IEC contactor cross reference: frame sizes and part numbers
Meisterline Controls scopes and quotes UL 508A control panels. This page lines up IEC contactor frames from ABB, Allen-Bradley, Schneider Electric and Siemens by their published AC-3 and 480 V horsepower ratings, then shows how each line’s part numbers are built: frame, poles and auxiliary contacts, and coil code, with the catalog page for each.
Frames side by side
A matching frame is a starting point, not an equivalent. Coil voltage, auxiliary contact arrangement and horsepower at your voltage all have to be checked before a part can be substituted. Send the list and we’ll check it against your ratings.
AC-3 is the IEC motor-duty rating at 400 V. Horsepower is the 3-phase rating at 480 V. "Nearest frame" is the other line's smallest frame with an equal or higher AC-3 rating and an equal or higher horsepower at 480 V, where that frame's UL listing is confirmed in its own catalog. 3-pole frames. One row per ABB AF frame, with the other lines placed against it. The Z and T versions are listed under the ABB coil codes below.
The frame number is a size name, not the rating. The AF16, for example, is rated 18 A AC-3, and the AF30 is rated 32 A. Every rating in the table is read from ABB's catalog pages listed under it.
| ABB AF frame | AC-3 at 400 V | hp at 480 V | Nearest frame: Allen-Bradley | Nearest frame: Schneider Electric (Square D) | Nearest frame: Siemens |
|---|---|---|---|---|---|
| AF09 | 9 A | 5 hp | 100-C09 / 100-E09 | LC1D09 | 3RT2016 / 3RT2023 |
| AF12 | 12 A | 7.5 hp | 100-C12 / 100-E12 | LC1D12 | 3RT2017 / 3RT2024 |
| AF16 | 18 A | 10 hp | 100-C23 | LC1D18 | 3RT2026 |
| AF26 | 26 A | 15 hp | 100-E26 | LC1D32 | 3RT2027 |
| AF30 | 32 A | 20 hp | 100-E30 | LC1D32 | 3RT2027 |
| AF38 1 | 38 A | 25 hp | 100-E38 | 3RT2028 | |
| AF40 | 40 A | 30 hp | 100-E40 | LC1D40A | 3RT2035 |
| AF52 | 53 A | 40 hp | 100-C55 | LC1D65A | 3RT2037 |
| AF65 2 | 65 A | 50 hp | 100-E65 | 3RT2037 | |
| AF80 | 80 A | 60 hp | 100-E80 | LC1D80 | 3RT2045 |
| AF96 3 | 105 A | 75 hp | 100-E116 | LC1D115A / LC1G115 | 3RT2047 |
| AF116 | 116 A | 75 hp | 100-E116 | LC1D150A / LC1G150 | 3RT1055 |
| AF140 | 140 A | 100 hp | 100-E146 | LC1D150A / LC1G150 | 3RT1055 |
| AF146 | 146 A | 100 hp | 100-E146 | LC1D150A / LC1G150 | 3RT1055 |
| AF190 | 190 A | 125 hp | 100-E190 | LC1G225 | 3RT1064 / 3RT1264 |
| AF205 | 205 A | 150 hp | 100-E205 | LC1G225 | 3RT1064 / 3RT1264 |
| AF265 | 265 A | 200 hp | 100-E265 | LC1G265 | 3RT1065 / 3RT1265 |
| AF305 | 305 A | 250 hp | 100-E305 | LC1G330 | 3RT1075 / 3RT1275 |
| AF370 | 370 A | 300 hp | 100-E370 | LC1G400 | 3RT1075 / 3RT1275 |
| AF400 4 | 400 A | 350 hp | 100-E400 | ||
| AF460 | 460 A | 400 hp | 100-E460 | LC1G500 | 3RT1076 / 3RT1276 |
| AF580 5 | 580 A | 500 hp | 100-E580 | LC1G630 | |
| AF750 | 750 A | 600 hp | 100-E750 | LC1F780 | |
| AF1250 6 | Not published in the catalog | Not published in the catalog | |||
| AF1350 | 860 A | 800 hp | 100-E860 | LC1F1000 | |
| AF1650 | 1060 A | 900 hp | 100-E1060 | ||
| AF2050 | 1060 A | Not published in the catalog | |||
| AF2650 | Not published in the catalog | Not published in the catalog | |||
| AF2850 | Not published in the catalog | Not published in the catalog |
Ratings: ABB main catalog 1SBC100214C0202 Rev D (2024-02), pages 118 and 162–171, and ABB 9AKK108468A0527 (2024-07), pages 4–6. Allen-Bradley: Rockwell 100-TD013Q (2026-05), pages 17 and 59. Schneider Electric: Square D Digest 179, Section 17 (2026-08), pages 11, 14 and 16. Siemens: Industrial Controls catalog Section 2 (2026-02), pages 8, 9 and 13. Eaton XT frames aren’t named in this table. Eaton’s catalog prints ratings for the XT contactors, and Meisterline Controls names a frame only where the catalog states the UL listing. Eaton XT direct current contactors are confirmed and are covered through our Parts Check.
