Part number reference · Overload relays

Overload relay cross reference: current ranges and part numbers

Meisterline Controls scopes and quotes UL 508A control panels. This page lines up overload relay current ranges from ABB, Allen-Bradley and Schneider Electric: for each published range, the smallest range on each line that fully covers it, with its trip class and the contactor frames it mounts to. Below that, how each line’s part numbers are built.

Current ranges side by side

A matching range is a starting point, not an equivalent. Trip class, reset mode, single-phase use and the contactor the relay mounts to all have to be checked before a relay can be substituted. Send the list and we’ll check it against your ratings, and quote the panel it goes into when you need one.

The range is the relay’s published current adjustment range in amperes, as printed in each catalog. There is one row for every range published on any of the three lines, so no brand is the anchor; rows run from the smallest range up, and the brand columns run alphabetically. Each brand cell names that line’s smallest range that fully covers the row’s range: its low end is at or below the row’s, and its high end is at or above it. “Smallest” means the lowest high end, then the narrowest range, judged against every range of that line. A relay is named only where its UL listing is stated in its own catalog. Trip class is as printed (an E marks ABB’s electronic trip classes). “Mounts to” lists the contactor frames the catalog names for that relay.

Reset mode isn’t a column, because it isn’t printed for every relay shown: the Square D NEMA section lists some Schneider Electric Class 20 relays without it. The reset modes ABB and Allen-Bradley print are given in their numbering sections below.

