | 2 | Schneider Electric (Square D) XB5AD33 | Schneider Electric Harmony XB5 (plastic, Ø22) complete selector switch, standard black lever, 3-position maintained, 2 N.O., screw clamp terminals | — | No cross on file |
| 11 | Control power on light | 1 | 1 | Schneider Electric (Square D) XB5AVG3 | Schneider Electric Harmony XB5 (plastic) complete pilot light, Protected LED, green, 110–120 Vac, screw clamp terminalsContact block / light unit: included | — | Eaton M22-L-G-230GNearest available, differs on lamp voltage (wider range), terminal type (not confirmed), ordered as one unit vs operator + contact block (not confirmed)equivalent for your team to approve, see A7 |
| 12 | Enclosure 24 x 20 x 8 | 1 | 1 | nVent Hoffman A24H2008SSLP | nVent HOFFMAN Continuous Hinge with Clamps LP enclosure A24H2008SSLP, stainless steel, Type 4X, 24 x 20 x 8 in. (H x W x D), panel A24P20Backpan / mounting panel: ordered separately (A24P20) | Lead timePotential lead time issue based on stock levels · checked 2026-10-30 | No cross on file |
| 13 | Alternator contactor | 1 | 1 | Allen-Bradley 100-C23D11 | — | Check part numbernot in Allen-Bradley's current catalogs — did you mean 100-C23D10 or 100-C23D01? | — |
| 14 | VFD input fuses | 3 | 3 | Eaton Bussmann KTK-R-10 | Eaton Bussmann series Limitron KTK-R Class CC fast-acting rejection fuse 10 A, 600 Vac, IR 200 kA | —Published short-circuit rating on its own: 200 kA (fuse rated 600 V) | Mersen ATMR10Exact matchequivalent for your team to approve, see A8 |
| 15 | Lockout contactor | 1 | 1 | Allen-Bradley 100-C23D10 | Allen-Bradley 100-C23 3-pole IEC contactor, 1 NO aux, coil 120 V AC 60 Hz | —Stock not published | Schneider Electric (Square D) LC1D25G7Nearest available, differs on coil voltage and type (wider range), AC-3 rating (higher), hp 3-phase 600 V (higher), hp 3-phase 208 V (higher) and 1 moreequivalent for your team to approve, see A9 |
| 16 | Overload for lockout contactor | 1 | 1 | Allen-Bradley 193-1EEDB | Allen-Bradley E100 electronic overload relay Basic (Bulletin 193, IEC), 3.2…16 A, single- and three-phase, trip class 10/20, manual reset — direct mount to 100-C09…C23 | —Stock not published | No cross on file |
| 17 | Spare overload | 1 | 1 | Schneider Electric (Square D) LRD14 | Schneider Electric TeSys Deca thermal overload relay (ambient compensated, bimetallic), 7–10 A, Class 10, with single-phase sensitivity, direct mounting to LC1/LC2 D09–D38 | — | Lovato Electric RF381000Nearest available, differs on adjustment range (wider range)equivalent for your team to approve, see A10Stock not published |
| 18 | 3 | 3 | Eaton Bussmann FRS-R-30 | Eaton Bussmann series Fusetron FRS-R Class RK5 dual-element time-delay fuse 30 A, 600 Vac / 300 Vdc, IR 200 kA AC / 20 kA DC | —No manufacturer given — found as Eaton BussmannPublished short-circuit rating on its own: 200 kA (fuse rated 600 V) | Mersen TRS30RExact matchequivalent for your team to approve, see A11 | |
| 19 | Spare fuse set | 3 | 3 | Mersen TRS30R | Mersen Tri-Onic TRS-R Class RK5 time-delay fuse 30 A, 600 V AC / 300 V DC, 200 kA AC / 20 kA DC IR | —Published short-circuit rating on its own: 200 kA (fuse rated 600 V) | Eaton Bussmann FRS-R-30Exact matchequivalent for your team to approve, see A12 |
| 20 | Spare motor protector | 1 | 1 | ABB MS132-10 | ABB MS132 manual motor starter, thermal and magnetic protection, 6.3…10 A, Irm 150 Ain ABB's stocking program | —Published short-circuit rating on its own: 65 kA at 480 V | Allen-Bradley 140MT-C3E-C10Nearest available, differs on interrupting rating (higher)equivalent for your team to approve, see A13Stock not published |
Items in your parts list that do not fit together. We have not changed anything — please confirm or correct.
