Part number reference · Molded case circuit breakers

Fixed-trip molded case breaker cross reference by trip rating

Meisterline Controls scopes and quotes UL 508A control panels. This page lines up fixed-trip UL 489 molded case circuit breakers from ABB, Allen-Bradley, Eaton, Schneider Electric and Siemens by trip rating, lists each frame’s interrupting rating at 480 V, and shows how each line’s part numbers are built, with the catalog page for each.

Trip ratings side by side

A matching trip rating is a starting point, not an equivalent. Interrupting rating at your voltage, voltage rating (including slash ratings such as 480Y/277 V), pole count, terminals and lugs, and any series or combination rating all have to be checked before a breaker can be substituted. Send the list and we’ll check it against your ratings.

Scope: fixed-trip breakers only. Adjustable-trip breakers go through our Parts Check, where the setting is confirmed.

Trip ratingABB Record Plus, Tmax XTAllen-Bradley 140G frameEaton Power Defense, Series GSchneider Electric (Square D) PowerPacTSiemens 3VA5
15 AFB100 / XT1 / XT2140G-G / 140G-HPD-1 / PD-2 / EGB-frame3VA51
16 ANot in the FB100 or Tmax XT TMF ranges140G-G / 140G-HNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame rangesNot in the 3VA5 fixed-thermal ranges
20 AFB100 / XT1 / XT2140G-G / 140G-HPD-1 / PD-2 / EGB-frame3VA51
25 AFB100 / XT1 / XT2 / XT4140G-G / 140G-H / 140G-JPD-1 / PD-2 / EGB-frame3VA51
30 AFB100 / XT1 / XT2 / XT4140G-G / 140G-H / 140G-JPD-1 / PD-2 / EGB-frame3VA51
32 ANot in the FB100 or Tmax XT TMF ranges140G-G / 140G-H / 140G-JNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame rangesNot in the 3VA5 fixed-thermal ranges
35 AFB100 / XT1 / XT2 / XT4140G-G / 140G-H / 140G-JPD-1 / PD-2 / EGB-frame3VA51
40 AFB100 / XT1 / XT2 / XT4140G-G / 140G-H / 140G-JPD-1 / PD-2 / EGB-frame3VA51 / 3VA52
45 AFB100 / XT1140G-GPD-1 / PD-2 / EGB-frame3VA51 / 3VA52
50 AFB100 / XT1 / XT2 / XT4140G-G / 140G-H / 140G-JPD-1 / PD-2 / EGB-frame3VA51 / 3VA52
60 AFB100 / XT1 / XT2 / XT3 / XT4140G-G / 140G-H / 140G-I / 140G-JPD-1 / PD-2 / EGB-frame3VA51 / 3VA52
63 ANot in the FB100 or Tmax XT TMF ranges140G-G / 140G-H / 140G-I / 140G-JNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame rangesNot in the 3VA5 fixed-thermal ranges
70 AFB100 / XT1 / XT2 / XT3 / XT4140G-G / 140G-H / 140G-I / 140G-JPD-1 / PD-2 / EGB-frame / Q-frame3VA51 / 3VA52
80 AFB100 / XT1 / XT3 / XT4140G-G / 140G-IPD-1 / PD-2 / EGB-frame / Q-frame3VA51 / 3VA52
90 AFB100 / XT1 / XT3 / XT4140G-G / 140G-IPD-1 / PD-2 / EGB-frame / Q-frame3VA51 / 3VA52
100 AFB100 / XT1 / XT3 / XT4140G-G / 140G-IPD-1 / PD-2 / PD-3 / EGB-frame / Q-frame3VA51 / 3VA52
110 AXT1 / XT3 / XT4140G-G / 140G-IPD-1 / PD-2 / EGB-frame / Q-frame3VA51 / 3VA52
125 AXT1 / XT3 / XT4140G-G / 140G-IPD-1 / PD-2 / PD-3 / EGB-frame / Q-frame3VA51 / 3VA52
150 AXT3 / XT4140G-IPD-2 / PD-3Q-frame3VA52
160 ANot in the FB100 or Tmax XT TMF ranges140G-INot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame rangesNot in the 3VA5 fixed-thermal ranges
175 AXT3 / XT4140G-IPD-2 / PD-3Q-frame3VA52
200 AXT3 / XT4140G-IPD-2 / PD-3Q-frame3VA52 / 3VA53
225 AXT3 / XT4140G-IPD-2 / PD-3Q-frame3VA52 / 3VA53
250 AXT4Not in the 140G fixed-trip rangesPD-3Q-frame3VA52 / 3VA53
300 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-3 / PD-4Not in the B- or Q-frame ranges3VA53
350 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-3 / PD-4Not in the B- or Q-frame ranges3VA53
400 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-3 / PD-4Not in the B- or Q-frame ranges3VA53
450 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-4Not in the B- or Q-frame ranges3VA54
500 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-3 / PD-4Not in the B- or Q-frame ranges3VA54
600 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-3 / PD-4Not in the B- or Q-frame ranges3VA54 / 3VA55
700 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-4Not in the B- or Q-frame ranges3VA55
800 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesPD-4Not in the B- or Q-frame ranges3VA55 / 3VA57
900 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA57
1000 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA57
1200 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA57
1400 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA58
1600 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA58
1800 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA59
2000 ANot in the FB100 or Tmax XT TMF rangesNot in the 140G fixed-trip rangesNot in the Power Defense or EG fixed-trip rangesNot in the B- or Q-frame ranges3VA59

