You sell the components. We scope, quote and manage the panel around them. Panel jobs you'd otherwise hand off stay with you, and so do the components on them.
A cross table from a distributor's request.
Parts Check (sample), lines 1–3 and 7 of 10
| Line | Tag | Qty / panel | Total | Part number | Description | Flag | Alternate |
|---|---|---|---|---|---|---|---|
| 1 | Main breaker | 1 | 2 | Schneider Electric (Square D) HDL36030 | Square D PowerPacT H-frame (150 A) molded case circuit breaker, 3-pole, 30 A, 600 Vac, D interrupting (25 kA @ 240 Vac, 18 kA @ 480 Vac, 14 kA @ 600 Vac), thermal-magnetic, lugs both ends, standard (80%) ratedLug / terminal kit: included | Lead timePotential lead time issue based on stock levels · checked 2026-11-01Published short-circuit rating on its own: 18 kA at 480 V | ABB XT2NU3030AFF000XXXNearest available, differs on interrupting rating (higher)equivalent for your team to approve, see A1Lead time: Potential lead time issue based on stock levels |
| 2 | M1 agitator drive | 1 | 2 | Siemens 6SL3210-5BE22-2UV0 | Siemens SINAMICS V20 basic converter 6SL3210-5BE22-2UV0, 2.2 kW / 3 hp, IL 5.6/4.8 A, IH 5.6/4.8 A, 380…480 V 3-phase AC, frame FSA, without integrated line filterdiscontinued | Discontinueddiscontinued; Siemens publishes 6SL3210-5BE22-2UV1 as the successorLead time: Potential lead time issue based on stock levels | Siemens 6SL3210-5BE22-2UV1published successor, see A2Lead time: Potential lead time issue based on stock levels |
| 3 | M2 motor protector | 1 | 2 | Allen-Bradley 140MT-C3E-B63 | Allen-Bradley 140MT C-frame adjustable thermal / fixed magnetic MPCB (motor protective switching device), 4…6.3 A, normal break, magnetic trip 88 A | —Stock not publishedPublished short-circuit rating on its own: 65 kA at 480 V | ABB MS132-6.3Nearest available, differs on interrupting rating (higher)equivalent for your team to approve, see A3 |
| 7 | Fuse holder | 1 | 2 | Eaton Bussmann CHCC2DU | Eaton Bussmann series CHCC Class CC modular DIN-Rail holder, 2-pole, without indication, 600 V, 30 A, SCCR 200 kA | Lead timePotential lead time issue based on stock levels · checked 2026-11-01 | No cross on file (we hold no cross rules for this kind of part) |
ABB SACE Tmax XT2N molded case circuit breaker, 3-pole, 30 A, TMF/TMD thermal-magnetic trip unit, 80% rated, 25 kA @ 480 V AC, front terminals (F)
Nearest available, differs on interrupting rating (higher). No exact match was found; this one needs your approval.
Matched (yours → alternate): Kind of product: circuit breaker · Poles: 3 · Trip curve / trip unit: thermal-magnetic · Trip rating: 30 A · Interrupting rating: 18 kA @480 V → 65 kA @240 V / 25 kA @480 V / 18 kA @600 V / 35 kA @250 V DC (2 poles in series) / 35 kA @500 V DC (3 poles in series) (covers yours) · Fixed vs adjustable trip: fixed trip
Confirm on the catalog data:
Other candidates, nearest first: ABB XT2SU3030AFF000XXX, XT2HU3030AFF000XXX, XT2LU3030AFF000XXX, XT2VU3030AFF000XXX. Each also covers your part on every rating compared; the further down the list, the further above your ratings it sits. They differ in details we did not compare (options, versions or ratings not on file), so check the one you prefer before approving it instead.
Siemens SINAMICS V20 basic converter 6SL3210-5BE22-2UV1, 2.2 kW / 3 hp, IL 5.6/4.8 A, IH 5.6/4.8 A, 380…480 V 3-phase AC, frame FSA, without integrated line filter
Siemens publishes this as the successor to your part.
Matched (yours → alternate): published by Siemens as the replacement · UL listing not confirmed from the catalog
ABB MS132 manual motor starter, thermal and magnetic protection, 4…6.3 A, Irm 78.8 A
Nearest available, differs on interrupting rating (higher). No exact match was found; this one needs your approval.
Matched (yours → alternate): Poles: 3 · Trip type: thermal-magnetic · Adjustment range: 4–6.3 A · Interrupting rating: 65 kA @480 V → 65 kA @480 V / 18 kA @600 V (covers yours) · UL 508 Type E / Type F: UL 508 Type E (self-protected) · Slash vs straight voltage rating: this one is not slash-only where yours is straight (from the printed text)
Differs from your part:
Confirm on the catalog data: