For panel shops

Requests that arrive ready to quote.

The bill of material is checked, the ratings are stated, the scope is defined, and the open questions are written down before the request reaches you.

Photo: a panel shop floor with back plates in build

Working with us

A request package as it arrives.

Parts Check (sample), all 20 lines

PanelDuplex booster pump station control panel
Quantity1 panel
Supply480 V 3-phase 60 Hz
Control voltage120 V AC
Short-circuit rating (SCCR)25 kA at 480 V
The assembly SCCR is confirmed by the build shop.
LineTagQty / panelTotalPart numberDescriptionFlagAlternate
1 Main breaker 1 1 Schneider Electric (Square D) HDL36060 Square D PowerPacT H-frame (150 A) molded case circuit breaker, 3-pole, 60 A, 600 Vac, D interrupting (25 kA @ 240 Vac, 18 kA @ 480 Vac, 14 kA @ 600 Vac), thermal-magnetic, lugs both ends, standard (80%) ratedLug / terminal kit: included —Published short-circuit rating on its own: 18 kA at 480 V ABB XT2NU3060AFF000XXXNearest available, differs on interrupting rating (higher)equivalent for your team to approve, see A1Lead time: Potential lead time issue based on stock levels
2 VFD, pump 1 1 1 Siemens 6SL3210-5BE21-5UV0 Siemens SINAMICS V20 basic converter 6SL3210-5BE21-5UV0, 1.5 kW / 2 hp, IL 4.1/4.1 A, IH 4.1/4.1 A, 380…480 V 3-phase AC, frame FSA, without integrated line filterdiscontinued Discontinueddiscontinued; Siemens publishes 6SL3210-5BE21-5UV1 as the successor Siemens 6SL3210-5BE21-5UV1published successor, see A2Lead time: Potential lead time issue based on stock levels
3 Contactor, pump 2 1 1 Schneider Electric (Square D) LC1D25G7 Schneider Electric TeSys Deca contactor, 3-pole (3 NO), 25 A AC-3, 40 A AC-1, coil 120 V AC 50/60 Hz, screw terminals — Siemens 3RT2026-1NF30Nearest available, differs on coil voltage and type (wider range)equivalent for your team to approve, see A3Lead time: Potential lead time issue based on stock levels
4 Overload, pump 2 1 1 Siemens 3RU2116-1JB0 Siemens SIRIUS 3RU21 thermal overload relay 3RU2116-1JB0, size S00, 7–10 A, CLASS 10, 1 NO + 1 NC, screw terminals, direct mount — Schneider Electric (Square D) LRD14Exact matchequivalent for your team to approve, see A4
5 Motor protector, pump 2 1 1 Siemens 3RV2011-1JA10 Siemens SIRIUS 3RV20 motor starter protector 3RV2011-1JA10, size S00, 7–10 A, CLASS 10, screw terminals, no auxiliary switch — No cross on file: cannot confirm — we haven't confirmed your part's interrupting rating against the catalog page (decoded from its catalog number: 65 kA @480Y/277 V); confirm it with Siemens before using it for SCCR
6 Control transformer 480/120V 250VA 1 1 Siemens MT0250A Siemens Class MT industrial control power transformer, 250 VA, primary 240x480 / 230x460 / 220x440 V, secondary 120/115/110 V, 50/60 Hz, touch-safe terminals — No cross on file
7 Control circuit fuses 2 2 Eaton Bussmann LP-CC-10 Eaton Bussmann series Low-Peak LP-CC Class CC time-delay rejection fuse 10 A, 600 Vac, 150 Vdc, IR 200 kA AC / 20 kA DC — Littelfuse KLDR010Nearest available, differs on DC voltage rating (higher)equivalent for your team to approve, see A5Lead time: Potential lead time issue based on stock levels
8 24VDC power supply 1 1 Phoenix Contact 2904601 Phoenix Contact QUINT4-PS/1AC/24DC/10 — QUINT POWER, 1~, 24 V / 10 A, input 85 V AC … 264 V AC 90 V DC … 350 V DC, 50 x 130 x 125 mm — No cross on file
9 Pump run lights 3 3 Schneider Electric (Square D) XB4BVB3 Schneider Electric Harmony XB4 (metal) complete pilot light, Protected LED, green, 24 Vac/Vdc, screw clamp terminalsContact block / light unit: included —No manufacturer given — found as Schneider Electric Allen-Bradley 800FD-P3N3Exact matchequivalent for your team to approve, see A6Stock not published
