Part number reference · Disconnect switches

Disconnect switch ratings and part numbers

Meisterline Controls scopes and quotes UL 508A control panels. This page lines up fusible and non-fusible disconnect switches from five brands by UL ampere rating and the UL standard each catalog names, then shows how each line’s part numbers are built: series, rating, poles, fusing and options, with the catalog page for each.

Switches side by side

A matching row is a starting point, not an equivalent. Voltage rating, pole count, fuse class, horsepower at your voltage, short-circuit rating, and the handle and shaft all have to be checked before a switch can be substituted. Send the list and we’ll check it against your ratings. Meisterline Controls can also quote the panel it goes into.

Rated current is the UL ampere rating each brand prints for the switch (general-use rating where the catalog names one). UL standard is the standard the catalog states for that series: UL 98 (enclosed and dead-front switches), UL 508 (industrial control equipment), UL 60947-4-1 or UL 489 (titles as Eaton prints them, p.V5-T8-2). One row per rated current and UL standard. Each brand’s series at exactly that rating and standard sit in its column, with the columns in alphabetical order. There is no anchor line and no nearest-size rule: every series is placed by its own catalog rating. “(Recognized)” marks a series the catalog calls UL Recognized. “(Convertible)” marks a switch that serves fusible or non-fusible duty depending on a separately ordered fuse kit; it appears in both tables.

The size number in a part number is not always the UL rating. ABB’s OT16F is rated 20 A and the OT25F 30 A (BuyLog p.9-55); Square D’s Vario and TeSys VLS switches print a UL and an International Electrotechnical Commission (IEC) figure, and the UL figure is used here (Digest p.8-5, p.8-10). Horsepower isn’t published in the catalog data we hold for comparison, so it isn’t a column.

In scope: alternating current (AC) disconnect switches, open and enclosed, from the catalogs listed under the tables. UL 489 molded case switches have their own table below the fusible table. Not in these tables: direct current (DC) and photovoltaic switches, double-throw, changeover and transfer switches, and cam switches.