How each line’s part numbers are built
Each section uses only that line’s own catalog, with the page for every code. Where two pages of the same catalog disagree, the item is left out and noted.
ABB AF
Format: AFframe-main poles-auxiliary contacts-coil code. ABB’s catalogs don’t print a numbering key. The meanings below are the headings of the catalog tables each code appears in, with the page.
Main poles (second segment)
| Code | Meaning | Catalog page |
|---|---|---|
| -30 | 3 main poles | Main catalog p.120 |
| -40 | 4 N.O. main poles | Main catalog p.264 |
| -22 | 2 N.O. + 2 N.C. main poles (4-pole AF09, AF16, AF26, AF38, AF40, AF80) | Main catalog p.264, p.267 |
Auxiliary contacts (third segment)
| Code | Auxiliary contacts fitted | Catalog page |
|---|---|---|
| 10 | 1 N.O. | Main catalog p.120 |
| 01 | 1 N.C. | Main catalog p.120 |
| 00 | None | Main catalog p.120 |
| 11 | 1 N.O. + 1 N.C. | Main catalog p.144 |
| 22 | 2 N.O. + 2 N.C. | Main catalog p.159 |
| …K | Push-in spring terminals (for example AF09-30-10K-13) | Main catalog p.204 |
| …B | Bar connections; without B, built-in cable clamps. AF116, AF140, AF146 only. | Main catalog p.125 |
22 means main poles in the second segment and auxiliary contacts in the third.
Coil code (fourth segment): the common ones
| Code | Coil voltage | Frames |
|---|---|---|
| 11 | 24–60 V AC / 20–60 V DC | AF09 to AF370 |
| 12 | 48–130 V AC/DC | AF09 to AF370 |
| 13 | 100–250 V AC/DC | AF09 to AF370 |
| 14 | 250–500 V AC/DC | AF09 to AF370 |
Main catalog p.110. ABB notes on p.120 that coil 11 isn't for direct control by a PLC output.
Coil code: the full range
| Code | Coil voltage | Frames | What the catalog says |
|---|---|---|---|
| 31 / 32 / 33 / 34 | Same bands as 11 / 12 / 13 / 14 | AF116 to AF370 | Built-in PLC interface, opening time below 20 ms (p.126, p.129, p.111) |
| 42 / 43 | 110–120 V AC / 220–240 V AC (AC only) | AF116 to AF370 | AC operated, optimized for short operation times (p.127, p.130) |
| 68 / 69 / 70 / 71 | 24–60 V DC / 48–130 / 100–250 / 250–500 V AC/DC | AF400 to AF1250; AF1350 and up use 70 only | p.110 |
| Z: 20 / 21 / 22 / 23 | 12–20 V DC / 24–60 V AC, 20–60 V DC / 48–130 / 100–250 V AC/DC | AF09Z to AF38Z | "AC / DC operated for specific applications" (p.122) |
| Z: 30 | 24 V DC | AF09Z to AF38Z | "24 V DC operated designed for PLC", low holding consumption (p.121, p.110) |
| T | 220/230–240 V AC | AF1350T to AF2850T | Built-in Low Voltage Ride Through: rides through control-voltage drop-outs up to 1 second without opening (p.146) |
Z and T are not separate frames. AF09Z is the AF09 frame with the Z coil family; AF1350T is the AF1350 frame with built-in LVRT. In the table above they share their base frame's row.
One number, segment by segment
| Segment | Value | Meaning | Catalog page |
|---|---|---|---|
| Frame | AF09 | AF09 frame: 9 A AC-3 at 400 V, 5 hp at 480 V | Main catalog p.120 |
| Main poles | 30 | 3 main poles | Main catalog p.120 |
| Auxiliary contacts | 10 | 1 N.O., 0 N.C. | Main catalog p.120 |
| Coil code | 13 | 100–250 V AC 50/60 Hz and 100–250 V DC | Main catalog p.110 |
AF09-30-10-13 is ABB order code 1SBL137001R1310.