Siemens 3RU2 and 3RB and Eaton XT overload relays aren’t named in this table. Their catalogs don’t state a UL listing in the form this page uses: the word Listed, a UL file number with its category code, or a UL file number with the standard. Schneider Electric’s LR2K0321 (10–14 A) is printed “Not UL Listed” (Square D Digest 179, Section 17 page 9), so it isn’t named either.
Published rangeSmallest covering range: ABBSmallest covering range: Allen-BradleySmallest covering range: Schneider Electric (Square D)
0.1–0.13 A0.1–0.13 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.1–0.16 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D09…D38
0.1–0.16 A0.1–0.32 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.1–0.16 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D09…D38
0.1–0.32 A0.1–0.32 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.1–0.5 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
0.1–0.5 ANo range in our data covers this one0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.1–0.5 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
0.11–0.16 A0.1–0.32 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.11–0.16 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.13–0.17 A0.13–0.17 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.1–0.5 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
0.16–0.23 A0.1–0.32 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.16–0.23 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.16–0.25 A0.1–0.32 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.16–0.25 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D09…D38
0.17–0.23 A0.17–0.23 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.16–0.23 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.2–1 ANo range in our data covers this one0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
No range in our data covers this one
0.23–0.31 A0.23–0.31 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.23–0.36 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.23–0.36 ANo range in our data covers this one0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.23–0.36 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.25–0.4 ANo range in our data covers this one0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.25–0.4 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D09…D38
0.3–1 A0.3–1 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
No range in our data covers this one
0.31–0.41 A0.31–0.41 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.1–0.5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors
0.1–0.5 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
0.36–0.54 A0.3–1 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.36–0.54 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.4–0.63 A0.3–1 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.4–0.63 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D09…D38
0.4–2 ANo range in our data covers this oneNo range in our data covers this one0.4–2 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
0.41–0.55 A0.41–0.55 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.4–0.63 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D09…D38
0.54–0.8 A0.3–1 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.54–0.8 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.55–0.74 A0.55–0.74 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.54–0.8 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.63–1 A0.3–1 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.63–1 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
0.74–1 A0.74–1 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
0.2–1 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
0.63–1 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
0.8–1.2 A0.8–2.7 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
No range in our data covers this one0.8–1.2 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
0.8–2.7 A0.8–2.7 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
No range in our data covers this oneNo range in our data covers this one
1–1.3 A1–1.3 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1–1.6 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
1–1.6 A0.8–2.7 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1–1.6 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
1–5 ANo range in our data covers this one1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
No range in our data covers this one
1.2–1.8 A0.8–2.7 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.2–1.8 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
1.3–1.7 A1.3–1.7 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.2–1.8 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
1.6–2.5 A0.8–2.7 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.6–2.5 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
1.6–8 ANo range in our data covers this oneNo range in our data covers this one1.6–8 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
1.7–2.3 A1.7–2.3 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.6–2.5 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
1.8–2.6 A0.8–2.7 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.8–2.6 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
1.9–6.3 A1.9–6.3 A
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
No range in our data covers this one1.6–8 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
2–6.3 A2–6.3 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
No range in our data covers this one1.6–8 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
2.3–3.1 A2.3–3.1 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.6–8 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
2.5–4 A2–6.3 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
2.5–4 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
2.6–3.7 A2–6.3 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
2.6–3.7 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
3.1–4.2 A3.1–4.2 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
1–5 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
1.6–8 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
3.2–16 ANo range in our data covers this one3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
No range in our data covers this one
3.7–5.5 A2–6.3 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
3.7–5.5 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
4–6 A2–6.3 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
4–6 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
4.2–5.7 A4.2–5.7 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
4–6 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
5.4–27 ANo range in our data covers this one5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
No range in our data covers this one
5.5–8 ANo range in our data covers this one3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
5.5–8 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
5.7–7.6 A5.7–7.6 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
5.5–8 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
5.7–18.9 A5.7–18.9 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
No range in our data covers this one
6.4–32 ANo range in our data covers this oneNo range in our data covers this one6.4–32 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
7–10 A5.7–18.9 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
7–10 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
7.6–10 A7.6–10 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
7–10 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D09…D38
8–11.5 A5.7–18.9 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
8–11.5 A
TeSys K LR2K · Class 10 · mounts to 3-pole TeSys K contactors, screw-clamp terminals
9–13 A5.7–18.9 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
9–13 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D12…D38; LC1D/LC2D D40A…D65A
9–30 A9–30 A
EF45 · Class 10E, 20E, 30E selectable · mounts to AF26…AF38
No range in our data covers this one6.4–32 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
10–13 A10–13 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
9–13 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D12…D38; LC1D/LC2D D40A…D65A
11–55 ANo range in our data covers this one11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
No range in our data covers this one
12–18 A5.7–18.9 A
E16DU · Class 10E, 20E, 30E selectable · mounts to B6, B7
EF19 · Class 10E, 20E, 30E selectable · mounts to AF09…AF38, AFC09…AFC38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
12–18 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D18…D38; LC1D/LC2D D40A…D65A
13–16 A13–16 A
T16 · Class 10 · mounts to AS09…AS16, B6, B7, MC1, MC2
TF42 · Class 10 · mounts to AF09…AF38
3.2–16 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-E09…E16 / Bul. 300 Size 00…0; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 00 contactors; NEMA Size 0…2 contactors
12–18 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D18…D38; LC1D/LC2D D40A…D65A
13.2–66 ANo range in our data covers this one13.2–66 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
No range in our data covers this one
15–45 A15–45 A
EF45 · Class 10E, 20E, 30E selectable · mounts to AF26…AF38
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
No range in our data covers this one
16–20 A16–20 A
TF42 · Class 10 · mounts to AF09…AF38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
16–24 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D25…D38
16–24 A9–30 A
EF45 · Class 10E, 20E, 30E selectable · mounts to AF26…AF38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
16–24 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D25…D38
17–24 A9–30 A
EF45 · Class 10E, 20E, 30E selectable · mounts to AF26…AF38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
17–24 A
TeSys Deca bimetallic · Class 20 · mounts to LC1D/LC2D D25…D38
17–25 A 19–30 A
EF45 · Class 10E, 20E, 30E selectable · mounts to AF26…AF38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
17–25 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D40…D95
20–24 A20–24 A
TF42 · Class 10 · mounts to AF09…AF38
5.4–27 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C09…C23; 100-C30…C55; 100-E09…E16 / Bul. 300 Size 00…0; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
17–24 A
TeSys Deca bimetallic · Class 20 · mounts to LC1D/LC2D D25…D38
20–56 A20–56 A
EF65 · Class 10E, 20E, 30E selectable · mounts to AF40, AF52, AF65
EF96 · Class 10E, 20E, 30E selectable · mounts to AF80, AF96
13.2–66 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
No range in our data covers this one