Non-fusible disconnect switches

Siemens 3LD2, 3LD3 and 3LD5 open switch disconnectors aren’t named in either table. Section 18 prints “Certification according to UL standard: UL 508” and “UL60947-4-1 / UL489” (p.18/55) and “certified according to UL489 … also certified according to UL508” (p.18/87), and our data doesn’t hold their UL listing as stated by the brand. Siemens CFS466J and CFS467L 4-pole switches appear only in a footnote (“also available”, p.18/107), and no UL statement was found for Siemens MMS switches. Double-throw switches are outside these tables.
Rated current (UL)UL standardABBAllen-BradleyEatonSchneider Electric (Square D)Siemens
10 AUL 508None at this ratingNone at this ratingNone at this ratingMini-Vario VN12, Vario V02None at this rating
16 AUL 508None at this ratingNone at this ratingR5AMini-Vario VN20, Vario V013LD open types not named (note above the table)
16 A 1Not confirmed in the catalogNo series in this groupNo series in this groupNo series in this groupTeSys VLS size 13LD2 enclosed
20 AUL 508EOT520, OT16FNone at this ratingNone at this ratingVario V0, Vario V1None at this rating
20 AUL 60947-4-1OT20G1None at this ratingNone at this ratingNone at this ratingNone at this rating
25 AUL 508None at this ratingNone at this ratingR5AVario V23LD open types not named (note above the table)
25 ANot confirmed in the catalogNo series in this groupNo series in this groupNo series in this groupTeSys VLS size 13LD2 enclosed
30 AUL 98EOT930, OT30F, OT30G31494H, 1494U (convertible)R9C9422 (Recognized), LK4CNFS, GNF general duty, HNF heavy duty, LNF general duty, VBNFS (Recognized)
30 AUL 508EOT530, OT25FNone at this ratingR5A, T5AMD3LD open types not named (note above the table)
30 AUL 60947-4-1OT30G1None at this ratingNone at this ratingNone at this rating3LD open types not named (note above the table)
30 ANot confirmed in the catalogNo series in this group1494F (convertible), 1494GNo series in this groupNo series in this group3LD2 enclosed, MCS (Recognized) (convertible)
32 ANot confirmed in the catalogNo series in this groupNo series in this groupNo series in this groupTeSys VLS size 1No series in this group
40 AUL 508EOT540, OT40FNone at this ratingR5A, T5ANone at this rating3LD open types not named (note above the table)
40 AUL 60947-4-1OT40G1None at this ratingNone at this ratingNone at this rating3LD open types not named (note above the table)
40 ANot confirmed in the catalogNo series in this groupNo series in this groupNo series in this groupTeSys VLS size 1No series in this group
45 AUL 508None at this ratingNone at this ratingNone at this ratingVario V3None at this rating
50 AUL 60947-4-1OT50G1None at this ratingNone at this ratingNone at this ratingNone at this rating
60 AUL 98EOT960, OT60F, OT60G31494H, 1494U (convertible)R9C9422 (Recognized), TeSys VLS size 2, LK4CNFS, GNF general duty, HNF heavy duty, LNF general duty, VBNFS (Recognized)
60 A 2UL 508OT63FNone at this ratingR5B, T5BMD3LD open types not named (note above the table)
60 ANot confirmed in the catalogNo series in this group1494F (convertible), 1494GNo series in this groupTeSys VLS size 1MCS (Recognized) (convertible)
63 AUL 508None at this ratingNone at this ratingNone at this ratingVario V43LD open types not named (note above the table)
63 AUL 60947-4-1OT63G2None at this ratingNone at this ratingNone at this rating3LD open types not named (note above the table)
63 ANot confirmed in the catalogNo series in this groupNo series in this groupNo series in this groupNo series in this group3LD2 enclosed
80 AUL 508EOT580, OT80FNone at this ratingR5B, T5BNone at this ratingNone at this rating
80 AUL 60947-4-1OT80G2None at this ratingNone at this ratingNone at this ratingNone at this rating
100 A 3UL 98EOT9100, OT100F, OT100G3, OT160G1494H, 1494U (convertible)R9C, R9D9422 (Recognized), TeSys VLS size 2, LK4CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized)
100 A 4UL 508None at this rating1494G hazardous locationR5BVario V53LD open types not named (note above the table)
100 AUL 60947-4-1OT100G2None at this ratingNone at this ratingNone at this rating3LD open types not named (note above the table)
100 ANot confirmed in the catalogNo series in this group1494F (convertible), 1494GNo series in this groupNo series in this group3LD2 enclosed, MCS (Recognized) (convertible)
115 AUL 508None at this ratingNone at this ratingNone at this ratingVario V6None at this rating
125 ANot confirmed in the catalogNo series in this groupNo series in this groupNo series in this groupNo series in this group3LD2 enclosed
200 AUL 98EOT9200, OT200U1494H, 1494U (convertible)R9D9422 (Recognized), LK4CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized)
200 ANot confirmed in the catalogNo series in this group1494GNo series in this groupNo series in this groupMCS (Recognized) (convertible)
400 AUL 98EOT9400, OT400U1494U (convertible)R9E9422 (Recognized), LK4CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized)
400 ANot confirmed in the catalogNo series in this group1494GNo series in this groupNo series in this groupNo series in this group
600 AUL 98EOT9600, OT600U1494U (convertible)R9FLK4CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized)
600 ANot confirmed in the catalogNo series in this group1494GNo series in this groupNo series in this groupNo series in this group
800 AUL 98OT800UNone at this ratingR9GLK4CNFS, HNF heavy duty
1000 AUL 98None at this ratingNone at this ratingR9GLK4None at this rating
1200 AUL 98OT1200UNone at this ratingR9GNone at this ratingHNF heavy duty
1600 AUL 98OT1600UNone at this ratingNone at this ratingNone at this ratingNone at this rating
2000 AUL 98OT2000UNone at this ratingNone at this ratingNone at this ratingNone at this rating
1
These rows hold series whose UL standard the catalog does not settle. The Allen-Bradley 1494G heavy industrial and 1494F have no standard placed under their columns in the standards row of 1494-TD002F. The Siemens 3LD2 enclosed is described as listed and marked suitable for use as a motor disconnect, with no standard named. The Siemens MCS is described as UL Recognized, with no standard named. The Square D TeSys VLS size 1, 16 through 63 A, is given as UL 508 on pages 8-2 and 8-9 and as UL 60947-4-1 on page 8-10.
2
The ABB EOT560 enclosed UL 508 switch is left off this row. BuyLog Section 9 prints it as 50 A on page 9-94 and as 60 A on pages 9-93 and 9-95.
3
ABB’s OT160G is UL Listed at 100 A and UL Recognized at 125 A (BuyLog Section 9, p.9-43), so it sits in the 100 A row.
4
Eaton prints “Suitable as Motor Disconnect” for R5 switches from 16 to 80 A (p.V5-T8-10). The 100 A R5B is outside that range. Allen-Bradley’s hazardous-location 1494G is printed as one catalog number at this rating, 1494G-DH3N-203W (1494-TD002F p.45).