Allen-Bradley 100-C and 100-E
Format: 100-C + frame + coil code + contact code, for example 100-C23D10. Source: Rockwell technical data 100-TD013Q (2026-05). Rockwell prints the coil code as an explicit table; the other segments are the headings of the tables they’re printed in. The catalog lists numbers without the coil code and says to insert it: “100-C09⊗10 becomes Cat. No. 100-C09D10” (p.19).
Segments
| Segment | Meaning | Page |
|---|---|---|
| 100- | Non-reversing contactor | p.17, p.59 |
| 104- | Reversing contactor | p.18, p.61 |
| C / E | Bulletin 100-C or 100-E | p.1 |
| frame digits | The 3-pole row’s AC-3 rating (100-C23 is 23 A AC-3). Not defined as a rating: the 4-pole 100-C40 is 37 A. | p.17, p.18, p.59 |
| U (before the coil code) | Coil terminals on the load side; without U they’re on the line side. 100-C only. Example: 100-C09UD10. | p.19 |
| L (at the end) | Built-in terminal lugs, 100-E116 and 100-E146 only. Example: 100-E11611L. | p.59 |
Contact code (last digits)
| Code | Meaning | Page |
|---|---|---|
| 10 / 01 / 00 / 11 | 3-pole: auxiliary contacts N.O. / N.C. (1 N.O.; 1 N.C.; none; 1 N.O. + 1 N.C.) | p.17, p.59 |
| 400 / 300 / 200 | 4-pole: main poles 4 N.O.; 3 N.O. + 1 N.C.; 2 N.O. + 2 N.C. | p.18, p.60 |
| 22 / 02 | Reversing: printed against 1 N.O. + 1 N.C. and 0 N.O. + 1 N.C. auxiliary contacts per contactor | p.18, p.61 |
Coil code: the common ones
| Code | Coil voltage | Line |
|---|---|---|
| D | 110 V 50 Hz / 120 V 60 Hz AC | 100-C (p.19) |
| L | 200–220 V 50 Hz / 208–240 V 60 Hz AC | 100-C (p.19) |
| T | 240 V 50 Hz / 277 V 60 Hz AC | 100-C (p.19) |
| B | 440 V 50 Hz / 480 V 60 Hz AC | 100-C (p.19) |
| KJ | 24–60 V AC / 20–60 V DC | 100-E09 to E370 (p.62) |
| KY | 48–130 V AC/DC | 100-E09 to E370 (p.62) |
| KD | 100–250 V AC/DC | 100-E09 to E370 (p.62) |
| KN | 250–500 V AC/DC | 100-E09 to E370 (p.62) |
Coil code: the full range
| Code | Coil voltage | Frames | Page |
|---|---|---|---|
| G / KJ / KF | 400–415 V 50 Hz / 440 V 60 Hz; 24 V 50/60 Hz; 230 V 50/60 Hz | 100-C | p.19 |
| EQ / EJ / EW / EY / ED / EA | 12 / 24 / 36–48 / 48–72 / 110–125 / 220–250 V DC, electronic coil | 100-C09 to C55 | p.19 |
| DJ / DG / DD / DA | 24 / 72 / 110 / 220 V DC, conventional coil | 100-C60 to C97 | p.19 |
| EQ / EJ | 12–20 V DC / 24–60 V AC, 20–60 V DC, low consumption | 100-E09 to E38 | p.62 |
| QJ | 24 V DC, low consumption, faster drop-out | 100-E09 to E38 | p.62 |
| ED / EN | 100–250 / 250–500 V AC/DC with PLC input | 100-E116 to E370 | p.62 |
| EJ / EY / ED / EN | 24–60 V DC / 48–130 / 100–250 / 250–500 V AC/DC with PLC input | 100-E400 to E750, E1260 | p.62 |
| ED | 100–250 V AC/DC, the only code | 100-E860, E1060, E2050 to E2650 | p.62 |
Coil letters are not shared between the 100-C and the 100-E. EJ is 24 V direct current on a 100-C, and 24–60 V alternating current or 20–60 V direct current on a 100-E. ED, KD, KY and KN differ too.
Read the coil letter against its own line, especially when moving up a frame.
One number, segment by segment
| Segment | Value | Meaning | Page |
|---|---|---|---|
| Bulletin | 100- | Non-reversing contactor | p.17 |
| Line and frame | C23 | Bulletin 100-C, frame 23: 23 A AC-3, 15 hp at 460 V 3-phase | p.17 |
| Coil code | D | 110 V 50 Hz / 120 V 60 Hz AC; no U, so coil terminals on the line side | p.19 |
| Contact code | 10 | Auxiliary contacts 1 N.O., 0 N.C. | p.17 |
Printed in the catalog as 100-C2310 (p.17), with the coil code inserted per p.19: 100-C23D10.
