Disconnect switch ratings and part numbers
Meisterline Controls scopes and quotes UL 508A control panels. This page lines up fusible and non-fusible disconnect switches from five brands by UL ampere rating and the UL standard each catalog names, then shows how each line’s part numbers are built: series, rating, poles, fusing and options, with the catalog page for each.
Switches side by side
A matching row is a starting point, not an equivalent. Voltage rating, pole count, fuse class, horsepower at your voltage, short-circuit rating, and the handle and shaft all have to be checked before a switch can be substituted. Send the list and we’ll check it against your ratings. Meisterline Controls can also quote the panel it goes into.
Rated current is the UL ampere rating each brand prints for the switch (general-use rating where the catalog names one). UL standard is the standard the catalog states for that series: UL 98 (enclosed and dead-front switches), UL 508 (industrial control equipment), UL 60947-4-1 or UL 489 (titles as Eaton prints them, p.V5-T8-2). One row per rated current and UL standard. Each brand’s series at exactly that rating and standard sit in its column, with the columns in alphabetical order. There is no anchor line and no nearest-size rule: every series is placed by its own catalog rating. “(Recognized)” marks a series the catalog calls UL Recognized. “(Convertible)” marks a switch that serves fusible or non-fusible duty depending on a separately ordered fuse kit; it appears in both tables.
The size number in a part number is not always the UL rating. ABB’s OT16F is rated 20 A and the OT25F 30 A (BuyLog p.9-55); Square D’s Vario and TeSys VLS switches print a UL and an International Electrotechnical Commission (IEC) figure, and the UL figure is used here (Digest p.8-5, p.8-10). Horsepower isn’t published in the catalog data we hold for comparison, so it isn’t a column.
In scope: alternating current (AC) disconnect switches, open and enclosed, from the catalogs listed under the tables. UL 489 molded case switches have their own table below the fusible table. Not in these tables: direct current (DC) and photovoltaic switches, double-throw, changeover and transfer switches, and cam switches.
Non-fusible disconnect switches
| Rated current (UL) | UL standard | ABB | Allen-Bradley | Eaton | Schneider Electric (Square D) | Siemens |
|---|---|---|---|---|---|---|
| 10 A | UL 508 | None at this rating | None at this rating | None at this rating | Mini-Vario VN12, Vario V02 | None at this rating |
| 16 A | UL 508 | None at this rating | None at this rating | R5A | Mini-Vario VN20, Vario V01 | 3LD open types not named (note above the table) |
| 16 A 1 | Not confirmed in the catalog | No series in this group | No series in this group | No series in this group | TeSys VLS size 1 | 3LD2 enclosed |
| 20 A | UL 508 | EOT520, OT16F | None at this rating | None at this rating | Vario V0, Vario V1 | None at this rating |
| 20 A | UL 60947-4-1 | OT20G1 | None at this rating | None at this rating | None at this rating | None at this rating |
| 25 A | UL 508 | None at this rating | None at this rating | R5A | Vario V2 | 3LD open types not named (note above the table) |
| 25 A | Not confirmed in the catalog | No series in this group | No series in this group | No series in this group | TeSys VLS size 1 | 3LD2 enclosed |
| 30 A | UL 98 | EOT930, OT30F, OT30G3 | 1494H, 1494U (convertible) | R9C | 9422 (Recognized), LK4 | CNFS, GNF general duty, HNF heavy duty, LNF general duty, VBNFS (Recognized) |
| 30 A | UL 508 | EOT530, OT25F | None at this rating | R5A, T5A | MD | 3LD open types not named (note above the table) |
| 30 A | UL 60947-4-1 | OT30G1 | None at this rating | None at this rating | None at this rating | 3LD open types not named (note above the table) |