Fusible disconnect switches

Rated current (UL)UL standardABBAllen-BradleyEatonSchneider Electric (Square D)Siemens
30 AUL 98EOS930, OS301494H, 1494U (convertible)R9I, R9J9422 (Recognized), GS1, GS2CFS, GF general duty, HF heavy duty, VBFS (Recognized)
30 A 1UL 489None at this ratingNone at this ratingR4HNone at this ratingNone at this rating
30 A 2Not confirmed in the catalogNo series in this group1494F (convertible), 1494GNo series in this groupNo series in this groupMCS (Recognized) (convertible)
60 AUL 98EOS960, OS601494H, 1494U (convertible)R9J, R9K9422 (Recognized), GS2CFS, GF general duty, HF heavy duty, VBFS (Recognized)
60 ANot confirmed in the catalogNo series in this group1494F (convertible), 1494GNo series in this groupNo series in this groupMCS (Recognized) (convertible)
100 AUL 98EOS9100, OS1001494H, 1494U (convertible)R9K9422 (Recognized), GS2CFS, GF general duty, HF heavy duty, VBFS (Recognized)
100 ANot confirmed in the catalogNo series in this group1494F (convertible), 1494GNo series in this groupNo series in this groupMCS (Recognized) (convertible)
200 AUL 98EOS9200, OS2001494H, 1494U (convertible)R9L9422 (Recognized), GS2CFS, GF general duty, HF heavy duty, VBFS (Recognized)
200 ANot confirmed in the catalogNo series in this group1494GNo series in this groupNo series in this groupMCS (Recognized) (convertible)
400 AUL 98EOS9400, OS4001494U (convertible)R9M9422 (Recognized), GS2CFS, GF general duty, HF heavy duty, VBFS (Recognized)
400 ANot confirmed in the catalogNo series in this group1494GNo series in this groupNo series in this groupNo series in this group
600 AUL 98EOS9600, OS6001494U (convertible)R9NGS2CFS, GF general duty, HF heavy duty, VBFS (Recognized)
600 ANot confirmed in the catalogNo series in this group1494GNo series in this groupNo series in this groupNo series in this group
800 AUL 98OS800None at this ratingR9NGS2CFS, HF heavy duty
1200 AUL 98OS1200None at this ratingNone at this ratingNone at this ratingHF heavy duty
1
Eaton’s R4H is the 30 A compact (H-frame) fusible switch, listed to UL 489 under file E305341, where the other R9 fusible frames are listed to UL 98 (p.V5-T8-26, p.V5-T8-60).
2
These rows hold series whose catalog doesn’t settle the UL standard. The note under the 16 A row of the non-fusible table names each one.

Molded case switches (UL 489)

A molded case switch is built in a molded case circuit breaker frame and listed to UL 489, without overcurrent protection for the circuit it feeds (Rockwell’s table reads “Molded case switch (no overcurrent protection)”, 140G-TD101E p.93). Square D lists its PowerPacT switches as automatic molded case switches and Siemens lists its Sentron switches as self-protective; check each catalog’s note on what that means before substituting one for another. Rows are the rated current; each cell names the frames at that rating, with poles, voltage and the catalog page (PDF page numbers in the documents named under the table). Lines the brand is phasing down are marked.