“Not in the … range” means that line’s catalog prints no fixed-trip, UL-listed breaker at that rating in the frames shown. A larger or adjustable-trip breaker from the same line may exist; those go through the Parts Check. Allen-Bradley 16, 32, 63 and 160 A appear as printed in Rockwell’s tables (pp.33, 37, 42, 46–47); Eaton prints 16, 32, 63 and 160 A for the EG as well but marks them “not UL listed ratings” (V4-T2-171 to 175), and Power Defense prints none of them, so they aren’t shown for Eaton.

Trip rating is the breaker’s continuous ampere rating as printed in the catalog’s selection table. A breaker counts as fixed-trip here only where its own catalog prints the overload (thermal) trip as fixed: ABB “TE = Fixed Thermal Magnetic” (Record Plus) and TMF, with the overload threshold and trip time both “Fixed” (Tmax XT catalog p.61), Allen-Bradley protection type C “Fixed thermal/fixed magnetic”, Eaton Power Defense TFF “Fixed Thermal / Fixed Magnetic” and TFA “Fixed thermal / Adjustable magnetic” (V4-T2-23, 31, 44, 58) and Series G “FF = Fixed fixed”, Square D “Fixed … thermal-magnetic protection”, and Siemens TM210 FTFM (fixed thermal, fixed magnetic) and TM230 FTAM (fixed thermal, adjustable magnetic). Eaton’s VFF and VFA (50 °C) trip units are marked “non UL” and aren’t shown. One row per trip rating; each cell names the frames of that line printed with a fixed-trip breaker at exactly that rating. Lines are in alphabetical order. Poles, voltage and interrupting ratings for each frame are in the frame table below.

UL: only UL 489 circuit breakers whose catalog states the UL listing appear. ABB: “UL489/cUL489 Listed” (BuyLog p.6-7); Tmax XT “comply with UL489 and CSA C22.2 Standards (E116596; E116595; E93565)” (Tmax XT catalog p.16), a UL file number with the standard. Allen-Bradley: “UL Listed” (140G-TD101 pp.19, 31). Eaton: Power Defense “UL 489” (V4-T2-6) and “UL File Number E7819” for each frame (V4-T2-12, 15), a UL file number with the standard; EG “UL and CSA listed: Yes”, to 125 A (V4-T2-165). Square D: “UL listed interrupting ratings” (B-frame, Digest Sec07 p.7-34) and “cULus” (Q-frame, p.7-41). Siemens: “All 3VA5 thermal-magnetic trip and 3VA6 electronic trip circuit breakers are UL listed for reverse feed applications” (Sect17 p.17/6), with the same statement for each 3VA5 frame. Supplementary protectors (UL 1077) are a different product and aren’t listed here.

Frames: poles, voltage and interrupting rating

Interrupting rating is the UL 489 rating in kA rms symmetrical at 480 V AC, by the line’s own interrupting code, for multi-pole breakers. 480 V is the voltage printed for most frames on this page; the one frame without it is a 240 V breaker, and that cell says so. Where 1-pole versions carry no 480 V rating, the cell says so.