20–100 ANo range in our data covers this one20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
No range in our data covers this one
22–28 A22–28 A
TF65 · Class 10 · mounts to AF40…AF65
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
6.4–32 A
TeSys Deca electronic · Class 5/10/20/30 selectable · mounts to LC1D/LC2D D09…D38
23–32 A15–45 A
EF45 · Class 10E, 20E, 30E selectable · mounts to AF26…AF38
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
23–32 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D25…D38; LC1D/LC2D D40A…D65A; LC1D/LC2D D40…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
24–29 A24–29 A
TF42 · Class 10 · mounts to AF09…AF38
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
23–32 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D25…D38; LC1D/LC2D D40A…D65A; LC1D/LC2D D40…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
25–33 A25–33 A
TF65 · Class 10 · mounts to AF40…AF65
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
No range in our data covers this one
25–70 A25–70 A
EF65 · Class 10E, 20E, 30E selectable · mounts to AF40, AF52, AF65
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
No range in our data covers this one
28–115 ANo range in our data covers this oneNo range in our data covers this one28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
29–35 A29–35 A
TF42 · Class 10 · mounts to AF09…AF38
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
30–38 A30–40 A
TF65 · Class 10 · mounts to AF40…AF65
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
30–38 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D32…D38
30–40 A30–40 A
TF65 · Class 10 · mounts to AF40…AF65
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
30–40 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D40A…D65A; LC1D/LC2D D40…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
30–150 ANo range in our data covers this one30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
No range in our data covers this one
35–38 A 235–38 A
TF42 · Class 10 · mounts to AF09…AF38
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
30–38 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D32…D38
36–47 A36–47 A
TF65 · Class 10 · mounts to AF40…AF65
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
36–100 A36–100 A
EF96 · Class 10E, 20E, 30E selectable · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
37–50 A20–56 A
EF65 · Class 10E, 20E, 30E selectable · mounts to AF40, AF52, AF65
EF96 · Class 10E, 20E, 30E selectable · mounts to AF80, AF96
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
37–50 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D40A…D65A; LC1D/LC2D D50…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
40–51 A40–51 A
TF96 · Class 10 · mounts to AF80, AF96
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
40–200 ANo range in our data covers this one40–200 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
44–53 A44–53 A
TF65 · Class 10 · mounts to AF40…AF65
11–55 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C30…C55; 100-E26…E38 / Bul. 300 Size 1; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 0…2 contactors
28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
48–60 A48–60 A
TF96 · Class 10 · mounts to AF80, AF96
13.2–66 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
48–65 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D40A…D65A; LC1D/LC2D D50…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
48–65 A25–70 A
EF65 · Class 10E, 20E, 30E selectable · mounts to AF40, AF52, AF65
13.2–66 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
48–65 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D40A…D65A; LC1D/LC2D D50…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
50–60 A50–60 A
TF65 · Class 10 · mounts to AF40…AF65
13.2–66 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-E40…E65 / Bul. 300 Size 2
48–65 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D40A…D65A; LC1D/LC2D D50…D95 (old D2-style D40…D65 without EverLink, and D80, D95)
54–150 A54–150 A
EF146 · Class 10E, 20E, 30E selectable · mounts to AF116, AF140, AF146
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
No range in our data covers this one
55–70 A25–70 A
EF65 · Class 10E, 20E, 30E selectable · mounts to AF40, AF52, AF65
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
55–70 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D65…D95
57–67 A57–67 A
TF65 · Class 10 · mounts to AF40…AF65
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
55–70 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D65…D95
57–68 A57–68 A
TF96 · Class 10 · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
55–70 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D65…D95
57–225 ANo range in our data covers this oneNo range in our data covers this one57–225 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
60–100 A36–100 A
EF96 · Class 10E, 20E, 30E selectable · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
60–100 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
60–300 ANo range in our data covers this one60–300 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 5 contactors
No range in our data covers this one
63–80 A36–100 A
EF96 · Class 10E, 20E, 30E selectable · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
63–80 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D65…D95
63–210 A63–210 A
EF205 · Class 10E, 20E, 30E selectable · mounts to AF145, AF185, AF190, AF205
60–300 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 5 contactors
57–225 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
65–78 A65–78 A
TF96 · Class 10 · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
63–80 A
TeSys Deca bimetallic · Class 10 or 20 · mounts to LC1D/LC2D D65…D95
66–90 A66–90 A
TF140DU · Class 10A · mounts to AF116…AF140
TA200DU · Class 10A · mounts to AF190…AF205
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
60–100 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
75–87 A75–87 A
TF96 · Class 10 · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
60–100 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
80–104 A80–110 A
TF140DU · Class 10A · mounts to AF116…AF140
TA200DU · Class 10A · mounts to AF190…AF205
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
80–104 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D95; LC1D/LC2D D115A…D150A
80–110 A80–110 A
TF140DU · Class 10A · mounts to AF116…AF140
TA200DU · Class 10A · mounts to AF190…AF205
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
28–115 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
80–400 ANo range in our data covers this one80–400 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
84–96 A84–96 A
TF96 · Class 10 · mounts to AF80, AF96
20–100 A
E100 193-1EE · Class 10/20 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 193-1EF · Class 10/15/20/30 selectable · mounts to 100-C60…C97; 100-E80…E96 / Bul. 300 Size 3; panel or DIN rail with pass-thru wiring, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 3 contactors
60–100 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
90–150 A54–150 A
EF146 · Class 10E, 20E, 30E selectable · mounts to AF116, AF140, AF146
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
90–150 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
95–120 A54–150 A
EF146 · Class 10E, 20E, 30E selectable · mounts to AF116, AF140, AF146
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
95–120 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D115A…D150A
100–135 A100–135 A
TF140DU · Class 10A · mounts to AF116…AF140
TA200DU · Class 10A · mounts to AF190…AF205
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
90–150 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
100–500 ANo range in our data covers this one100–500 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
110–140 A110–142 A
TF140DU · Class 10A · mounts to AF116…AF140
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
110–140 A
TeSys Deca bimetallic · Class 10 · mounts to LC1D/LC2D D150A
110–142 A110–142 A
TF140DU · Class 10A · mounts to AF116…AF140
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
90–150 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
110–150 A110–150 A
TA200DU · Class 10A · mounts to AF190…AF205
30–150 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
E100 592-1EF · Class 10/15/20/30 selectable · mounts to NEMA Size 4 contactors
90–150 A
TeSys Deca electronic · Class 10 or 10/20 selectable or 20 · mounts to LC1D/LC2D D115A…D150A
115–380 A115–380 A
EF370 · Class 10E, 20E, 30E selectable · mounts to AF210, AF260, AF265, AF300, AF305, AF370
80–400 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
120–600 ANo range in our data covers this one120–600 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
125–500 ANo range in our data covers this one100–500 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
125–500 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G265…500
130–175 A130–175 A
TA200DU · Class 10A · mounts to AF190…AF205
40–200 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
57–225 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
150–200 A150–200 A
TA200DU · Class 10A · mounts to AF190…AF205
40–200 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
57–225 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G115…225
150–500 A150–500 A
EF460 · Class 10E, 20E, 30E selectable · mounts to AF400, AF460
100–500 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
125–500 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G265…500
160–630 ANo range in our data covers this one160–800 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
160–630 A
TeSys Giga LR9G · Class 5/10/20/30 selectable · mounts beneath LC1G630
160–800 ANo range in our data covers this one160–800 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
250–800 A250–800 A
EF750 · Class 10E, 20E, 30E selectable · mounts to AF580, AF750
160–800 A
E100 193-1EF · Class 10/15/20/30 selectable · mounts to panel, with external current transformers, all contactors
No range in our data covers this one
375–1250 A375–1250 A
EF1250DU · Class 10E, 20E, 30E selectable · mounts to AF1350, AF1650, AF2050
No range in our data covers this oneNo range in our data covers this one
1
Schneider's LRD325, LR3D325 and LRD325L, for the LC1D40A through LC1D65A, are not named in this row. Square D prints their range as 17–25 A in Section 17 page 12 and as 16–25 A in Section 16 page 16. The 17–25 A relays named here are the LC1D40 through LC1D95 versions.
2
ABB prints the TF42-38 range as "35.0 … 38.0/40.0" on page 764 without saying what the 40.0 applies to. This row uses 35–38 A.