Rated currentABBAllen-BradleyEatonSchneider Electric (Square D)Siemens
50 ANone at this ratingNone at this ratingQUICKLAG HQP, BAB, QC (1 to 3 poles, 240 V) V4-T1 pp.6, 12, 20None at this ratingNone at this rating
60 AQ-Line TQB, TQC (2, 3 poles, 240 V) BuyLog pp.42, 46None at this ratingQUICKLAG HQP, BAB, QC (1 to 3 poles, 240 V) V4-T1 pp.6, 12, 20; Series C G-frame GD (3 poles, 480 V) V4-T2 p.238 (phasing down)QO, QOU non-automatic (2, 3 poles, 240 V) Sec.7 pp.11, 21None at this rating
100 AE150 TED, TEB (1 to 3 poles, up to 600 V) BuyLog pp.72, 186; Q-Line TQB, TQC (2, 3 poles, 240 V) BuyLog pp.42, 46None at this ratingPower Defense PD-2 (2 to 4 poles, 600 V) V4-T2 p.32; QUICKLAG HQP, BAB, QC (1 to 3 poles, 240 V) V4-T1 pp.6, 12, 20; Series C GD, EHD, FD, HFD (2 to 4 poles, up to 600 V) V4-T2 pp.238, 260 (phasing down)None at this rating3VA5 (2, 3 poles, up to 600 V) Sect.17 p.58; Sentron ED, CED (2, 3 poles, up to 600 V) Sect.17 p.125
125 ATmax XT1, XT2 (3, 4 poles, up to 600 V) BuyLog pp.87, 94140G frames G, H (3, 4 poles, 600 V) TD101E p.93Power Defense PD-1 (3, 4 poles, 600Y/347 V) V4-T2 p.23; Series G EGK (3, 4 poles, 600 V) V4-T2 p.175 (phasing down)PowerPacT B (2, 3 poles, 600 V) Sec.7 p.52; QOU non-automatic (2 poles, 240 V) Sec.7 p.21Sentron ED, CED (2, 3 poles, up to 600 V) Sect.17 p.125
150 ATmax XT4 (3, 4 poles, 600 V) Tmax XT p.300; E150 TED (3 poles, up to 600 V) BuyLog p.72None at this ratingPower Defense PD-2 (2 to 4 poles, 600 V) V4-T2 p.32; Series C FD, HFD (2 to 4 poles, 600 V) V4-T2 p.260 (phasing down)PowerPacT H (2, 3 poles, 600 V) Sec.7 p.523VA5 (2, 3 poles, 600 V) Sect.17 p.58
175 ANone at this ratingNone at this ratingNone at this ratingPowerPacT J (2, 3 poles, 600 V) Sec.7 p.52None at this rating
225 ATmax XT3 (3, 4 poles, 480 V) BuyLog p.95140G frame I (3, 4 poles, 600 V) TD101E p.93Power Defense PD-2 (2 to 4 poles, 600 V) V4-T2 p.32; Series C FD, HFD (2 to 4 poles, 600 V) V4-T2 p.260 (phasing down)PowerPacT Q (2, 3 poles, 240 V) Sec.7 p.52None at this rating
250 ATmax XT4 (3, 4 poles, 600 V) Tmax XT p.300140G frame J (3, 4 poles, 600 V) TD101E p.93None at this ratingPowerPacT J (2, 3 poles, 600 V) Sec.7 p.523VA5 (2, 3 poles, 600 V) Sect.17 p.58; Sentron HQR, FXD, HFXD, CFD (2, 3 poles, up to 600 V) Sect.17 p.125
400 ATmax XT5 (3, 4 poles, 600 V) Tmax XT p.333140G frame K (3, 4 poles, 600 V) TD102A p.50; 140G2 frame K (3 poles) TD101E p.93Power Defense PD-3 (2 to 4 poles, 600 V) V4-T2 p.44; Series C DK, KD, HKD, KDB (2 to 4 poles, up to 600 V) V4-T2 p.282 (phasing down)PowerPacT L (3, 4 poles, 600 V) Sec.7 p.523VA5, 3VA6 (2, 3 poles, 600 V) Sect.17 p.58; Sentron JXD, HJXD, CJD (2, 3 poles, up to 600 V) Sect.17 p.125
600 ATmax XT5 (3, 4 poles, 600 V) Tmax XT p.333140G2 frame L (3 poles) TD101E p.93Power Defense PD-3 (2 to 4 poles, 600 V) V4-T2 p.44; Series C LD, LDB, HLD (2 to 4 poles, 600 V) V4-T2 p.293 (phasing down)PowerPacT L, P (2 to 4 poles, up to 600 V) Sec.7 p.523VA5, 3VA6 (2, 3 poles, 600 V) Sect.17 p.58; Sentron LXD, HLXD, CLD (3 poles, 600 V) Sect.17 p.125
800 ATmax XT6 (3, 4 poles, 600 V) Tmax XT p.343140G frame M (3, 4 poles, 600 V) TD101E p.93Power Defense PD-4 (2 to 4 poles, 600 V) V4-T2 p.58; PD-5 (3, 4 poles, 600 V) V4-T2 pp.71, 72; Series C MDL, HMDL (2, 3 poles, 600 V) V4-T2 p.305 (phasing down); Series G NGK (3, 4 poles, 690 V) V4-T2 p.185 (phasing down)PowerPacT M, P (2, 3 poles, up to 600 V) Sec.7 p.523VA5 (2 to 4 poles, 600 V) Sect.17 p.58; Sentron LMXD, MXD, CMD (3 poles, 600 V) Sect.17 p.125
1000 ATmax XT7, XT7 M (3, 4 poles, 600 V) BuyLog pp.119, 129None at this ratingNone at this ratingPowerPacT P (2, 3 poles, up to 600 V) Sec.7 p.523VA5 (2, 3 poles, 600 V) Sect.17 p.58
1200 ATmax XT7, XT7 M (3, 4 poles, 600 V) BuyLog p.129; Tmax XT p.370140G frame N (3, 4 poles, 600 V) TD101E p.93Power Defense PD-5 (3, 4 poles, 600 V) V4-T2 p.72; Series G NGK (3, 4 poles, 690 V) V4-T2 p.185 (phasing down)PowerPacT P, R (2, 3 poles, up to 600 V) Sec.7 p.523VA5 (2, 3 poles, 600 V) Sect.17 p.58; Sentron NXD, CND (3 poles, 600 V) Sect.17 p.125
1250 ANone at this ratingNone at this ratingSeries G NGK (3 poles, 690 V) V4-T2 p.185 (phasing down)None at this ratingNone at this rating
1600 ANone at this ratingNone at this ratingPower Defense PD-6 (3, 4 poles, 600 V) V4-T2 p.80; Series G RGK (3, 4 poles, 600 V) V4-T2 p.195 (phasing down)PowerPacT R (2, 3 poles, 600 V) Sec.7 p.523VA5 (3 poles, 600 V) Sect.17 p.58; Sentron PXD (3 poles, 600 V) Sect.17 p.125
2000 ANone at this ratingNone at this ratingPower Defense PD-6 (3, 4 poles, 600 V) V4-T2 p.80; Series G RGK (3, 4 poles, 600 V) V4-T2 p.195 (phasing down)PowerPacT R (2, 3 poles, 600 V) Sec.7 p.523VA5 (3 poles, 600 V) Sect.17 p.58; Sentron RXD (3 poles, 600 V) Sect.17 p.125
2500 ANone at this rating140G frame R (3, 4 poles) TD101E p.93None at this ratingPowerPacT R (2, 3 poles, 600 V) Sec.7 p.52None at this rating