10 Hand-Off-Auto selector 2 2 Schneider Electric (Square D) XB5AD33 Schneider Electric Harmony XB5 (plastic, Ø22) complete selector switch, standard black lever, 3-position maintained, 2 N.O., screw clamp terminals — No cross on file
11 Control power on light 1 1 Schneider Electric (Square D) XB5AVG3 Schneider Electric Harmony XB5 (plastic) complete pilot light, Protected LED, green, 110–120 Vac, screw clamp terminalsContact block / light unit: included — Eaton M22-L-G-230GNearest available, differs on lamp voltage (wider range), terminal type (not confirmed), ordered as one unit vs operator + contact block (not confirmed)equivalent for your team to approve, see A7
12 Enclosure 24 x 20 x 8 1 1 nVent Hoffman A24H2008SSLP nVent HOFFMAN Continuous Hinge with Clamps LP enclosure A24H2008SSLP, stainless steel, Type 4X, 24 x 20 x 8 in. (H x W x D), panel A24P20Backpan / mounting panel: ordered separately (A24P20) Lead timePotential lead time issue based on stock levels · checked 2026-10-30 No cross on file
13 Alternator contactor 1 1 Allen-Bradley 100-C23D11 — Check part numbernot in Allen-Bradley's current catalogs — did you mean 100-C23D10 or 100-C23D01? —
14 VFD input fuses 3 3 Eaton Bussmann KTK-R-10 Eaton Bussmann series Limitron KTK-R Class CC fast-acting rejection fuse 10 A, 600 Vac, IR 200 kA —Published short-circuit rating on its own: 200 kA (fuse rated 600 V) Mersen ATMR10Exact matchequivalent for your team to approve, see A8
15 Lockout contactor 1 1 Allen-Bradley 100-C23D10 Allen-Bradley 100-C23 3-pole IEC contactor, 1 NO aux, coil 120 V AC 60 Hz —Stock not published Schneider Electric (Square D) LC1D25G7Nearest available, differs on coil voltage and type (wider range), AC-3 rating (higher), hp 3-phase 600 V (higher), hp 3-phase 208 V (higher) and 1 moreequivalent for your team to approve, see A9
16 Overload for lockout contactor 1 1 Allen-Bradley 193-1EEDB Allen-Bradley E100 electronic overload relay Basic (Bulletin 193, IEC), 3.2…16 A, single- and three-phase, trip class 10/20, manual reset — direct mount to 100-C09…C23 —Stock not published No cross on file
17 Spare overload 1 1 Schneider Electric (Square D) LRD14 Schneider Electric TeSys Deca thermal overload relay (ambient compensated, bimetallic), 7–10 A, Class 10, with single-phase sensitivity, direct mounting to LC1/LC2 D09–D38 — Lovato Electric RF381000Nearest available, differs on adjustment range (wider range)equivalent for your team to approve, see A10Stock not published
18 3 3 Eaton Bussmann FRS-R-30 Eaton Bussmann series Fusetron FRS-R Class RK5 dual-element time-delay fuse 30 A, 600 Vac / 300 Vdc, IR 200 kA AC / 20 kA DC —No manufacturer given — found as Eaton BussmannPublished short-circuit rating on its own: 200 kA (fuse rated 600 V) Mersen TRS30RExact matchequivalent for your team to approve, see A11
19 Spare fuse set 3 3 Mersen TRS30R Mersen Tri-Onic TRS-R Class RK5 time-delay fuse 30 A, 600 V AC / 300 V DC, 200 kA AC / 20 kA DC IR —Published short-circuit rating on its own: 200 kA (fuse rated 600 V) Eaton Bussmann FRS-R-30Exact matchequivalent for your team to approve, see A12
20 Spare motor protector 1 1 ABB MS132-10 ABB MS132 manual motor starter, thermal and magnetic protection, 6.3…10 A, Irm 150 Ain ABB's stocking program —Published short-circuit rating on its own: 65 kA at 480 V Allen-Bradley 140MT-C3E-C10Nearest available, differs on interrupting rating (higher)equivalent for your team to approve, see A13Stock not published