Ranges, trip classes and mounting: ABB main catalog 1SBC100214C0202 Rev D (2024-02), pages 758, 760, 764, 769, 773, 777, 781, 785, 790, 795 and 799, with the UL file per type on pages 998–999. Allen-Bradley: Rockwell 193-TD013D (2023-10), pages 5–7, UL on page 9. Schneider Electric: Square D Digest 179, Section 17 (2026-08), pages 12–13, UL on page 12, TeSys K on page 9 (UL file and category NLDX in the page’s file box) and TeSys Giga on page 14; Section 16 (2026-09), pages 16 and 122–123; and the TeSys catalog MKTED210011EN (2026-08) page 894 for the Giga cULus mark. Siemens and Eaton overload relays aren’t named in this table. Their catalogs print ratings for these relays, and Meisterline Controls names a relay only where the catalog states the UL listing. Siemens and Eaton overload relays are covered through our Parts Check.

An overload relay mounts to particular contactor frames. A range on another line that covers yours may mount to a different contactor, or need a separate mounting kit or a panel-mount version. When a relay changes lines, the contactor usually has to be checked with it. The “mounts to” entries above are the frames each catalog names.
Single-phase use differs by line and by version. ABB marks its TF and T16 thermal relays suitable for single-phase use and its EF and E16DU electronic relays not suitable (main catalog p.758). Schneider Electric offers TeSys Deca bimetallic relays with and without single-phase sensitivity, as separate part numbers (Section 17 p.12). Allen-Bradley lists the E100 as single- and three-phase devices (193-TD013D pp.6–7). Check single-phase use before substituting a relay on a single-phase or DC load.