Schneider Electric TeSys D and TeSys Giga
Format: LC1D + frame + [A] + [terminal digit] + coil code, for example LC1D18G7. Sources: Square D Digest 179, Section 17 (2026-08) = Digest; Schneider TeSys catalog MKTED210011EN (2026-08) = TeSys catalog. Neither prints an overall numbering key; the coil codes and some single digits are explained in tables and footnotes.
Segments
| Segment | Meaning | Page |
|---|---|---|
| LC1 | Contactor | Digest p.11 |
| LC2 | Reversing contactor: “For reversing operation, replace the prefix LC1 with LC2.” | TeSys catalog p.187 |
| D | TeSys Deca (formerly TeSys D) | Digest p.11 |
| G | TeSys Giga | Digest p.14 |
| frame digits | The row’s AC-3 rating (LC1D18 is 18 A). Not defined as a rating: LC1D80A is 66 A, a different contactor from LC1D80 (80 A). | TeSys catalog p.658 |
| A (after the frame) | D40A to D150A: power connections by EverLink BTR screw connectors | TeSys catalog p.658, p.652 |
| no terminal digit | Screw clamp terminals | TeSys catalog p.658 |
| 3 | Spring terminals (LC1D093 is spring, not lugs) | TeSys catalog p.659 |
| 6 | Lugs or bars: “insert a figure 6 before the voltage code. Example: LC1D09pp becomes LC1D096pp.” | TeSys catalog p.658 |
| 9 | Faston connectors, LC1D09 and LC1D12 only | TeSys catalog p.659 |
| V (on LC2D) | Electrical interlock pre-wired at the factory. Example: LC2D09B7V. | TeSys catalog p.666 |
Schneider notes that the spring-terminal LC1D323 and LC1D383 are not certified UL/CSA (TeSys catalog p.664).
Coil code: the common ones (Digest Table 17.23)
| Code | Coil voltage | Frames |
|---|---|---|
| B7 / F7 / G7 / U7 / T7 | 24 / 110 / 120 / 240 / 480 V AC 50/60 Hz | D09 to D38, D40A to D65A, D80, D95 |
| BNE / EHE / KUE | 24–60 / 48–130 / 100–250 V AC/DC | D09 to D65A, D115A, D150A |
| LSE | 200–500 V AC/DC | D115A, D150A |
| BL / BBE / BD | 24 V DC (low consumption on D09–D38; BBE on D40A–D65A; BD on D80, D95) | as shown |
Digest p.11. Schneider notes that LC1D40A to D80A with G7 or T7 are 60 Hz only.
Coil code: the full range (TeSys catalog)
| Code | Coil voltage | Page |
|---|---|---|
| …7 | 50/60 Hz AC, 12 to 690 V (for example J7 12 V, E7 48 V, LE7 208 V, M7 220 V, P7 230 V, W7 277 V, V7 400 V, R7 440 V, X7 600 V) | p.658, p.664, p.685 |
| …5 / …6 | 50 Hz / 60 Hz AC (for example G6 120 V 60 Hz on D80 and D95) | p.658, p.664 |
| …D | DC, 12 to 440 V (JD 12, BD 24, ED 48, FD 110, GD 125, MD 220, UD 250, RD 440 V) | p.658, p.664 |
| …L | DC low consumption, D09 to D38 (AL 5, JL 12, BL 24, EL 48, FL 110, ML 220, UL 250 V) | p.658, p.664 |
| BBE / BNE / EHE / KUE / LSE | Three-character codes are TeSys Deca Advanced (24 V DC; 24–60; 48–130; 100–250; 200–500 V AC/DC) | p.654 |
| Giga: BEE / EHE / KUE / LSE + A or N | 24–48 / 48–130 / 100–250 / 200–500 V AC/DC; A = Advanced version, N = Standard version | p.780 to p.783 |
One number, segment by segment
| Segment | Value | Meaning | Page |
|---|---|---|---|
| Prefix | LC1 | Contactor (LC2 would be reversing) | Digest p.11; TeSys catalog p.187 |
| Series | D | TeSys Deca | Digest p.11 |
| Frame | 18 | 18 A AC-3, 10 hp at 460 V | Digest p.11 |
| Terminal digit | (none) | Screw clamp terminals | TeSys catalog p.658 |
| Coil code | G7 | 120 V AC 50/60 Hz | Digest Table 17.23, p.11 |
Siemens 3RT
Format: 3RT then digits 4 to 12, for example 3RT2026-1AK60. Source: Siemens Industrial Controls catalog Section 2 (2026-02). Siemens prints a nomenclature key on page 4, with coil tables on pages 8, 9 and 56. Siemens notes that the key is “only a guide to decode the model number. All possible combinations of these are not available.”