Sources (PDF pages): ABB US BuyLog Section 6, 9AKK108467A9438 (2026-10), and SACE Tmax XT UL/CSA catalog 1SDC210200D0206 (2024-08). Allen-Bradley: Rockwell 140G-TD101E (2025-08) and 140G-TD102A (2025-07). Eaton: Volume 4 Tab 1, miniature circuit breakers, and Volume 4 Tab 2, molded case circuit breakers, CA08100005E (2026-07 and 2026-04). Schneider Electric: Square D Digest 179, Section 7 (2026-09). Siemens: Industrial Controls catalog Section 17 (2026-02).

Ratings and standards: ABB US BuyLog Section 9, 9AKK108467A9441 (2026-01), pages 9-4 to 9-11, 9-37 to 9-47, 9-55 to 9-62, 9-93 to 9-95, 9-104 and 9-105. Allen-Bradley: Rockwell 1494-TD002F-EN-P (2026-03), pages 3, 5 to 7, 26, 32 to 35, 45 and 47. Eaton: Volume 5 Tab 8, CA08100006E (2026-07), pages V5-T8-2, -5, -6, -10, -12, -13, -18, -19, -26 and -28 to -31. Schneider Electric: Square D Digest 179, Section 8 (2026-04), pages 8-2 to 8-5, 8-8 to 8-10, 8-24 to 8-28 (LK4 and GS, UL 98 with UL file E191098 on page 8-2) and 8-33. Siemens: Industrial Controls catalog Section 18 (2026-06), pages 18/3, 18/11 to 18/16, 18/23 to 18/25, 18/96, 18/98, 18/99, 18/103, 18/105 to 18/107 and 18/110 to 18/112. A series is placed in these tables only where the catalog states its UL listing or recognition. Enclosed switches are shown for ABB (EOT, EOS), Allen-Bradley (1494G, 1494H) and Siemens (VBII, 3LD2 enclosed), from the catalogs above.

UL 508 and UL 98 switches are applied differently. Eaton’s catalog (p.V5-T8-2) describes UL 98 switches as “used as disconnecting means without restrictions”, and UL 508 switches as manual motor controllers that can be used as a disconnect only when marked “suitable as motor disconnect”, installed on the load side of the branch circuit protective device, and not used as the main disconnect of a panel. Square D’s catalog describes its Vario switches as UL 508 manual motor controllers marked “Suitable as Motor Disconnect”, for installation on the load side of the motor branch circuit protection (p.8-5). A UL 508 row and a UL 98 row at the same current are not interchangeable.
The switch, its handle and its shaft are often separate part numbers. ABB prints “Handle and shaft are not included” on its OT ordering pages (p.9-55), Eaton builds a switch from switch body, shaft and external handle (p.V5-T8-6), and Square D builds an LK or GS switch from switch, shaft and handle (p.8-24). Allen-Bradley’s 1494F and 1494U and Siemens’ MCS take fusing through a separately ordered kit (1494-TD002F p.7 and p.26; Section 18 p.18/103). Count those parts when comparing lines.

How each line’s part numbers are built

Each section uses only that line’s own catalog, with the page for every code. Where two pages of the same catalog disagree, the item is left out and noted.

ABB OT, OS and enclosed EOT/EOS

Source: ABB US BuyLog Section 9, 9AKK108467A9441 (2026-01). ABB prints a type designation key for each range.

OT16 to OT160 non-fusible (p.9-39)

SegmentCodeMeaning
BrandOTABB switch-disconnector
Switch size16 … 160Size number. The UL ampere rating is printed separately (OT16F 20 A, OT25F 30 A, OT63F 60 A; p.9-55)
Operation and mountingF / FTF = base and DIN-rail mounting, front operated; FT = door mounting, front operated
Poles3 / 4 / 6 / 8Number of poles
Poles (OT160G)03 / 04 / 30 / 403 or 4 poles, operating mechanism at the left (03, 04) or right (30, 40) end
Included accessoriesN2 / P / KN2 = fourth pole switching with the main contacts; P = pistol handle and shaft; K = direct mount handle (base mounting only)

UL standard by size: OT16, 25, 40, 63, 80 are UL 508; OT30, 60, 100 are UL 98 (p.9-55). OT160G is UL Listed at 100 A and UL Recognized at 125 A under UL 98 (p.9-43).