How each line’s part numbers are built

Each section uses only that line’s own catalog, with the page for every code. Where two pages of the same catalog disagree, the item is left out and noted.

ABB TF, T16, TA and EF

Format: type-top of setting range, for example TF42-10. Source: ABB main catalog 1SBC100214C0202 Rev D (2024-02). ABB doesn’t print a numbering key for overload relays. The meanings below are the headings and columns of the ordering tables each type appears in, with the page. Each type also has a separate ABB order code (for example 1SAZ721201R1043), printed beside it.

Type (before the dash)

TypeKindSetting rangesTrip classSuitable forPage
T16Thermal0.10–16.0 A10AS09…AS16, B6, B7, MC1 and MC2p.760
TF42Thermal0.10–38.0 A10AF09…AF38p.764
TF65Thermal22.0–67.0 A10AF40…AF65p.769
TF96Thermal40.0–96.0 A10AF80, AF96p.773
TF140DUThermal66–142 A10AAF116…AF140p.777
TA200DUThermal66–200 A10AAF190…AF205p.781
E16DUElectronic0.10–18.9 A10E, 20E, 30E selectableB6 and B7p.785
EF19Electronic0.10–18.9 A10E, 20E, 30E selectableAF09…AF38 / AFC09…AFC38p.785
EF45Electronic9.00–45.0 A10E, 20E, 30E selectableAF26…AF38p.758; p.785 prints it for EF45-30
EF65Electronic20–70 A10E, 20E, 30E selectableAF40, AF52, AF65p.790
EF96Electronic20–100 A10E, 20E, 30E selectableAF80, AF96p.790
EF146Electronic54–150 A10E, 20E, 30E selectableAF116, AF140, AF146p.790
EF205Electronic63–210 A10E, 20E, 30E selectableAF145, AF185, AF190, AF205p.795
EF370Electronic115–380 A10E, 20E, 30E selectableAF210, AF260, AF265, AF300, AF305, AF370p.795
EF460Electronic, external current transformer150–500 A10E, 20E, 30E selectableAF400, AF460p.799
EF750Electronic, external current transformer250–800 A10E, 20E, 30E selectableAF580, AF750p.799
EF1250DUElectronic, external current transformer375–1250 A10E, 20E, 30E selectableAF1350, AF1650, AF2050p.799

Reset: every type above prints “Manual or automatic reset selectable” (thermal, pp.760–781) or “automatic or manual reset selectable” (electronic, pp.785–799).

ABB's type overview on page 758 and its ordering pages list different contactors for several overload types. The T16 gains the AS09 through AS16 on page 760. The E16DU is given as B6 and B7 on page 785, with BC6, BC7, VB6, VB7, VBC6 and VBC7 added on page 758. The EF750 is given as AF580 and AF750 on page 799, with the AF1250 added on page 758.