Questions · 8

Please check · 5

Items in your parts list that do not fit together. We have not changed anything — please confirm or correct.

Lamp voltagePump run lights (line 9): the lamp is 24 V AC/DC and the control circuit is stated as 120 V AC. There is a 24 V DC supply on line 8 — confirm which circuit it runs on.line 9Pump run lights
Motor protectionBoth a motor protector (line 5) and an overload relay (line 4) are on motor Pump 2. Please confirm both are intended.lines 5, 4Motor protector, pump 2; Overload, pump 2
Fuse holdersThe fuses on lines 7, 14, 18 and 19 (Class CC, RK5) have no fuse holder or fuse block on the parts list. Please add one or tell us where they mount.lines 7, 14, 18, 19Control circuit fuses; VFD input fuses; Spare fuse set
Short-circuit ratingMain breaker (line 1): its published rating on its own is 18 kA at 480 V, below the 25 kA you asked for. Combination and series ratings can change this — confirm with the shop.line 1Main breaker
Pilot light quantityLine 9 has 3 run lights for 2 motors. Please confirm the quantity and colors — are some of them fail or alarm lights?line 9Pump run lights

Confirm these parts · 1

Part numbers to confirm before the quote is firm.

Alternator contactorAllen-Bradley 100-C23D11 is not in Allen-Bradley's current catalogs. Did you mean Allen-Bradley 100-C23D10 or 100-C23D01 (each one character different — 100-C23D10 is the same part as line 15)? Please confirm.line 13Alternator contactor

We need information · 2

Not in your parts list — needed to firm the quote.

Usually on a duplex pump panelNot in your parts list: elapsed time meter for each pump; high-level alarm horn and light; float switches or a level controller. Should any of these be included?
Included vs ordered separatelyInclusion of lug / terminal kit is not stated in the catalog for 1 line — confirm with the shop.line 1Main breaker
Alternates for these lines (13)
A1 · line 1 · Main breaker
Schneider Electric (Square D) HDL36060 → ABB XT2NU3060AFF000XXX

ABB SACE Tmax XT2N molded case circuit breaker, 3-pole, 60 A, TMF/TMD thermal-magnetic trip unit, 80% rated, 25 kA @ 480 V AC, front terminals (F)

Nearest available, differs on interrupting rating (higher). No exact match was found; this one needs your approval.

Matched (yours → alternate): Kind of product: circuit breaker · Poles: 3 · Trip curve / trip unit: thermal-magnetic · Trip rating: 60 A · Interrupting rating: 18 kA @480 V → 65 kA @240 V / 25 kA @480 V / 18 kA @600 V / 35 kA @250 V DC (2 poles in series) / 35 kA @500 V DC (3 poles in series) (covers yours) · Fixed vs adjustable trip: fixed trip

Confirm on the catalog data:

  • interrupting rating at your voltage
  • combination / series ratings
  • frame size and panel space — fit not compared

Other candidates, nearest first: ABB XT2SU3060AFF000XXX, XT2HU3060AFF000XXX, XT2LU3060AFF000XXX, XT2VU3060AFF000XXX; Siemens 3VA5260-5ED31-0AA0, 3VA5260-6ED31-0AA0; and one other further above your ratings. Each also covers your part on every rating compared; the further down the list, the further above your ratings it sits. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

A2 · line 2 · VFD, pump 1
Siemens 6SL3210-5BE21-5UV0 → Siemens 6SL3210-5BE21-5UV1

Siemens SINAMICS V20 basic converter 6SL3210-5BE21-5UV1, 1.5 kW / 2 hp, IL 4.1/4.1 A, IH 4.1/4.1 A, 380…480 V 3-phase AC, frame FSA, without integrated line filter

Siemens publishes this as the successor to your part.

Matched (yours → alternate): published by Siemens as the replacement · UL listing not confirmed from the catalog

A3 · line 3 · Contactor, pump 2
Schneider Electric (Square D) LC1D25G7 → Siemens 3RT2026-1NF30

Siemens SIRIUS 3RT2026 3-pole contactor, size S0, 1 NO + 1 NC aux, coil 95-130 V AC/DC, screw terminals

Nearest available, differs on coil voltage and type (wider range). No exact match was found; this one needs your approval.

Matched (yours → alternate): Kind of product: general purpose contactor · Poles: 3 · Reversing / non-reversing: non-reversing · Coil voltage and type: 120 V AC 50/60 Hz → 95-130 V AC/DC (covers yours) · Duty: general · Enclosed / open: open · AC-3 rating: 25 A · hp 3-phase 480 V: 15 hp · hp 3-phase 600 V: 20 hp · hp 3-phase 240 V: 7.5 hp · hp 3-phase 208 V: 7.5 hp · Rated voltage: 600 V · AC-1 / thermal current rating: 40 A · Auxiliary contact arrangement: both 1 NO + 1 NC

Confirm on the catalog data:

  • SCCR of the combination with its upstream protective device
  • the overload relay that mounts on it
  • frame width and mounting of your accessories — fit not compared

Other candidates, nearest first: Siemens 3RT2026-2NF30. Siemens 3RT2026-2NF30 is tied with 3RT2026-1NF30 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

A4 · line 4 · Overload, pump 2
Siemens 3RU2116-1JB0 → Schneider Electric (Square D) LRD14

Schneider Electric TeSys Deca thermal overload relay (ambient compensated, bimetallic), 7–10 A, Class 10, with single-phase sensitivity, direct mounting to LC1/LC2 D09–D38

Exact match. Equal to your part on every attribute compared.