Positions
| Position | Meaning | Page |
|---|---|---|
| 3RT2 / 3RT1 | SIRIUS Innovations contactor / SIRIUS contactor | p.4 |
| 5th digit | 0 = 3-pole standard; 2 = 3-pole vacuum (3RT12) | p.4, p.13 |
| 6th digit (frame size) | 3RT2: 1 = S00, 2 = S0, 3 = S2, 4 = S3. 3RT1: 5 = S6, 6 = S10, 7 = S12 | p.4 |
| 7th digit (current) | Not mapped to amps in the key; the ratings are on the ordering pages (3RT2026 is 25 A AC-3) | p.4, p.8 |
| 8th digit (terminals) | 1 = screw; 2 = spring (3RT2 S00 and S0: all terminals); 3 = spring (3RT2 S2 and S3: coil); 6 = busbar (3RT1) | p.4, p.8 |
| 9th digit (coil type) | A = AC (3RT2) or AC/DC conventional (3RT1); B = DC (3RT2 S00, S0); N = UC electronic or solid state; P = solid state with RLT (3RT1) | p.4, p.8, p.9 |
| 10th and 11th (coil voltage) | See the coil codes below | p.8, p.9, p.56 |
| 12th digit (auxiliary contacts) | 3RT2: 0 = 1 N.O. + 1 N.C. (S0–S3), 1 = 1 N.O. (S00), 2 = 1 N.C. (S00), 4 = 2 N.O. + 2 N.C. 3RT1: 0 = none, 6 = 2 N.O. + 2 N.C. | p.4, p.8, p.9 |
| -0UA0 (suffix) | NEMA labeled contactor | p.8, p.9 |
Coil code: the common ones
| Code | Coil voltage | Frames | Page |
|---|---|---|---|
| K6 | 120 V 60 Hz / 110 V 50 Hz AC | 3RT201 to 3RT204 | p.8 |
| P6 | 240 V 60 Hz / 220 V 50 Hz AC | 3RT201 to 3RT204 | p.8 |
| V6 | 480 V 60 Hz AC | 3RT201 to 3RT204 | p.8 |
| C2 / H2 | 24 V / 48 V AC 50/60 Hz (S00 uses B0 / H0) | 3RT201 to 3RT204 | p.8 |
| B4 | 24 V DC | 3RT201, 3RT202 | p.8 |
| B3 / F3 / P3 | UC (AC/DC), ranges differ by size: S0 21–28 / 95–130 / 200–280 V; S2, S3 20–33 / 83–155 / 175–280 V | 3RT202 to 3RT204 | p.8 |
| B3 / F3 / P3 | 3RT1 conventional coil: 23–26 / 110–127 / 220–240 V AC/DC | 3RT105 to 3RT107 | p.9 |
Coil code: the full range
| Code | Coil voltage | Frames | Page |
|---|---|---|---|
| A4 / W4 / E4 / F4 / G4 / M4 | 12 / 48 / 60 / 110 / 125 / 220 V DC | 3RT201, 3RT202 | p.8 |
| D3 / M3 / U3 / V3 / R3 / S3 / T3 | 42–48 / 200–220 / 240–277 / 380–420 / 440–480 / 500–550 / 575–600 V AC/DC, conventional coil | 3RT105 to 3RT107 | p.9 |
| B3 / F3 / P3 with N or P | Solid-state coil: 21–27.3 / 96–127 / 200–277 V AC/DC | 3RT105 to 3RT107 | p.9 |
| …0 / …2 / …6 | 50 Hz; 50/60 Hz; USA and Canada 60 Hz rows of the full coil table (for example F0 110 V 50 Hz, G2 110 V 50/60 Hz) | 3RT20 | p.56 |
One number, segment by segment
| Position | Value | Meaning | Page |
|---|---|---|---|
| Family | 3RT2 | SIRIUS Innovations contactor | p.4 |
| 5th | 0 | 3-pole standard | p.4 |
| 6th | 2 | Frame size S0 | p.4 |
| 7th | 6 | 3RT2026: 25 A AC-3, 15 hp at 460 V | p.8 |
| 8th | 1 | Screw terminals | p.4, p.8 |
| 9th | A | AC coil | p.4, p.8 |
| 10th and 11th | K6 | 120 V 60 Hz / 110 V 50 Hz | p.8 |
| 12th | 0 | 1 N.O. + 1 N.C. auxiliary contacts | p.4, p.8 |