| Lamp voltage | Pump run lights (line 9): the lamp is 24 V AC/DC and the control circuit is stated as 120 V AC. There is a 24 V DC supply on line 8 — confirm which circuit it runs on. | line 9Pump run lights |
| Motor protection | Both a motor protector (line 5) and an overload relay (line 4) are on motor Pump 2. Please confirm both are intended. | lines 5, 4Motor protector, pump 2; Overload, pump 2 |
| Fuse holders | The fuses on lines 7, 14, 18 and 19 (Class CC, RK5) have no fuse holder or fuse block on the parts list. Please add one or tell us where they mount. | lines 7, 14, 18, 19Control circuit fuses; VFD input fuses; Spare fuse set |
| Short-circuit rating | Main breaker (line 1): its published rating on its own is 18 kA at 480 V, below the 25 kA you asked for. Combination and series ratings can change this — confirm with the shop. | line 1Main breaker |
| Pilot light quantity | Line 9 has 3 run lights for 2 motors. Please confirm the quantity and colors — are some of them fail or alarm lights? | line 9Pump run lights |
Part numbers to confirm before the quote is firm.
| Alternator contactor | Allen-Bradley 100-C23D11 is not in Allen-Bradley's current catalogs. Did you mean Allen-Bradley 100-C23D10 or 100-C23D01 (each one character different — 100-C23D10 is the same part as line 15)? Please confirm. | line 13Alternator contactor |
Not in your parts list — needed to firm the quote.
| Usually on a duplex pump panel | Not in your parts list: elapsed time meter for each pump; high-level alarm horn and light; float switches or a level controller. Should any of these be included? | |
| Included vs ordered separately | Inclusion of lug / terminal kit is not stated in the catalog for 1 line — confirm with the shop. | line 1Main breaker |
ABB SACE Tmax XT2N molded case circuit breaker, 3-pole, 60 A, TMF/TMD thermal-magnetic trip unit, 80% rated, 25 kA @ 480 V AC, front terminals (F)
Nearest available, differs on interrupting rating (higher). No exact match was found; this one needs your approval.
Matched (yours → alternate): Kind of product: circuit breaker · Poles: 3 · Trip curve / trip unit: thermal-magnetic · Trip rating: 60 A · Interrupting rating: 18 kA @480 V → 65 kA @240 V / 25 kA @480 V / 18 kA @600 V / 35 kA @250 V DC (2 poles in series) / 35 kA @500 V DC (3 poles in series) (covers yours) · Fixed vs adjustable trip: fixed trip
Confirm on the catalog data:
Other candidates, nearest first: ABB XT2SU3060AFF000XXX, XT2HU3060AFF000XXX, XT2LU3060AFF000XXX, XT2VU3060AFF000XXX; Siemens 3VA5260-5ED31-0AA0, 3VA5260-6ED31-0AA0; and one other further above your ratings. Each also covers your part on every rating compared; the further down the list, the further above your ratings it sits. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Siemens SINAMICS V20 basic converter 6SL3210-5BE21-5UV1, 1.5 kW / 2 hp, IL 4.1/4.1 A, IH 4.1/4.1 A, 380…480 V 3-phase AC, frame FSA, without integrated line filter
Siemens publishes this as the successor to your part.
Matched (yours → alternate): published by Siemens as the replacement · UL listing not confirmed from the catalog
Siemens SIRIUS 3RT2026 3-pole contactor, size S0, 1 NO + 1 NC aux, coil 95-130 V AC/DC, screw terminals
Nearest available, differs on coil voltage and type (wider range). No exact match was found; this one needs your approval.