Line and frameFixed-trip ratings (A)PolesMaximum AC voltagekA at 480 V, by interrupting codeCatalog pages
ABB Record Plus FB10015, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 1001, 2, 3600/347 V (1-pole: 347 V)FBV 35 · FBN 65 · FBH 100 · FBL 150. 1-pole: no 480 V rating printed.BuyLog pp.6-178 to 6-181
ABB Tmax XT1 (125 A)15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 1253, 4600Y/347 VN 25 · S 35 · H 65Tmax XT pp.61, 248–249
ABB Tmax XT2 (125 A)15, 20, 25, 30, 35, 40, 50, 60, 70 (80 A and up are TMA, adjustable thermal)3, 4600 VN 25 · S 35 · H 65 · L 100 · V 150 · X 200Tmax XT pp.61, 250–268
ABB Tmax XT3 (225 A)60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 2253, 4600Y/347 VN 25 · S 35Tmax XT pp.61, 246, 272; BuyLog p.6-95
ABB Tmax XT4 (250 A)25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 (80 A and up: 3-pole only)3, 4600 VN 25 · S 35 · H 65 · L 100 · V 150 · X 200Tmax XT pp.61, 274–296
Allen-Bradley 140G frame G (125 A)15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63, 70, 80, 90, 100, 110, 1253, 4600Y/347 VG2 25 · G3 35 · G6 65140G-TD101 pp.32–33
Allen-Bradley 140G frame H (125 A)15, 16, 20, 25, 30, 32, 35, 40, 50, 60, 63, 70 (80 A and up are adjustable thermal)3, 4 (current-limiting HC: 3)600 VH2 25 · H3 35 · H6 65 · H0 100 · H15 150140G-TD101 pp.34–37
Allen-Bradley 140G frame I (225 A)60, 63, 70, 80, 90, 100, 110, 125, 150, 160, 175, 200, 2253, 4600Y/347 VI2 25 · I3 35140G-TD101 pp.41–42
Allen-Bradley 140G frame J (250 A)25, 30, 32, 35, 40, 50, 60, 63, 70 (80 A and up are adjustable thermal)3, 4 (current-limiting JC: 3)600 VJ2 25 · J3 35 · J6 65 · J0 100140G-TD101 pp.43–47
Eaton Power Defense PD-1 (125 A)TFF: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 1251, 2, 3, 4 (N and P: 3, 4)600Y/347 V (interrupting table, V4-T2-22; the technical data, V4-T2-12, prints 600/347 V)C 18 · F 25 · G 35 · K 50 · M 65 · N 85 · P 100. 1-pole: rated at 277 V, no 480 V rating.V4-T2-12, 22, 23
Eaton Power Defense PD-2 (225 A)TFF: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 (1-pole: to 150)1, 2, 3, 4600 VF 25 · G 35 · K 50 · M 65 · N 85 · P 100. 1-pole: rated at 277 V, no 480 V rating.V4-T2-12, 30, 31
Eaton Power Defense PD-3 (400 A and 600 A constructions)TFA: 100, 125, 150, 175, 200, 225, 250, 300, 350, 400, 500, 6002 (in a 3-pole frame), 3, 4600 VF 25 · G 35 · K 50 · M 65 · N 85 · P 100V4-T2-15, 43, 44
Eaton Power Defense PD-4 (800 A)TFA: 300, 350, 400, 450, 500, 600, 700, 8002 (in a 3-pole frame), 3, 4600 VG 35 · K 50 · M 65V4-T2-15, 58
Eaton Series G EG15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125. 110 A: EGB, and the EGS and EGH bolt-on versions.1, 2, 3, 4 (EGE: 2–4; EGC: 3, 4)600Y/347 VEGB 18 · EGE 25 · EGS 35 · EGH 65 · EGC 100. 1-pole: no 480 V rating printed.V4-T2-163, 165, 170–177
Schneider Electric (Square D) PowerPacT B-frame (125 A)15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125 (BK: 15–30)1, 2, 3, 4 (BK: 1, 2)600Y/347 VBD 18 · BG 35 · BJ 65 · BK 65 (2-pole). 1-pole: rated at 277 V (480Y/277 V on I-Line versions only).Digest Sec07 pp.7-34, 7-35
Schneider Electric (Square D) PowerPacT Q-frame (250 A)70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 2502, 3240 V240 V breaker: no 480 V rating. At 240 V: QB 10 · QD 25 · QG 65 · QJ 100 (3-pole QJ: 208Y/120 V only).Digest Sec07 p.7-41
Siemens 3VA51 (125 A)15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125 (FTFM and FTAM)FTFM: 1, 1-in-2, 2, 3, 4. FTAM: 3, 4600Y/347 VS 25 · M 35 · H 65. 1-pole and 1-in-2-pole: no 480 V rating printed.Sect17 pp.17/14–17/18
Siemens 3VA52 (250 A)FTFM 40–250; FTAM 70–250 (40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250)2 (in a 3-pole frame), 3, 4600 VM 35 · H 65 · C 100Sect17 pp.17/24–17/27
Siemens 3VA53 (400 A)FTAM: 200, 225, 250, 300, 350, 4002 (in a 3-pole frame), 3, 4600 VM 35 · H 65 · C 100Sect17 pp.17/32–17/33
Siemens 3VA54 (600 A)FTAM: 450, 500, 6002 (in a 3-pole frame), 3, 4600 VM 35 · H 65 · C 100Sect17 p.17/37
Siemens 3VA55 (800 A)FTAM: 600, 700, 8002 (in a 3-pole frame), 3, 4600 VM 35 · H 65 · C 100Sect17 p.17/41
Siemens 3VA57 (1200 A)FTAM: 800, 900, 1000, 12002 (in a 3-pole frame), 3600 VM 35 · H 65 · C 100Sect17 p.17/47
Siemens 3VA58 (1600 A)FTAM: 1400, 16003600 VM 35 · H 65 · C 100Sect17 p.17/51
Siemens 3VA59 (2000 A)FTAM: 1800, 20003600 VM 35 · H 65 · C 100Sect17 p.17/55