| 30 A | Not confirmed in the catalog | No series in this group | 1494F (convertible), 1494G | No series in this group | No series in this group | 3LD2 enclosed, MCS (Recognized) (convertible) |
| 32 A | Not confirmed in the catalog | No series in this group | No series in this group | No series in this group | TeSys VLS size 1 | No series in this group |
| 40 A | UL 508 | EOT540, OT40F | None at this rating | R5A, T5A | None at this rating | 3LD open types not named (note above the table) |
| 40 A | UL 60947-4-1 | OT40G1 | None at this rating | None at this rating | None at this rating | 3LD open types not named (note above the table) |
| 40 A | Not confirmed in the catalog | No series in this group | No series in this group | No series in this group | TeSys VLS size 1 | No series in this group |
| 45 A | UL 508 | None at this rating | None at this rating | None at this rating | Vario V3 | None at this rating |
| 50 A | UL 60947-4-1 | OT50G1 | None at this rating | None at this rating | None at this rating | None at this rating |
| 60 A | UL 98 | EOT960, OT60F, OT60G3 | 1494H, 1494U (convertible) | R9C | 9422 (Recognized), TeSys VLS size 2, LK4 | CNFS, GNF general duty, HNF heavy duty, LNF general duty, VBNFS (Recognized) |
| 60 A 2 | UL 508 | OT63F | None at this rating | R5B, T5B | MD | 3LD open types not named (note above the table) |
| 60 A | Not confirmed in the catalog | No series in this group | 1494F (convertible), 1494G | No series in this group | TeSys VLS size 1 | MCS (Recognized) (convertible) |
| 63 A | UL 508 | None at this rating | None at this rating | None at this rating | Vario V4 | 3LD open types not named (note above the table) |
| 63 A | UL 60947-4-1 | OT63G2 | None at this rating | None at this rating | None at this rating | 3LD open types not named (note above the table) |
| 63 A | Not confirmed in the catalog | No series in this group | No series in this group | No series in this group | No series in this group | 3LD2 enclosed |
| 80 A | UL 508 | EOT580, OT80F | None at this rating | R5B, T5B | None at this rating | None at this rating |
| 80 A | UL 60947-4-1 | OT80G2 | None at this rating | None at this rating | None at this rating | None at this rating |
| 100 A 3 | UL 98 | EOT9100, OT100F, OT100G3, OT160G | 1494H, 1494U (convertible) | R9C, R9D | 9422 (Recognized), TeSys VLS size 2, LK4 | CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized) |
| 100 A 4 | UL 508 | None at this rating | 1494G hazardous location | R5B | Vario V5 | 3LD open types not named (note above the table) |
| 100 A | UL 60947-4-1 | OT100G2 | None at this rating | None at this rating | None at this rating | 3LD open types not named (note above the table) |
| 100 A | Not confirmed in the catalog | No series in this group | 1494F (convertible), 1494G | No series in this group | No series in this group | 3LD2 enclosed, MCS (Recognized) (convertible) |
| 115 A | UL 508 | None at this rating | None at this rating | None at this rating | Vario V6 | None at this rating |
| 125 A | Not confirmed in the catalog | No series in this group | No series in this group | No series in this group | No series in this group | 3LD2 enclosed |
| 200 A | UL 98 | EOT9200, OT200U | 1494H, 1494U (convertible) | R9D | 9422 (Recognized), LK4 | CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized) |
| 200 A | Not confirmed in the catalog | No series in this group | 1494G | No series in this group | No series in this group | MCS (Recognized) (convertible) |
| 400 A | UL 98 | EOT9400, OT400U | 1494U (convertible) | R9E | 9422 (Recognized), LK4 | CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized) |
| 400 A | Not confirmed in the catalog | No series in this group | 1494G | No series in this group | No series in this group | No series in this group |