Matched (yours → alternate): Kind of product: general purpose contactor · Poles: 3 · Reversing / non-reversing: non-reversing · Coil voltage and type: 120 V AC 50/60 Hz → 95-130 V AC/DC (covers yours) · Duty: general · Enclosed / open: open · AC-3 rating: 25 A · hp 3-phase 480 V: 15 hp · hp 3-phase 600 V: 20 hp · hp 3-phase 240 V: 7.5 hp · hp 3-phase 208 V: 7.5 hp · Rated voltage: 600 V · AC-1 / thermal current rating: 40 A · Auxiliary contact arrangement: both 1 NO + 1 NC
Confirm on the catalog data:
Other candidates, nearest first: Siemens 3RT2026-2NF30. Siemens 3RT2026-2NF30 is tied with 3RT2026-1NF30 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Schneider Electric TeSys Deca thermal overload relay (ambient compensated, bimetallic), 7–10 A, Class 10, with single-phase sensitivity, direct mounting to LC1/LC2 D09–D38
Exact match. Equal to your part on every attribute compared.
Matched (yours → alternate): Kind of product: overload relay · Reset type: manual/automatic · Trip class: 10 · Adjustment range: 7–10 A · Phase-loss sensitivity: sensitive
Confirm on the catalog data:
Littelfuse UL Class CC KLDR time-delay fuse 10 A, 600 Vac / 300 Vdc, 200 kA AC IR, 20 kA DC
Nearest available, differs on DC voltage rating (higher). No exact match was found; this one needs your approval.
Matched (yours → alternate): Fuse class: CC · Ampere rating: 10 A · Voltage rating: 600 V · Time-delay / fast-acting: time-delay · Interrupting rating: 200 kA · DC voltage rating: 150 V → 300 V (covers yours) · DC interrupting rating (kA): 20 kA · DC rating basis: published rating
Confirm on the catalog data:
Allen-Bradley 800FD 22 mm monolithic pilot light, green lens, LED 24V AC/DC, standard screw terminals
Exact match. Equal to your part on every attribute compared.
Matched (yours → alternate): Mounting size: 22 mm · Color: green · Steady / flashing / audible: steady · Lamp type: led · Lamp voltage: 24 V AC/DC · Terminal type: screw · Ordered as one unit vs operator + contact block: complete unit
Eaton M22 LED indicating light, flush, flat lens, green lens, green LED 85–264 Vac light unit
Nearest available, differs on lamp voltage (wider range), terminal type (not confirmed), ordered as one unit vs operator + contact block (not confirmed). No exact match was found; this one needs your approval.
Matched (yours → alternate): Mounting size: 22 mm · Color: green · Steady / flashing / audible: steady · Lamp type: led · Lamp voltage: 110–120 V AC → 85–264 V AC (covers yours)
Other candidates, nearest first: Eaton M22-L-G-230G-P. Eaton M22-L-G-230G-P is tied with M22-L-G-230G on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Mersen Amp-Trap ATMR Class CC fast-acting fuse 10 A, 600 V AC / 600 V DC, 200 kA AC / 100 kA DC IR
Exact match. Equal to your part on every attribute compared.
Matched (yours → alternate): Fuse class: CC · Ampere rating: 10 A · Voltage rating: 600 V · Time-delay / fast-acting: fast-acting · Interrupting rating: 200 kA
Confirm on the catalog data:
Schneider Electric TeSys Deca contactor, 3-pole (3 NO), 25 A AC-3, 40 A AC-1, coil 120 V AC 50/60 Hz, screw terminals
Nearest available, differs on coil voltage and type (wider range), AC-3 rating (higher), hp 3-phase 600 V (higher), hp 3-phase 208 V (higher) and 1 more. No exact match was found; this one needs your approval.