Siemens prints “UL listed” for every 3VA5 frame, but never prints the standard number against it. Only the 3VA6 text names UL 489.

The 3VA5 is on this page on that listing statement. If your submittal needs the standard number, ask Siemens for it in writing.

Ratings: ABB US BuyLog Section 6, 9AKK108467A9438 (2026-10), pages 6-7 and 6-178 to 6-181, and SACE Tmax XT UL/CSA catalog 1SDC210200D0206 (2024-08), PDF pages 16, 61 and 248–296. Allen-Bradley: Rockwell 140G-TD101E-EN-P (2025-08), pages 19, 31–37 and 41–47. Eaton: Volume 4 Tab 2, CA08100005E (2026-04), pages V4-T2-6, 12, 15, 22, 23, 30, 31, 43, 44, 58, 163, 165 and 170–177. Schneider Electric: Square D Digest 179, Section 07 (2026-09), pages 7-33 to 7-35 and 7-41. Siemens: Industrial Controls catalog Section 17 (2026-02), pages 17/6, 17/14 to 17/18, 17/24 to 17/27, 17/32, 17/33, 17/37, 17/41, 17/47, 17/51 and 17/55.

ABB Formula isn’t named in this table: its catalog marks the order-code tables only “(UL and IEC)” (BuyLog pp.6-50 to 6-52), with no UL file number or standard, and Meisterline Controls names a breaker only where the catalog states the UL listing. Lines whose catalogs don’t print the trip as fixed or adjustable (Square D H-, J- and LA/LH-frame thermal-magnetic, Eaton Series C, ABB TEY and E150, Siemens Sentron and BQ) are covered through our Parts Check. Miniature plug-on and bolt-on panelboard breakers, such as ABB Q-Line, aren’t covered on this page.

ABB prints the Tmax XT3S at 35 kA at 480 V in the Tmax XT ordering-code key (p.246, “S … 35” for XT3) and in BuyLog Section 6 (p.6-95, “S (35kA)”). The XT3S ordering table on Tmax XT p.272 heads its rating column “25kA”, the same as the XT3N table above it. This page uses 35 kA, the value printed in both of the other places.