| 600 A | UL 98 | EOT9600, OT600U | 1494U (convertible) | R9F | LK4 | CNFS, GNF general duty, HNF heavy duty, VBNFS (Recognized) |
| 600 A | Not confirmed in the catalog | No series in this group | 1494G | No series in this group | No series in this group | No series in this group |
| 800 A | UL 98 | OT800U | None at this rating | R9G | LK4 | CNFS, HNF heavy duty |
| 1000 A | UL 98 | None at this rating | None at this rating | R9G | LK4 | None at this rating |
| 1200 A | UL 98 | OT1200U | None at this rating | R9G | None at this rating | HNF heavy duty |
| 1600 A | UL 98 | OT1600U | None at this rating | None at this rating | None at this rating | None at this rating |
| 2000 A | UL 98 | OT2000U | None at this rating | None at this rating | None at this rating | None at this rating |
Fusible disconnect switches
| Rated current (UL) | UL standard | ABB | Allen-Bradley | Eaton | Schneider Electric (Square D) | Siemens |
|---|---|---|---|---|---|---|
| 30 A | UL 98 | EOS930, OS30 | 1494H, 1494U (convertible) | R9I, R9J | 9422 (Recognized), GS1, GS2 | CFS, GF general duty, HF heavy duty, VBFS (Recognized) |
| 30 A 1 | UL 489 | None at this rating | None at this rating | R4H | None at this rating | None at this rating |
| 30 A 2 | Not confirmed in the catalog | No series in this group | 1494F (convertible), 1494G | No series in this group | No series in this group | MCS (Recognized) (convertible) |
| 60 A | UL 98 | EOS960, OS60 | 1494H, 1494U (convertible) | R9J, R9K | 9422 (Recognized), GS2 | CFS, GF general duty, HF heavy duty, VBFS (Recognized) |
| 60 A | Not confirmed in the catalog | No series in this group | 1494F (convertible), 1494G | No series in this group | No series in this group | MCS (Recognized) (convertible) |
| 100 A | UL 98 | EOS9100, OS100 | 1494H, 1494U (convertible) | R9K | 9422 (Recognized), GS2 | CFS, GF general duty, HF heavy duty, VBFS (Recognized) |
| 100 A | Not confirmed in the catalog | No series in this group | 1494F (convertible), 1494G | No series in this group | No series in this group | MCS (Recognized) (convertible) |
| 200 A | UL 98 | EOS9200, OS200 | 1494H, 1494U (convertible) | R9L | 9422 (Recognized), GS2 | CFS, GF general duty, HF heavy duty, VBFS (Recognized) |
| 200 A | Not confirmed in the catalog | No series in this group | 1494G | No series in this group | No series in this group | MCS (Recognized) (convertible) |
| 400 A | UL 98 | EOS9400, OS400 | 1494U (convertible) | R9M | 9422 (Recognized), GS2 | CFS, GF general duty, HF heavy duty, VBFS (Recognized) |
| 400 A | Not confirmed in the catalog | No series in this group | 1494G | No series in this group | No series in this group | No series in this group |
| 600 A | UL 98 | EOS9600, OS600 | 1494U (convertible) | R9N | GS2 | CFS, GF general duty, HF heavy duty, VBFS (Recognized) |
| 600 A | Not confirmed in the catalog | No series in this group | 1494G | No series in this group | No series in this group | No series in this group |
| 800 A | UL 98 | OS800 | None at this rating | R9N | GS2 | CFS, HF heavy duty |
| 1200 A | UL 98 | OS1200 | None at this rating | None at this rating | None at this rating | HF heavy duty |
Molded case switches (UL 489)
A molded case switch is built in a molded case circuit breaker frame and listed to UL 489, without overcurrent protection for the circuit it feeds (Rockwell’s table reads “Molded case switch (no overcurrent protection)”, 140G-TD101E p.93). Square D lists its PowerPacT switches as automatic molded case switches and Siemens lists its Sentron switches as self-protective; check each catalog’s note on what that means before substituting one for another. Rows are the rated current; each cell names the frames at that rating, with poles, voltage and the catalog page (PDF page numbers in the documents named under the table). Lines the brand is phasing down are marked.