Matched (yours → alternate): Kind of product: overload relay · Reset type: manual/automatic · Trip class: 10 · Adjustment range: 7–10 A · Phase-loss sensitivity: sensitive

Confirm on the catalog data:

  • mounting to the contactor
  • SCCR of the combination it is used in
A5 · line 7 · Control circuit fuses
Eaton Bussmann LP-CC-10 → Littelfuse KLDR010

Littelfuse UL Class CC KLDR time-delay fuse 10 A, 600 Vac / 300 Vdc, 200 kA AC IR, 20 kA DC

Nearest available, differs on DC voltage rating (higher). No exact match was found; this one needs your approval.

Matched (yours → alternate): Fuse class: CC · Ampere rating: 10 A · Voltage rating: 600 V · Time-delay / fast-acting: time-delay · Interrupting rating: 200 kA · DC voltage rating: 150 V → 300 V (covers yours) · DC interrupting rating (kA): 20 kA · DC rating basis: published rating

Confirm on the catalog data:

  • fuse holder / clip fit
A6 · line 9 · Pump run lights
Schneider Electric (Square D) XB4BVB3 → Allen-Bradley 800FD-P3N3

Allen-Bradley 800FD 22 mm monolithic pilot light, green lens, LED 24V AC/DC, standard screw terminals

Exact match. Equal to your part on every attribute compared.

Matched (yours → alternate): Mounting size: 22 mm · Color: green · Steady / flashing / audible: steady · Lamp type: led · Lamp voltage: 24 V AC/DC · Terminal type: screw · Ordered as one unit vs operator + contact block: complete unit

A7 · line 11 · Control power on light
Schneider Electric (Square D) XB5AVG3 → Eaton M22-L-G-230G

Eaton M22 LED indicating light, flush, flat lens, green lens, green LED 85–264 Vac light unit

Nearest available, differs on lamp voltage (wider range), terminal type (not confirmed), ordered as one unit vs operator + contact block (not confirmed). No exact match was found; this one needs your approval.

Matched (yours → alternate): Mounting size: 22 mm · Color: green · Steady / flashing / audible: steady · Lamp type: led · Lamp voltage: 110–120 V AC → 85–264 V AC (covers yours)

Other candidates, nearest first: Eaton M22-L-G-230G-P. Eaton M22-L-G-230G-P is tied with M22-L-G-230G on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

A8 · line 14 · VFD input fuses
Eaton Bussmann KTK-R-10 → Mersen ATMR10

Mersen Amp-Trap ATMR Class CC fast-acting fuse 10 A, 600 V AC / 600 V DC, 200 kA AC / 100 kA DC IR

Exact match. Equal to your part on every attribute compared.

Matched (yours → alternate): Fuse class: CC · Ampere rating: 10 A · Voltage rating: 600 V · Time-delay / fast-acting: fast-acting · Interrupting rating: 200 kA

Confirm on the catalog data:

  • fuse holder / clip fit
A9 · line 15 · Lockout contactor
Allen-Bradley 100-C23D10 → Schneider Electric (Square D) LC1D25G7

Schneider Electric TeSys Deca contactor, 3-pole (3 NO), 25 A AC-3, 40 A AC-1, coil 120 V AC 50/60 Hz, screw terminals

Nearest available, differs on coil voltage and type (wider range), AC-3 rating (higher), hp 3-phase 600 V (higher), hp 3-phase 208 V (higher) and 1 more. No exact match was found; this one needs your approval.

Matched (yours → alternate): Kind of product: general purpose contactor · Poles: 3 · Reversing / non-reversing: non-reversing · Coil voltage and type: 120 V AC 60 Hz → 120 V AC 50/60 Hz (covers yours) · Duty: general · Enclosed / open: open · AC-3 rating: 23 A → 25 A (covers yours) · hp 3-phase 480 V: 15 hp · hp 3-phase 600 V: 15 hp → 20 hp (covers yours) · hp 3-phase 240 V: 7.5 hp · hp 3-phase 208 V: 5 hp → 7.5 hp (covers yours) · Rated voltage: 600 V · AC-1 / thermal current rating: 32 A → 40 A (covers yours) · Auxiliary contact arrangement: 1 NO + 1 NC covers your 1 NO (extra contacts unused)