Several lines are not on this page because their catalogs do not print the trip as fixed. The Square D H-frame prints a fixed alternating current magnetic trip with factory-sealed trip units and does not state the thermal trip; the J-frame and the LA and LH print an adjustable magnetic trip without stating the thermal. Eaton Series C prints non-interchangeable trip units, with fixed thermal and adjustable magnetic appearing only in the J and L trip unit keys rather than against the complete breakers. The ABB TEY and E150 print non-interchangeable trip. The Siemens Sentron and BQ do not state it.

This page covers fixed-trip breakers. Send any of the lines above through our Parts Check.

Eaton Series G (EG): the brand is phasing this line down. It stays on this page so a breaker already in a panel can be found.
“Fixed-trip” covers two kinds of trip unit. Fixed thermal, fixed magnetic: nothing on the breaker is set. Fixed thermal, adjustable magnetic (Siemens TM230 FTAM, Sect17 p.17/15): the continuous rating is fixed and the instantaneous pickup is set on the breaker. Both are in the table; Eaton Power Defense PD-3 and PD-4 are fixed thermal, adjustable magnetic (TFA, V4-T2-44, 58). On the Allen-Bradley 140G H and J frames, the same frame is fixed (protection code C) up to 70 A and adjustable thermal (code F) from 80 A (140G-TD101 pp.37, 44, 46), so read the protection code, not just the frame.
Voltage ratings are printed two ways. ABB FB100, ABB Tmax XT1 and XT3, Allen-Bradley 140G G and I frames, Eaton Power Defense PD-1, Eaton EG, Square D B-frame and Siemens 3VA51 are printed with a slash rating such as 600Y/347 V or 600/347 V; Allen-Bradley 140G H and J frames, ABB Tmax XT2 and XT4, Eaton Power Defense PD-2 to PD-4, and Siemens 3VA52 to 3VA59 are printed at a straight 600 V. Compare the voltage rating exactly as printed, including the Y, before substituting.

How each line’s part numbers are built

Each section uses only that line’s own catalog, with the page for every code. Where two pages of the same catalog disagree, the item is left out and noted.

ABB Record Plus FB100

Format: F frame interrupting rating poles voltage type rated current connection, for example FBN36TE050R. Source: ABB US BuyLog Section 6, 9AKK108467A9438 (2026-10). ABB prints the product number structure on page 6-178.

SegmentCodeMeaningPage
FamilyFRecord Plusp.6-178
Frame ratingB100 Ap.6-178
Interruption rating (480 V)V / N / H / L35 / 65 / 100 / 150 kAp.6-178
Poles1 / 2 / 31, 2 or 3 polesp.6-178
Voltage rating6600/347p.6-178
TypeTEFixed Thermal Magneticp.6-178
Rated current015–10015, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 Ap.6-178
ConnectionR / R2 / RVStandard, no lugs / load lugs only / A-Series AD Plus lighting panel (includes load lugs and panel connections)p.6-178

One number, segment by segment

SegmentValueMeaningPage
FamilyFRecord Plusp.6-178
FrameB100 A framep.6-178
Interruption ratingN65 kA at 480 Vp.6-178
Poles33 polesp.6-178
Voltage6600/347p.6-178
TypeTEFixed thermal magneticp.6-178
Rated current05050 Ap.6-178
ConnectionRStandard, no lugsp.6-178

FBN36TE050R is printed in the 3-pole ordering table (p.6-181).

ABB Tmax XT (TMF)

Source: ABB SACE Tmax XT UL/CSA catalog 1SDC210200D0206 (2024-08), PDF pages. The ordering tables print each breaker’s US/CA part number in a row that names the frame, the interrupting rating at 480 V, the frame rating (Iu), the trip unit and the rated current (In), with separate columns for 3 and 4 poles. The catalog doesn’t print a key for the part number’s characters, so this section reads numbers from their table rows rather than decoding them.

Trip units

CodeOverload thresholdOverload trip timeShort-circuit thresholdPage
TMFFixedFixedFixed (fixed instantaneous)p.61
TMAAdjustableFixedAdjustable (fixed instantaneous)p.61

Only TMF breakers are on this page. TMA and the Ekip electronic trip units are adjustable and go through our Parts Check.