| Rated current | ABB | Allen-Bradley | Eaton | Schneider Electric (Square D) | Siemens |
|---|---|---|---|---|---|
| 50 A | None at this rating | None at this rating | QUICKLAG HQP, BAB, QC (1 to 3 poles, 240 V) V4-T1 pp.6, 12, 20 | None at this rating | None at this rating |
| 60 A | Q-Line TQB, TQC (2, 3 poles, 240 V) BuyLog pp.42, 46 | None at this rating | QUICKLAG HQP, BAB, QC (1 to 3 poles, 240 V) V4-T1 pp.6, 12, 20; Series C G-frame GD (3 poles, 480 V) V4-T2 p.238 (phasing down) | QO, QOU non-automatic (2, 3 poles, 240 V) Sec.7 pp.11, 21 | None at this rating |
| 100 A | E150 TED, TEB (1 to 3 poles, up to 600 V) BuyLog pp.72, 186; Q-Line TQB, TQC (2, 3 poles, 240 V) BuyLog pp.42, 46 | None at this rating | Power Defense PD-2 (2 to 4 poles, 600 V) V4-T2 p.32; QUICKLAG HQP, BAB, QC (1 to 3 poles, 240 V) V4-T1 pp.6, 12, 20; Series C GD, EHD, FD, HFD (2 to 4 poles, up to 600 V) V4-T2 pp.238, 260 (phasing down) | None at this rating | 3VA5 (2, 3 poles, up to 600 V) Sect.17 p.58; Sentron ED, CED (2, 3 poles, up to 600 V) Sect.17 p.125 |
| 125 A | Tmax XT1, XT2 (3, 4 poles, up to 600 V) BuyLog pp.87, 94 | 140G frames G, H (3, 4 poles, 600 V) TD101E p.93 | Power Defense PD-1 (3, 4 poles, 600Y/347 V) V4-T2 p.23; Series G EGK (3, 4 poles, 600 V) V4-T2 p.175 (phasing down) | PowerPacT B (2, 3 poles, 600 V) Sec.7 p.52; QOU non-automatic (2 poles, 240 V) Sec.7 p.21 | Sentron ED, CED (2, 3 poles, up to 600 V) Sect.17 p.125 |
| 150 A | Tmax XT4 (3, 4 poles, 600 V) Tmax XT p.300; E150 TED (3 poles, up to 600 V) BuyLog p.72 | None at this rating | Power Defense PD-2 (2 to 4 poles, 600 V) V4-T2 p.32; Series C FD, HFD (2 to 4 poles, 600 V) V4-T2 p.260 (phasing down) | PowerPacT H (2, 3 poles, 600 V) Sec.7 p.52 | 3VA5 (2, 3 poles, 600 V) Sect.17 p.58 |
| 175 A | None at this rating | None at this rating | None at this rating | PowerPacT J (2, 3 poles, 600 V) Sec.7 p.52 | None at this rating |
| 225 A | Tmax XT3 (3, 4 poles, 480 V) BuyLog p.95 | 140G frame I (3, 4 poles, 600 V) TD101E p.93 | Power Defense PD-2 (2 to 4 poles, 600 V) V4-T2 p.32; Series C FD, HFD (2 to 4 poles, 600 V) V4-T2 p.260 (phasing down) | PowerPacT Q (2, 3 poles, 240 V) Sec.7 p.52 | None at this rating |
| 250 A | Tmax XT4 (3, 4 poles, 600 V) Tmax XT p.300 | 140G frame J (3, 4 poles, 600 V) TD101E p.93 | None at this rating | PowerPacT J (2, 3 poles, 600 V) Sec.7 p.52 | 3VA5 (2, 3 poles, 600 V) Sect.17 p.58; Sentron HQR, FXD, HFXD, CFD (2, 3 poles, up to 600 V) Sect.17 p.125 |
| 400 A | Tmax XT5 (3, 4 poles, 600 V) Tmax XT p.333 | 140G frame K (3, 4 poles, 600 V) TD102A p.50; 140G2 frame K (3 poles) TD101E p.93 | Power Defense PD-3 (2 to 4 poles, 600 V) V4-T2 p.44; Series C DK, KD, HKD, KDB (2 to 4 poles, up to 600 V) V4-T2 p.282 (phasing down) | PowerPacT L (3, 4 poles, 600 V) Sec.7 p.52 | 3VA5, 3VA6 (2, 3 poles, 600 V) Sect.17 p.58; Sentron JXD, HJXD, CJD (2, 3 poles, up to 600 V) Sect.17 p.125 |