This table follows the ordering pages, except for the EF45, where page 785 prints a suitable frame range for the EF45-30 and none for the EF45-45; page 758 is used there instead.

After the dash

SegmentMeaningPage
-10, -0.13, -1250 …The top of the setting range: TF42-10 is set 7.60 … 10.0 A; EF1250DU-1250 is set 375 … 1250 Ap.764, p.799
-V1000ATEX variant (TF140DU and TA200DU), same setting rangesp.777, p.781

One number, segment by segment

SegmentValueMeaningPage
TypeTF42TF42 thermal overload relay, trip class 10, suitable for AF09…AF38 contactorsp.764
Top of setting range10Setting range 7.60 … 10.0 Ap.764

TF42-10 is ABB order code 1SAZ721201R1043 (p.764).

Allen-Bradley E100

Format: bulletin-1typerange codecontactor code[-height], for example 193-1EFDB. Source: Rockwell technical data 193-TD013D (2023-10). Rockwell prints a catalog number explanation on page 5 and notes that “not all combinations produce a valid catalog number”; the valid numbers are listed on pages 6 and 7. The key doesn’t give a meaning for the 1 after the dash.

Bulletin and type

CodeMeaningPage
193IEC overload relayp.5
592NEMA overload relayp.5
EEBasic: trip class 10 or 20, manual reset only. Bulletin 193 only.p.5, p.6
EFAdvanced: trip class 10, 15, 20 or 30, manual or automatic resetp.5, p.7

Adjustment range code

CodeRangeCodeRange
A0.1…0.5 AH30…150 A
B0.2…1.0 AJ40…200 A
C1.0…5.0 AK60…300 A
D3.2…16 AL100…500 A
E5.4…27 AM120…600 A
F11…55 AN160…800 A
G20…100 AQ13.2…66 A
W80…400 A

p.5.

Contactor and mounting code

CodeBulletin 193 (IEC)Bulletin 592 (NEMA)Page
B100-C09…C23p.5
CBulletin 500 NEMA Size 0…2p.5
D100-C30…C55Bulletin 500 NEMA Size 3p.5
E100-C60…C97Bulletin 500 NEMA Size 4p.5
F100-E09…E16, Bulletin 300 Size 00…0Bulletin 500 NEMA Size 5p.5
G100-E26…E38, Bulletin 300 Size 1p.5
H100-E40…E65, Bulletin 300 Size 2p.5
J100-E80…E96, Bulletin 300 Size 3p.5
TBulletin 500 NEMA Size 00p.5
PIntegrated panel / DIN rail mount and pass-thru wiring, built-in current transformer, all contactorsp.5, p.6
ZPanel mount with external current transformers (customer supplied), all contactorsp.5, p.7
-X1Reduced standoff height, 1-9/16 in (39.7 mm), for height-restricted Type 7 and 9 explosion-proof enclosures; 592 NEMA Size 4 on p.7p.5, p.7

The same letter means a different contactor on the two bulletins: D, E and F name IEC contactors on Bulletin 193 and NEMA sizes on Bulletin 592.

One number, segment by segment

SegmentValueMeaningPage
Bulletin193IEC overload relayp.5
Type1EFAdvanced: trip class 10, 15, 20 or 30, manual or automatic resetp.5, p.7
Adjustment rangeD3.2…16 Ap.5
ContactorB100-C09…C23p.5
Height(none)Standard heightp.5

193-1EFDB is listed as a catalog number on p.7.

Schneider Electric TeSys Deca, K and Giga

Format: LRD / LR3D / LR2D + range number + [L] + [6], for example LRD14L. Sources: Square D Digest 179, Section 17 (2026-08), Table 17.25 on page 12 and Tables 17.26–17.27 on page 13; and Section 16 (2026-09), page 122. The Digest doesn’t print an overall numbering key. The prefixes come from the table columns, and the L, the 6 and the range number from the notes on Section 16 page 122.