One number, read from its table row

ColumnValuePage
US/CA part numberXT1NU3100AFF000XXXp.248
Table headingSACE XT1N TMF, front terminals (F)p.248
SizeXT1p.248
Interrupting rating (480 V)25 kAp.248
Iu (frame rating)125 Ap.248
Trip unitTMFp.248
In (rated current)100 Ap.248
Poles3 (the 4-pole number in the same row is XT1NU4100AFF000XXX)p.248

Allen-Bradley 140G

Format: 140G- frame interrupting code protection type poles - rated current, for example 140G-G3C3-C30. Source: Rockwell 140G-TD101E-EN-P (2025-08), “Catalog Number Explanation” for each frame (p.32 frame G, p.34 frame H, p.41 frame I, p.43 frame J). Rockwell notes that not all combinations generate a valid catalog number (p.32).

SegmentCodeMeaningPage
Bulletin140GMCCBp.32
Frame size / ratingG / H / HC / I / J / JC125 A / 125 A / 125 A current limiting / 225 A / 250 A / 250 A current limitingpp.32, 34, 41, 43
Interrupting rating (based on Ic at 480 V)2 / 3 / 6 / 0 / 1525 / 35 / 65 / 100 / 150 kA (0 on frames H and J; 15 on frame H)pp.32, 34, 41, 43
Protection typeCFixed thermal/fixed magnetic (all four frames)pp.32, 34, 41, 43
Protection type, adjustable (not on this page)E / FE: adjust thermal/fixed magnetic (frame G). F: adjust thermal/adjust magnetic (frames H, J)pp.32, 34, 43
Number of poles3 / 43 poles / 4 polesp.32
Rated currentC□ / D□Example: C30 = 30 A; D16 = 160 Ap.32
Continuous rated(blank)80% ratedp.32

Rockwell’s numbering rule gives the 140G-D12 as 120 A. Its own selection tables print it at 125 A, and the D17 and D22 at 175 A and 225 A.

This page uses the table values. The five-ampere difference is small enough to pass unnoticed and large enough to matter when you’re sizing against a calculated load or coordinating with an upstream device.

One number, segment by segment

SegmentValueMeaningPage
Bulletin140G-MCCBp.32
FrameGFrame G, 125 Ap.32
Interrupting code335 kA at 480 V (65 kA at 240 V, 14 kA at 600Y/347 V)pp.32, 33
Protection typeCFixed thermal/fixed magneticp.32
Poles33 polesp.32
Rated currentC3030 App.32, 33

140G-G3C3-C30 is printed in Table 17 (p.33).

Eaton Power Defense

Format: PD certifications frame poles interrupting rating continuous current trip unit terminals, for example PDG13M0125TFFJ. Source: Eaton Volume 4 Tab 2, CA08100005E (2026-04), “Catalog Number / Product Selection” for each frame (V4-T2-23 frame 1, V4-T2-31 frame 2, V4-T2-44 frame 3, V4-T2-58 frame 4). Eaton presents it “as a tool to develop catalog numbers”. Electronic (PXR) trip units are adjustable and go through our Parts Check.

SegmentCodeMeaningPage
Product seriesPDPower DefenseV4-T2-23
Certifications / standardsG / F / DG = UL/CSA/IEC (frame 1), UL/CSA/IEC/CCC (frames 2 to 4); F = 100% UL/CSA rated (frame 3); D = UL/CSA, rated to 240 V AC (frames 2, 3)V4-T2-23, 31, 32, 44
Frame size1 / 2 / 3 / 4125 A / 225 A / 400 A and 600 A constructions / 800 AV4-T2-22, 30, 43, 58
Poles1 / 2 / 3 / 4 / 0 / 61-pole, 2-pole, 3-pole, 4-pole (100% N), 4-pole (0% N), 4-pole (60% N); not every frame takes every optionV4-T2-23, 31, 44, 58
Interrupting rating (480 V)C / F / G / K / M / N / P18 / 25 / 35 / 50 / 65 / 85 / 100 kA (C on frame 1 only; frame 4: G, K, M)V4-T2-23, 31, 44, 58
Continuous current0015–0800Four digits in amperes, for example 0125 = 125 A. Frame 3 also prints H250 to H400 (high override, 600 A construction).V4-T2-23, 31, 44, 58
Trip unitTFF / TFATFF = Fixed thermal / Fixed magnetic (frames 1, 2). TFA = Fixed thermal / Adjustable magnetic (frames 3, 4).V4-T2-23, 31, 44, 58
Trip unit, not on this pageVFF / VFA50 °C fixed thermal versions, marked “(non UL)”V4-T2-23, 31, 44, 58
TerminalsN / J / K / LNo terminals / line and load terminals / line only terminals / load only terminalsV4-T2-23