OT200 to OT2000 non-fusible (p.9-41)

SegmentCodeMeaning
Switch size200 … 2000Ampere rating, 200 to 2000 A
Operation and mountingUFront operated, base mounting, UL/CSA
Poles03 / 04 / 12 / 22 / 30 / 403 or 4 poles; mechanism at the left end (03, 04), between the poles (12, 22) or at the right end (30, 40)
ConstructionW / K / PW = wide phase distance; K = direct mount handle; P = external handle and metal shaft included

OT Plus OT20 to OT100 non-fusible (p.9-40)

SegmentCodeMeaning
Switch size20 … 100Ampere rating, 20 to 100 A
Poles3 / 4 / 6 / 8Number of poles
Mounting and operationB / D / MB = base and DIN-rail, front operated; D = door mounting; M = DIN panel mounting
TerminalsS / QS = screw terminals; Q = Quick-Spring terminals
Fourth poleN1 / N2Fourth pole simultaneous, mounted on the left (N1) or right (N2)
Included accessories(empty) / UEmpty = black padlockable knob handle included; U = without knob handle, locking ring included

UL standard: G1 and G2 types (20 to 100 A) are UL 60947-4-1, and G3 types (30, 60, 100 A) are UL 98 (p.9-38, p.9-60, p.9-61).

The OT Plus key on page 9-40 prints G2 as frame 1 and G2 as frame 2. The technical pages show the OT20G1 through OT50G1 as frame G1. The frame letter is left out of the key above.

OS fusible (p.9-5, p.9-6)

SegmentCodeMeaning
BrandOSABB switch fuse / fusible switch
Switch size30 … 1200Ampere rating, 30 to 1200 A. The 30 A OS Mini adds generation letter F (OS30F…, p.9-5)
Fuse typeAJ / ACC / J / LOS Mini: AJ = Class J, ACC = Class CC. 60 to 1200 A: J = Class J, L = Class L
Operation(blank) / SFront operation; S = side operation
Poles03 / 04 / 12 / 22 / 30 / 403 or 4 poles; mechanism at the left end (03, 04), between the poles (12, 22) or at the right end (30, 40)
NeutralN1 / N2 / N3 / FN1, N2 = non-fused switched neutral left or right; N3 = detachable neutral link; F = fused switched neutral
Included handleP / KP = pistol handle and shaft; K = direct mount handle

All OS ratings, 30 to 1200 A, are UL 98 (p.9-4, p.9-7).

The OS key on page 9-6 states that sizes 60 through 1200 A are followed by a generation letter G. The 200 A and larger types are printed without it — the OS200J03 on page 9-9, for example. The generation letter is left out of the key above for 60 A and up.

Enclosed EOT and EOS (p.9-93)

SegmentCodeMeaning
ProductEEnclosed switch
Switch typeOT / OSOT = non-fused; OS = fused
UL listing5 / 95 = UL 508; 9 = UL 98 (UL/cUL)
Ampere rating20 … 80020 = 20 A through 800 = 800 A
FusingN / C / JN = non-fused; C = fused Class CC; J = fused Class J
Poles3 / 4 / 6 / 8Number of poles
Switch styleP / CP = standard; C = changeover (changeover types are not in the table above)
SeriesA / B / CA, B or C series
Enclosure1 / 3 / P / X1 = Type 1 metallic (UL 98 only); 3 = Type 1/3R/12 metallic; P = Type 1/3R/12/4/4X plastic; X = Type 4/4X stainless
HandlePB / PR / PX / SB / SRPistol black, red/yellow or stainless; selector black or red/yellow
Auxiliary contactA / 1A = none; 1 = 1 normally open (N.O.) and 1 normally closed (N.C.)
ABB prints the EOT560 enclosed UL 508 switch as 50 A on page 9-94, and as 60 A in the key on page 9-93 and in the technical data on page 9-95. The EOT560 is left out of the tables above.

One number, segment by segment

SegmentValueMeaningCatalog page
BrandOTABB switch-disconnectorp.9-39
Switch size16Size 16: UL ampere rating 20 A, UL 508p.9-39, p.9-55
Operation and mountingFBase and DIN-rail mounting, front operatedp.9-39
Poles44 polesp.9-39
Included accessoriesN2Fourth pole, switching together with the main contactsp.9-39

OT16F4N2 is ABB order number 1SCA104829R1001 (p.9-55). Handle and shaft are not included.

Allen-Bradley 1494G, 1494H, 1494F and 1494U

Source: Rockwell technical data 1494-TD002F-EN-P (2026-03). Rockwell prints a catalog number explanation for 1494G (p.32) and 1494U (p.5), and notes that “not all combinations produce a valid catalog number.” 1494H and 1494F are listed by complete catalog number (p.47, p.26) without a key.