Prefix (bimetallic, Table 17.25)

PrefixMeaningPage
LRDAmbient-compensated bimetallic relay with single-phase sensitivitySec. 17 p.12
LR3DAmbient-compensated bimetallic relay without single-phase sensitivitySec. 17 p.12
LR2DClass 20 with single-phase sensitivity, in the rows for LC1D40…D95 (for example LR2D3522)Sec. 17 p.12

Range number and suffixes

CodeMeaningPage
01 … 35Range number, called the “Number Suffix”: 01 = 0.10–0.16 A, 10 = 4–6 A, 14 = 7–10 A, 32 = 23–32 A, for LC1D09…D38. Each row of Table 17.25 pairs the range with the contactor frames.Sec. 16 p.122; Sec. 17 p.12
313 … 365Ranges for LC1D40A…D65A (for example LRD313 = 9–13 A)Sec. 17 p.12
3322 … 3365Ranges for LC1D40…D95; 3353, 3355, 3357 and 3359 mount to the old D2-style D40…D65 (no EverLink terminations) and to D80 and D95 onlySec. 17 p.12, note [13]
4365, 4367, 436980–104, 95–120 and 110–140 A, for LC1D115A…D150ASec. 17 p.12
LTrip class 20. “For tripping class 10: with screw termination, remove the L from the end of the above part number.”Sec. 16 p.122
6Ring tongue connector: “With a ring tongue connector, change the L6 to 6” for class 10 (LRD326 is Class 10, 23–32 A)Sec. 16 p.122

Electronic relays (LR9D)

CodeMeaningPage
LR9D01 / 02 / 08 / 320.1–0.5, 0.4–2, 1.6–8 and 6.4–32 A; Class 5/10/20/30 selectable; direct mounting beneath LC1D/LC2D D09…D38Sec. 17 p.13
LR9D5367 / 536960–100 / 90–150 A, Class 10, beneath LC1D115A…D150ASec. 17 p.13
LR9D5567 / 556960–100 / 90–150 A, Class 20Sec. 17 p.13
LR9D67 / 6960–100 / 90–150 A, Class 10/20 selectableSec. 17 p.13

Several TeSys Deca items are printed differently in Square D's two Digest sections, so they are left off this table:

  • The LRD325, LR3D325 and LRD325L print as 17–25 A in Section 17 page 12 and 16–25 A in Section 16 page 16.
  • Class 20 at 0.40–0.63 A — the LRD04L, LR3D04L and their 6 versions — are listed on Section 16 pages 122 and 123, and shown as a dash on Section 17 page 12 and Section 16 page 16.
  • The LR3D05L and LR3D06L are listed on Section 16 page 123 and shown as a dash on page 122 and Section 17 page 12.

Section 17 page 12 also prints the LR3D21L in the 9–13 A Class 20 cell, where Section 16 prints the LR3D16L.

TeSys K (LR2K) and TeSys Giga (LR9G)

CodeMeaningPage
LR2K03 + range numberTeSys K thermal overload relay, Class 10, manual or automatic reset, for 3-pole TeSys K contactors with screw-clamp terminals: 01 = 0.11–0.16 A, 02 = 0.16–0.23 A, 03 = 0.23–0.36 A, 04 = 0.36–0.54 A, 05 = 0.54–0.8 A, 06 = 0.8–1.2 A, 07 = 1.2–1.8 A, 08 = 1.8–2.6 A, 10 = 2.6–3.7 A, 12 = 3.7–5.5 A, 14 = 5.5–8 A, 16 = 8–11.5 A. LR2K0321 (10–14 A) is printed “Not UL Listed” (note [5]).Sec. 17 p.9, Table 17.16
LR9G115 / 225TeSys Giga electronic relay, 28–115 / 57–225 A, Class 5/10/20/30 selectable, mounting beneath LC1G115…225Sec. 17 p.14
LR9G500 / 630125–500 A beneath LC1G265…500; 160–630 A beneath LC1G630Sec. 17 p.14

One number, segment by segment

SegmentValueMeaningPage
PrefixLRDBimetallic, with single-phase sensitivitySec. 17 p.12
Range number147–10 A, direct mounting to LC1D/LC2D D09…D38Sec. 17 p.12; Sec. 16 p.122
Class suffixLTrip class 20 (LRD14 without the L is Class 10)Sec. 17 p.12; Sec. 16 p.122
Terminal suffix(none)Screw termination (LRD14L6 is the ring tongue version)Sec. 16 p.122