One number, segment by segment

SegmentValueMeaningPage
Product seriesPDPower DefenseV4-T2-23
CertificationsGUL/CSA/IECV4-T2-23
Frame1Frame 1, 125 AV4-T2-23
Poles33-poleV4-T2-23
Interrupting ratingM65 kA at 480 V (25 kA at 600Y/347 V)V4-T2-22, 23
Continuous current0125125 AV4-T2-23
Trip unitTFFFixed thermal / fixed magneticV4-T2-23
TerminalsJLine and load terminalsV4-T2-23

PDG13M0125TFFJ is printed as the key example on V4-T2-23.

Eaton Series G EG

Format: E standard performance poles amperes trip unit terminations, for example EGH3015FFG. Source: Eaton Volume 4 Tab 2, CA08100005E (2026-04), “Catalog Number Selection” on page V4-T2-170. Eaton notes it is “an aid to understanding catalog numbers” and not for building them.

SegmentCodeMeaningPage
FrameEEG frameV4-T2-170
Standard / applicationGIEC/CE/UL/CSAV4-T2-170
Performance (kA at 480 V)B / E / S / H / C18 / 25 / 35 / 65 / 100 (at 240 V: 25 / 35 / 85 / 100 / 200)V4-T2-163, 170
Number of poles1 / 2 / 3 / 4One / two / three / four, neutral 0% protectedV4-T2-170
Amperes015–12515 to 125 A. 016, 032, 063 and 160 “cannot be UL rated”.V4-T2-170
Trip unitFF / AFFF = fixed fixed (fixed thermal, fixed magnetic). AF = adjustable thermal, fixed magnetic, and “Adjustable thermal are not UL listed”.V4-T2-170, 171
Terminations / hardwareG / M / E / BG = line/load standard terminals, metric hardware; M = metric end caps; E = imperial end caps; B = bolt-onV4-T2-170
Eaton's pages differ on the four-pole digit 7. The key on page V4-T2-170 gives 7 as four-pole with the neutral 100% protected. The EGC table on page V4-T2-175 heads its EGC7 column as four-pole with a 0% protected neutral, while its own note says to change the fourth digit to 7 for 100% protection. Digit 7 is left out of the table above.

One number, segment by segment

SegmentValueMeaningPage
FrameEEG frameV4-T2-170
StandardGIEC/CE/UL/CSAV4-T2-170
PerformanceH65 kA at 480 VV4-T2-163, 170
Poles3Three polesV4-T2-170
Amperes01515 AV4-T2-170
Trip unitFFFixed thermal, fixed magneticV4-T2-170, 174
TerminationsGLine/load standard terminals, metric hardwareV4-T2-170

EGH3015FFG is printed in the EG-Frame 70/65 table (V4-T2-174) and as the key example on V4-T2-170.

Schneider Electric (Square D) PowerPacT B-frame and Q-frame

Format: frame interrupting rating termination poles voltage amperage [suffix], for example BDL36100. Source: Square D Digest 179, Section 07 (2026-09), Table 7.48 “Common Catalog Numbering System for PowerPacT Circuit Breakers” (p.7-33), with the B-frame tables on p.7-34 and the Q-frame tables on p.7-41.

SegmentCodeMeaningPage
FrameB / Q125 A frame / 250 A frame (the key also lists H, J, L, M, P and R)p.7-33
Interrupting rating, B-frameD / G / J / K18 / 35 / 65 / 65 kA at 480 V (multi-pole); K is 15–30 A, 1- and 2-polep.7-34, Table 7.51
Interrupting rating, Q-frameB / D / G / J10 / 25 / 65 / 100 kA at 240 Vp.7-41, Table 7.67
Termination, B-frameA / F / L / M / PI-Line / no lugs (terminal nut kit both ends) / EverLink lugs both ends / EverLink lugs ON end, nut kit OFF end / nut kit ON end, EverLink lugs OFF endp.7-34, Table 7.49
Termination, Q-frameA / E / F / L / M / PI-Line / bolt-on I-Line / no lugs / lugs both ends / lugs ON end, studs OFF end / lugs OFF end, studs ON endp.7-41, Table 7.68
Poles1 / 2 / 3 / 41-pole to 4-polep.7-33
Voltage4 / 6480 V / 600 V. Q-frame numbers carry 2 in this place (for example QGL32200); the key doesn’t list 2, and the Q-frame is a 240 Vac breaker.pp.7-33, 7-41
Amperage015–250Three digits, for example 100 = 100 Ap.7-33
Lug option suffix, B-frameLU / LV / LW / LC / LHControl wire terminal ON end / OFF end / both ends; copper mechanical lugs; aluminum mechanical lugs. No suffix = EverLink lugs both ends.p.7-34, Table 7.50