Confirm on the catalog data:

  • SCCR of the combination with its upstream protective device
  • the overload relay that mounts on it
  • frame width and mounting of your accessories — fit not compared

Other candidates, nearest first: Schneider Electric LC1D25KUE; Siemens 3RT2026-1AK60, 3RT2026-2AK60; Schneider Electric LC1D25EHE; Siemens 3RT2026-1NF30, 3RT2026-2NF30. Schneider Electric LC1D25KUE, Siemens 3RT2026-1AK60, Siemens 3RT2026-2AK60, Schneider Electric LC1D25EHE, Siemens 3RT2026-1NF30 and Siemens 3RT2026-2NF30 are tied with LC1D25G7 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

A10 · line 17 · Spare overload
Schneider Electric (Square D) LRD14 → Lovato Electric RF381000

Lovato thermal overload relay RF38, 6.3…10 A, phase-loss (single-phasing) sensitive, manual or automatic reset — Direct mounting on BF09...BF38 contactors. Independent mounting with RFX3804 base

Nearest available, differs on adjustment range (wider range). No exact match was found; this one needs your approval.

Matched (yours → alternate): Kind of product: overload relay · Reset type: manual/automatic · Trip class: 10 · Adjustment range: 7–10 A → 6.3–10 A (covers yours) · Phase-loss sensitivity: sensitive

Confirm on the catalog data:

  • mounting to the contactor
  • SCCR of the combination it is used in
A11 · line 18
Eaton Bussmann FRS-R-30 → Mersen TRS30R

Mersen Tri-Onic TRS-R Class RK5 time-delay fuse 30 A, 600 V AC / 300 V DC, 200 kA AC / 20 kA DC IR

Exact match. Equal to your part on every attribute compared.

Matched (yours → alternate): Fuse class: RK5 · Ampere rating: 30 A · Voltage rating: 600 V · Time-delay / fast-acting: time-delay · Interrupting rating: 200 kA · DC voltage rating: 300 V · DC interrupting rating (kA): 20 kA · DC rating basis: published rating

Confirm on the catalog data:

  • fuse holder / clip fit

Other candidates, nearest first: Littelfuse FLSR030, FLSR030ID. Littelfuse FLSR030 and Littelfuse FLSR030ID are tied with TRS30R on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

A12 · line 19 · Spare fuse set
Mersen TRS30R → Eaton Bussmann FRS-R-30

Eaton Bussmann series Fusetron FRS-R Class RK5 dual-element time-delay fuse 30 A, 600 Vac / 300 Vdc, IR 200 kA AC / 20 kA DC

Exact match. Equal to your part on every attribute compared.

Matched (yours → alternate): Fuse class: RK5 · Ampere rating: 30 A · Voltage rating: 600 V · Time-delay / fast-acting: time-delay · Interrupting rating: 200 kA · DC voltage rating: 300 V · DC interrupting rating (kA): 20 kA · DC rating basis: published rating

Confirm on the catalog data:

  • fuse holder / clip fit

Other candidates, nearest first: Littelfuse FLSR030, FLSR030ID. Littelfuse FLSR030 and Littelfuse FLSR030ID are tied with FRS-R-30 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

A13 · line 20 · Spare motor protector
ABB MS132-10 → Allen-Bradley 140MT-C3E-C10

Allen-Bradley 140MT C-frame adjustable thermal / fixed magnetic MPCB (motor protective switching device), 6.3…10 A, normal break, magnetic trip 140 A

Nearest available, differs on interrupting rating (higher). No exact match was found; this one needs your approval.

Matched (yours → alternate): Poles: 3 · Trip type: thermal-magnetic · Adjustment range: 6.3–10 A · Interrupting rating: 65 kA @480 V → 65 kA @480 V / 30 kA @600 V (covers yours) · UL 508 Type E / Type F: UL 508 Type E (self-protected) · Slash vs straight voltage rating: this one is not slash-only where yours is straight (from the printed text)

Differs from your part:

  • instantaneous (magnetic) trip 140 A vs 150 A on your part

Confirm on the catalog data:

  • SCCR of the combination with its contactor
  • the link or mounting kit to its contactor
  • module width and mounting to your contactor — fit not compared

Other candidates, nearest first: Allen-Bradley 140MT-D9E-C10, 140MT-D9T-C10. Allen-Bradley 140MT-D9E-C10 and Allen-Bradley 140MT-D9T-C10 are tied with 140MT-C3E-C10 on every rating compared. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.

We'd like to talk.

Email orders@meisterlinecontrols.com