1494G enclosed safety disconnect switches (p.32)

SegmentCodeMeaning
Bulletin1494G / 1494GY / 1494GXStandard-size enclosure (30 to 600 A); large-size (30 to 200 A); extra large-size (30 to 100 A)
Switch ratingB / C / D / E / F / G30 / 60 / 100 / 200 / 400 / 600 A
EnclosureF / C / KF = Type 3R/4/12 painted metal; C = Type 4/4X 304 stainless steel; K = Type 12 hazardous location (Class II Div. 2 Group F+G, Class III Div. 1 and 2)
Poles2 / 32-pole 1-phase; 3-pole 3-phase
FusingN / H / J / RNon-fusible; Class H, J or R fuse clips
Fuse voltage(blank) / 2 / 6Blank = non-fusible; 2 = 240 V AC / 250 V DC; 6 = 600 V AC / 600 V DC
Options-98 / -203W / -412 / -413 / -414For example: N.O. auxiliary; viewing window; painted metal handle; stainless-steel handle; protective fuse cover

The hazardous-location version is printed as one catalog number, 1494G-DH3N-203W, 100 A non-fusible (p.45).

1494U universal flange switches, factory-assembled kits (p.5)

SegmentCodeMeaning
Bulletin1494UDisconnect switch, rod or cable operated
FusingN / J / RNon-fusible; Class J fuse; Class R fuse
Switch rating30 … 60030, 60, 100, 200, 400, 600 A
OptionsCR, C3–C6, LA, LC, M, N, S, NO, NC, PC …Threaded rod; cable length 3 to 6 ft; lugs; painted metal, non-metallic or stainless handle; auxiliary contacts; protective cover. Options are listed in alphabetical order.

The switch bodies are 1494U-D30 to 1494U-D400 and 1494V-DS600 (p.6). Fusing is added with a trailer fuse block kit (p.7).

The standards compliance row on page 3 is laid out in merged cells. It places UL 98 under the 1494H and 1494U, UL 508 under the 1494G hazardous location column, and no standard under the 1494G heavy industrial or the 1494F. Those two sit in the "Not confirmed in the catalog" rows.

One number, segment by segment

SegmentValueMeaningPage
Bulletin1494GEnclosed safety disconnect switch, standard-size enclosurep.32
Switch ratingB30 Ap.32
EnclosureFType 3R/4/12 painted metalp.32
Poles33-pole, 3-phasep.32
FusingJClass J fuse clipsp.32
Fuse voltage6600 V AC / 600 V DCp.32

1494G-BF3J6 is printed in the 600 V fusible table (p.34). Rockwell notes that replacing J with R or H gives Class R or Class H clips, for example 1494G-BF3R6.

Eaton R5 and R9

Source: Eaton Volume 5 Tab 8, Rotary Disconnects, CA08100006E (2026-07). Eaton prints a catalog numbering system on p.V5-T8-60.

Segments (p.V5-T8-60)

SegmentCodeMeaning
UL listingR5 / R9 / R4R5 = UL 508; R9 = UL 98; R4 = UL 489
FrameA / BUL 508, 16–40 A / 60–100 A
FrameC / D / E / F / GUL 98 non-fusible: 30–100 A / 100–200 A / 400 A / 600 A / 800–1200 A
FrameHUL 489 fusible, 30 A compact
FrameJ / K / L / M / NUL 98 fusible: 30–60 A / 60–100 A / 200 A / 400 A / 600–800 A
Poles2 / 3 / 4Two-, three- or four-pole
Ampere rating016 … 1200016 = 16 A through 1200 = 1200 A
ProtectionU / FU = non-fusible; F = fusible
Fuse type acceptedCC / J / LClass CC, J or L; blank on non-fusible devices

T5A and T5B are the toggle versions of the R5 switch (“Three-Pole Toggle Switch Only”, p.V5-T8-6). Eaton prints “Suitable as Motor Disconnect” for R5 from 16 to 80 A (p.V5-T8-10).

One number, segment by segment

SegmentValueMeaningPage
UL listingR9UL 98p.V5-T8-60
FrameKUL 98 fusible, 60–100 Ap.V5-T8-60
Poles3Three-polep.V5-T8-60
Ampere rating100100 Ap.V5-T8-60
ProtectionFFusiblep.V5-T8-60
Fuse typeJClass Jp.V5-T8-60

R9K3100FJ is printed as a switch body (K-frame, Class J) on p.V5-T8-30. The handle and shaft are separate selections.

Schneider Electric Vario and TeSys VLS

Source: Square D Digest 179, Section 8, Operating Mechanisms and Disconnect Switches (2026-04). The Digest prints identification keys for Vario (Table 8.1, p.8-3) and TeSys VLS (Table 8.28, p.8-9). The 9422 and MD switches are listed by complete catalog number (p.8-33, p.8-8) without a key.