One number, segment by segment

SegmentValueMeaningPage
FrameBB-frame, 125 Ap.7-33
Interrupting ratingD18 kA at 480 V (25 kA at 240 V, 14 kA at 600Y/347 V)p.7-34
TerminationLEverLink lugs both endsp.7-34
Poles33-polep.7-33
Voltage6600 V in the key; the B-frame is rated up to 600Y/347 Vacpp.7-33, 7-34
Amperage100100 Ap.7-34

BDL36100 is printed in Table 7.52 (p.7-34) and as the example on the same page.

Siemens 3VA5

Format: 3VA then digits and letters in fixed positions, for example 3VA5140-5ED31-0AA0. Source: Siemens Industrial Controls catalog Section 17 (2026-02), “Catalog Numbering Logic” on pages 17/14 and 17/15.

PositionCodeMeaningPage
Breaker designation4 / 5 / 6Thermal magnetic panelboard breakers / thermal magnetic (cable-in cable-out) breakers / electronic trip breakersp.17/14
Frame size1 / 2 / 3 / 4 / 5 / 7 / 8 / 9125/150 A / 250 A / 400 A / 600 A / 800 A / 1200 A / 1600 A / 2000 A (6 = 1000 A)p.17/14
Rated currenttwo digitsRead with the frame: 3VA5140 is 40 A, 3VA5340 is 400 A. 15 A is 95; 100, 110 and 125 A are 10, 11 and 12 on the 3VA51.pp.17/14, 17/16
Interrupting capacity at 480 V (3VA5)4 / 5 / 6 / 725 / 35 / 65 / 100 kAp.17/14
Trip unitED / ECTM210 FTFM: fixed thermal, fixed magnetic / TM230 FTAM: fixed thermal, adjustable magneticp.17/15
Trip unit, 100% neutralGD / GCTM210 / TM230 with 100% neutralp.17/15
Trip unit, adjustable (not on this page)EF / GFTM240 ATAM: adjustable thermal, adjustable magneticp.17/15
Number of poles1 / 2 / 3 / 4 / 5 / 61, 2, 3, 4 pole / 1-in-2 pole / 2-in-3 polep.17/15
Connection technology1 / 2 / 6No wire connector / nut keeper kit, line and load / wire connector, line and loadp.17/15
Regional specifics0 / 1 / 2Standard / NAVAL/50C (3VA41/3VA5) / 100% ratedp.17/15
Auxiliary releases; auxiliary/alarm switchesA; A0Without; withoutp.17/15

Interrupting classes by name: 3VA51 S / M / H = 25 / 35 / 65 kA at 480 V (p.17/17); 3VA52 to 3VA59 M / H / C = 35 / 65 / 100 kA at 480 V (pp.17/27, 17/33, 17/37, 17/41, 17/47, 17/51, 17/55).

One number, segment by segment

PositionValueMeaningPage
Family3VA3VA molded case circuit breakerp.17/14
Breaker designation5Thermal magnetic (cable-in cable-out)p.17/14
Frame size1125/150 A frame (3VA51)p.17/14
Rated current4040 App.17/14, 17/17
Interrupting capacity535 kA at 480 V (M class)pp.17/14, 17/17
Trip unitEDTM210 FTFM, fixed thermal and fixed magneticp.17/15
Poles33 polep.17/15
Connection1No wire connectorp.17/15
Regional specifics0Standardp.17/15
Auxiliary releases; switchesAA0Without auxiliary releases; without auxiliary/alarm switchesp.17/15

3VA5140-5ED31-0AA0 is printed in the 3VA51 3-pole table (p.17/17).