Matched (yours → alternate): Kind of product: general purpose contactor · Poles: 3 · Reversing / non-reversing: non-reversing · Coil voltage and type: 120 V AC 60 Hz → 120 V AC 50/60 Hz (covers yours) · Duty: general · Enclosed / open: open · AC-3 rating: 23 A → 25 A (covers yours) · hp 3-phase 480 V: 15 hp · hp 3-phase 600 V: 15 hp → 20 hp (covers yours) · hp 3-phase 240 V: 7.5 hp · hp 3-phase 208 V: 5 hp → 7.5 hp (covers yours) · Rated voltage: 600 V · AC-1 / thermal current rating: 32 A → 40 A (covers yours) · Auxiliary contact arrangement: 1 NO + 1 NC covers your 1 NO (extra contacts unused)
Confirm on the catalog data:
Other candidates, nearest first: Schneider Electric LC1D25KUE; Siemens 3RT2026-1AK60, 3RT2026-2AK60; Schneider Electric LC1D25EHE; Siemens 3RT2026-1NF30, 3RT2026-2NF30. Schneider Electric LC1D25KUE, Siemens 3RT2026-1AK60, Siemens 3RT2026-2AK60, Schneider Electric LC1D25EHE, Siemens 3RT2026-1NF30 and Siemens 3RT2026-2NF30 are tied with LC1D25G7 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Lovato thermal overload relay RF38, 6.3…10 A, phase-loss (single-phasing) sensitive, manual or automatic reset — Direct mounting on BF09...BF38 contactors. Independent mounting with RFX3804 base
Nearest available, differs on adjustment range (wider range). No exact match was found; this one needs your approval.
Matched (yours → alternate): Kind of product: overload relay · Reset type: manual/automatic · Trip class: 10 · Adjustment range: 7–10 A → 6.3–10 A (covers yours) · Phase-loss sensitivity: sensitive
Confirm on the catalog data:
Mersen Tri-Onic TRS-R Class RK5 time-delay fuse 30 A, 600 V AC / 300 V DC, 200 kA AC / 20 kA DC IR
Exact match. Equal to your part on every attribute compared.
Matched (yours → alternate): Fuse class: RK5 · Ampere rating: 30 A · Voltage rating: 600 V · Time-delay / fast-acting: time-delay · Interrupting rating: 200 kA · DC voltage rating: 300 V · DC interrupting rating (kA): 20 kA · DC rating basis: published rating
Confirm on the catalog data:
Other candidates, nearest first: Littelfuse FLSR030, FLSR030ID. Littelfuse FLSR030 and Littelfuse FLSR030ID are tied with TRS30R on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Eaton Bussmann series Fusetron FRS-R Class RK5 dual-element time-delay fuse 30 A, 600 Vac / 300 Vdc, IR 200 kA AC / 20 kA DC
Exact match. Equal to your part on every attribute compared.
Matched (yours → alternate): Fuse class: RK5 · Ampere rating: 30 A · Voltage rating: 600 V · Time-delay / fast-acting: time-delay · Interrupting rating: 200 kA · DC voltage rating: 300 V · DC interrupting rating (kA): 20 kA · DC rating basis: published rating
Confirm on the catalog data:
Other candidates, nearest first: Littelfuse FLSR030, FLSR030ID. Littelfuse FLSR030 and Littelfuse FLSR030ID are tied with FRS-R-30 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Allen-Bradley 140MT C-frame adjustable thermal / fixed magnetic MPCB (motor protective switching device), 6.3…10 A, normal break, magnetic trip 140 A
Nearest available, differs on interrupting rating (higher). No exact match was found; this one needs your approval.
Matched (yours → alternate): Poles: 3 · Trip type: thermal-magnetic · Adjustment range: 6.3–10 A · Interrupting rating: 65 kA @480 V → 65 kA @480 V / 30 kA @600 V (covers yours) · UL 508 Type E / Type F: UL 508 Type E (self-protected) · Slash vs straight voltage rating: this one is not slash-only where yours is straight (from the printed text)
Differs from your part:
Confirm on the catalog data:
Other candidates, nearest first: Allen-Bradley 140MT-D9E-C10, 140MT-D9T-C10. Allen-Bradley 140MT-D9E-C10 and Allen-Bradley 140MT-D9T-C10 are tied with 140MT-C3E-C10 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Email orders@meisterlinecontrols.com