| 600 A | Tmax XT5 (3, 4 poles, 600 V) Tmax XT p.333 | 140G2 frame L (3 poles) TD101E p.93 | Power Defense PD-3 (2 to 4 poles, 600 V) V4-T2 p.44; Series C LD, LDB, HLD (2 to 4 poles, 600 V) V4-T2 p.293 (phasing down) | PowerPacT L, P (2 to 4 poles, up to 600 V) Sec.7 p.52 | 3VA5, 3VA6 (2, 3 poles, 600 V) Sect.17 p.58; Sentron LXD, HLXD, CLD (3 poles, 600 V) Sect.17 p.125 |
| 800 A | Tmax XT6 (3, 4 poles, 600 V) Tmax XT p.343 | 140G frame M (3, 4 poles, 600 V) TD101E p.93 | Power Defense PD-4 (2 to 4 poles, 600 V) V4-T2 p.58; PD-5 (3, 4 poles, 600 V) V4-T2 pp.71, 72; Series C MDL, HMDL (2, 3 poles, 600 V) V4-T2 p.305 (phasing down); Series G NGK (3, 4 poles, 690 V) V4-T2 p.185 (phasing down) | PowerPacT M, P (2, 3 poles, up to 600 V) Sec.7 p.52 | 3VA5 (2 to 4 poles, 600 V) Sect.17 p.58; Sentron LMXD, MXD, CMD (3 poles, 600 V) Sect.17 p.125 |
| 1000 A | Tmax XT7, XT7 M (3, 4 poles, 600 V) BuyLog pp.119, 129 | None at this rating | None at this rating | PowerPacT P (2, 3 poles, up to 600 V) Sec.7 p.52 | 3VA5 (2, 3 poles, 600 V) Sect.17 p.58 |
| 1200 A | Tmax XT7, XT7 M (3, 4 poles, 600 V) BuyLog p.129; Tmax XT p.370 | 140G frame N (3, 4 poles, 600 V) TD101E p.93 | Power Defense PD-5 (3, 4 poles, 600 V) V4-T2 p.72; Series G NGK (3, 4 poles, 690 V) V4-T2 p.185 (phasing down) | PowerPacT P, R (2, 3 poles, up to 600 V) Sec.7 p.52 | 3VA5 (2, 3 poles, 600 V) Sect.17 p.58; Sentron NXD, CND (3 poles, 600 V) Sect.17 p.125 |
| 1250 A | None at this rating | None at this rating | Series G NGK (3 poles, 690 V) V4-T2 p.185 (phasing down) | None at this rating | None at this rating |
| 1600 A | None at this rating | None at this rating | Power Defense PD-6 (3, 4 poles, 600 V) V4-T2 p.80; Series G RGK (3, 4 poles, 600 V) V4-T2 p.195 (phasing down) | PowerPacT R (2, 3 poles, 600 V) Sec.7 p.52 | 3VA5 (3 poles, 600 V) Sect.17 p.58; Sentron PXD (3 poles, 600 V) Sect.17 p.125 |
| 2000 A | None at this rating | None at this rating | Power Defense PD-6 (3, 4 poles, 600 V) V4-T2 p.80; Series G RGK (3, 4 poles, 600 V) V4-T2 p.195 (phasing down) | PowerPacT R (2, 3 poles, 600 V) Sec.7 p.52 | 3VA5 (3 poles, 600 V) Sect.17 p.58; Sentron RXD (3 poles, 600 V) Sect.17 p.125 |
| 2500 A | None at this rating | 140G frame R (3, 4 poles) TD101E p.93 | None at this rating | PowerPacT R (2, 3 poles, 600 V) Sec.7 p.52 | None at this rating |
Sources (PDF pages): ABB US BuyLog Section 6, 9AKK108467A9438 (2026-10), and SACE Tmax XT UL/CSA catalog 1SDC210200D0206 (2024-08). Allen-Bradley: Rockwell 140G-TD101E (2025-08) and 140G-TD102A (2025-07). Eaton: Volume 4 Tab 1, miniature circuit breakers, and Volume 4 Tab 2, molded case circuit breakers, CA08100005E (2026-07 and 2026-04). Schneider Electric: Square D Digest 179, Section 7 (2026-09). Siemens: Industrial Controls catalog Section 17 (2026-02).