Mini-Vario and Vario (Table 8.1, p.8-3)

SegmentCodeMeaning
ModelV / KV = Vario; K = operator
Operator or accessoryCD / CF / BD / BF / CCD / CCF / VE / VD / ZSingle-hole or four-hole red and yellow (CD, CF) or black and gray (BD, BF); with extension shaft (CCD, CCF); handle installed on the unit, red (VE) or black (VD); Z = accessory, power pole, neutral or ground
Switch type (UL/IEC A)N12 / N20Mini-Vario 10/12 A; 16/20 A
Switch type (UL/IEC A)02 / 01 / 0 / 1 / 2Vario 10/12, 16/20, 20/25, 20/32, 25/40 A
Switch type (UL/IEC A)3 / 4 / 5 / 6Vario 45/63, 63/80, 100/125, 115/175 A
EnclosureGE / GU / G30, A30, W30Mini-Vario IP55 non-metallic; Vario IP55 non-metallic; Type 1/12/4/4X metallic (Class 9421)

The first figure of each pair is the UL rating (Table 8.13, p.8-5). The Mini-Vario enclosed VCFN12GE and VCFN20GE are printed as “Non-UL Listed” (p.8-3) and are not in the table above.

TeSys VLS (Table 8.28, p.8-9)

SegmentCodeMeaning
ProductVLSDisconnect switch
Poles1P / 3P1 pole; 3 poles
Current016 … 125016 = 16 A through 125 = 125 A (IEC figure; the UL general-use rating is printed in Table 8.30, p.8-10)
MountingD / RD = door mounting; R = DIN rail mounting
Body size1 / 21 = small size (16–63 A); 2 = large size (63–125 A), UL 98
For the small size, code 1 at 16 through 63 A, the Digest names the standard as UL 508 on page 8-2 and in the key on page 8-9, and as UL 60947-4-1 in the certification table on page 8-10. The standard is left off code 1 above, and the VLS size 1 sits in the "Not confirmed in the catalog" rows.

One number, segment by segment

SegmentValueMeaningPage
ProductVLSDisconnect switchp.8-9
Poles3P3 polesp.8-9
Current100100 A; UL general use 100 A at 600 V ACp.8-9, p.8-10
MountingRDIN rail mountingp.8-9
Body size2Large size, 63–125 A, cULus per UL 98 (File E487907)p.8-9, p.8-10

VLS3P100R2 is printed in Table 8.30 (p.8-10), where the DIN rail versions come complete with a black handle.

Siemens VBII, CFS, CNFS and MCS

Source: Siemens Industrial Controls catalog Section 18, Safety and Disconnect Switches (2026-06). Siemens prints a numbering system for VBII safety switches (p.18/6), CFS (p.18/105) and CNFS (p.18/110).

VBII general-duty and heavy-duty safety switches (p.18/6)

SegmentCodeMeaning
Switch typeG / L / HG = general duty; L = general duty, quick install; H = heavy duty (DT and DTG are double throw, not in the table above)
FusingF / NFFused; non-fused
Poles2 / 3 / 4 / 6Number of poles
Voltage1 / 2 / 6120 V or 120/240 V; 240 V; 600 V
Amperes1 … 81 = 30 A, 2 = 60 A, 3 = 100 A, 4 = 200 A, 5 = 400 A, 6 = 600 A, 7 = 800 A, 8 = 1200 A
Neutral(omit) / NLess neutral; with neutral
Enclosure(omit) / R / S / SS / X / JType 1 indoor; Type 3R outdoor; Type 4/4X stainless; Type 4/4X 316 stainless; Type 4/4X non-metallic; Type 12 industrial
SeriesA / (omit)A = all general duty, 400 A and 600 A heavy duty; omitted on other heavy duty

CFS fusible and CNFS non-fusible compact switches (p.18/105, p.18/110)

SegmentCodeMeaning
TypeCFS / CNFSCompact fusible switch; compact non-fusible switch
Poles33 poles
Max. voltage6600 V
Ampere rating1 … 71 = 30 A, 2 = 60 A, 3 = 100 A, 4 = 200 A, 5 = 400 A, 6 = 600 A, 7 = 800 A
Fuse provisions (CFS)C / J / JL / LClass CC; Class J, right-hand mechanism; Class J, left-hand mechanism; Class L, right-hand mechanism
Maximum AIC rating (CFS)5 / (omit)Ampere interrupting capacity: 5 = 100 kiloamperes (kA); omitted = 200 kA, Class J fused
VersionN / N1CFS: N = new size-reduced version, N1 = new 100 kA 60 A switch. CNFS: N = compact design

MCS switches carry an R or L suffix for a right- or left-handed mechanism drive and take a fuse kit or a no-fuse kit ordered separately (p.18/103).

One number, segment by segment

SegmentValueMeaningPage
Switch typeHHeavy dutyp.18/6
FusingFFusedp.18/6
Poles33 polesp.18/6
Voltage6600 Vp.18/6
Amperes4200 Ap.18/6
NeutralNWith neutralp.18/6
EnclosureRType 3R, outdoorp.18/6

HF364NR is printed in the 600 V heavy-duty fusible table (p.18/15). As a 200 A heavy-duty switch it has no series letter.