Ratings and standards: ABB US BuyLog Section 9, 9AKK108467A9441 (2026-01), pages 9-4 to 9-11, 9-37 to 9-47, 9-55 to 9-62, 9-93 to 9-95, 9-104 and 9-105. Allen-Bradley: Rockwell 1494-TD002F-EN-P (2026-03), pages 3, 5 to 7, 26, 32 to 35, 45 and 47. Eaton: Volume 5 Tab 8, CA08100006E (2026-07), pages V5-T8-2, -5, -6, -10, -12, -13, -18, -19, -26 and -28 to -31. Schneider Electric: Square D Digest 179, Section 8 (2026-04), pages 8-2 to 8-5, 8-8 to 8-10, 8-24 to 8-28 (LK4 and GS, UL 98 with UL file E191098 on page 8-2) and 8-33. Siemens: Industrial Controls catalog Section 18 (2026-06), pages 18/3, 18/11 to 18/16, 18/23 to 18/25, 18/96, 18/98, 18/99, 18/103, 18/105 to 18/107 and 18/110 to 18/112. A series is placed in these tables only where the catalog states its UL listing or recognition. Enclosed switches are shown for ABB (EOT, EOS), Allen-Bradley (1494G, 1494H) and Siemens (VBII, 3LD2 enclosed), from the catalogs above.
How each line’s part numbers are built
Each section uses only that line’s own catalog, with the page for every code. Where two pages of the same catalog disagree, the item is left out and noted.
ABB OT, OS and enclosed EOT/EOS
Source: ABB US BuyLog Section 9, 9AKK108467A9441 (2026-01). ABB prints a type designation key for each range.
OT16 to OT160 non-fusible (p.9-39)
| Segment | Code | Meaning |
|---|---|---|
| Brand | OT | ABB switch-disconnector |
| Switch size | 16 … 160 | Size number. The UL ampere rating is printed separately (OT16F 20 A, OT25F 30 A, OT63F 60 A; p.9-55) |
| Operation and mounting | F / FT | F = base and DIN-rail mounting, front operated; FT = door mounting, front operated |
| Poles | 3 / 4 / 6 / 8 | Number of poles |
| Poles (OT160G) | 03 / 04 / 30 / 40 | 3 or 4 poles, operating mechanism at the left (03, 04) or right (30, 40) end |
| Included accessories | N2 / P / K | N2 = fourth pole switching with the main contacts; P = pistol handle and shaft; K = direct mount handle (base mounting only) |
UL standard by size: OT16, 25, 40, 63, 80 are UL 508; OT30, 60, 100 are UL 98 (p.9-55). OT160G is UL Listed at 100 A and UL Recognized at 125 A under UL 98 (p.9-43).
OT200 to OT2000 non-fusible (p.9-41)
| Segment | Code | Meaning |
|---|---|---|
| Switch size | 200 … 2000 | Ampere rating, 200 to 2000 A |
| Operation and mounting | U | Front operated, base mounting, UL/CSA |
| Poles | 03 / 04 / 12 / 22 / 30 / 40 | 3 or 4 poles; mechanism at the left end (03, 04), between the poles (12, 22) or at the right end (30, 40) |
| Construction | W / K / P | W = wide phase distance; K = direct mount handle; P = external handle and metal shaft included |
OT Plus OT20 to OT100 non-fusible (p.9-40)
| Segment | Code | Meaning |
|---|---|---|
| Switch size | 20 … 100 | Ampere rating, 20 to 100 A |
| Poles | 3 / 4 / 6 / 8 | Number of poles |
| Mounting and operation | B / D / M | B = base and DIN-rail, front operated; D = door mounting; M = DIN panel mounting |
| Terminals | S / Q | S = screw terminals; Q = Quick-Spring terminals |
| Fourth pole | N1 / N2 | Fourth pole simultaneous, mounted on the left (N1) or right (N2) |
| Included accessories | (empty) / U | Empty = black padlockable knob handle included; U = without knob handle, locking ring included |
UL standard: G1 and G2 types (20 to 100 A) are UL 60947-4-1, and G3 types (30, 60, 100 A) are UL 98 (p.9-38, p.9-60, p.9-61).
OS fusible (p.9-5, p.9-6)
| Segment | Code | Meaning |
|---|---|---|
| Brand | OS | ABB switch fuse / fusible switch |
| Switch size | 30 … 1200 | Ampere rating, 30 to 1200 A. The 30 A OS Mini adds generation letter F (OS30F…, p.9-5) |
| Fuse type | AJ / ACC / J / L | OS Mini: AJ = Class J, ACC = Class CC. 60 to 1200 A: J = Class J, L = Class L |
| Operation | (blank) / S | Front operation; S = side operation |
| Poles | 03 / 04 / 12 / 22 / 30 / 40 | 3 or 4 poles; mechanism at the left end (03, 04), between the poles (12, 22) or at the right end (30, 40) |
| Neutral | N1 / N2 / N3 / F | N1, N2 = non-fused switched neutral left or right; N3 = detachable neutral link; F = fused switched neutral |
| Included handle | P / K | P = pistol handle and shaft; K = direct mount handle |
All OS ratings, 30 to 1200 A, are UL 98 (p.9-4, p.9-7).
Enclosed EOT and EOS (p.9-93)
| Segment | Code | Meaning |
|---|---|---|
| Product | E | Enclosed switch |
| Switch type | OT / OS | OT = non-fused; OS = fused |
| UL listing | 5 / 9 | 5 = UL 508; 9 = UL 98 (UL/cUL) |
| Ampere rating | 20 … 800 | 20 = 20 A through 800 = 800 A |
| Fusing | N / C / J | N = non-fused; C = fused Class CC; J = fused Class J |
| Poles | 3 / 4 / 6 / 8 | Number of poles |
| Switch style | P / C | P = standard; C = changeover (changeover types are not in the table above) |
| Series | A / B / C | A, B or C series |
| Enclosure | 1 / 3 / P / X | 1 = Type 1 metallic (UL 98 only); 3 = Type 1/3R/12 metallic; P = Type 1/3R/12/4/4X plastic; X = Type 4/4X stainless |
| Handle | PB / PR / PX / SB / SR | Pistol black, red/yellow or stainless; selector black or red/yellow |
| Auxiliary contact | A / 1 | A = none; 1 = 1 normally open (N.O.) and 1 normally closed (N.C.) |
One number, segment by segment
| Segment | Value | Meaning | Catalog page |
|---|---|---|---|
| Brand | OT | ABB switch-disconnector | p.9-39 |
| Switch size | 16 | Size 16: UL ampere rating 20 A, UL 508 | p.9-39, p.9-55 |
| Operation and mounting | F | Base and DIN-rail mounting, front operated | p.9-39 |
| Poles | 4 | 4 poles | p.9-39 |
| Included accessories | N2 | Fourth pole, switching together with the main contacts | p.9-39 |
OT16F4N2 is ABB order number 1SCA104829R1001 (p.9-55). Handle and shaft are not included.
Allen-Bradley 1494G, 1494H, 1494F and 1494U
Source: Rockwell technical data 1494-TD002F-EN-P (2026-03). Rockwell prints a catalog number explanation for 1494G (p.32) and 1494U (p.5), and notes that “not all combinations produce a valid catalog number.” 1494H and 1494F are listed by complete catalog number (p.47, p.26) without a key.
1494G enclosed safety disconnect switches (p.32)
| Segment | Code | Meaning |
|---|---|---|
| Bulletin | 1494G / 1494GY / 1494GX | Standard-size enclosure (30 to 600 A); large-size (30 to 200 A); extra large-size (30 to 100 A) |
| Switch rating | B / C / D / E / F / G | 30 / 60 / 100 / 200 / 400 / 600 A |
| Enclosure | F / C / K | F = Type 3R/4/12 painted metal; C = Type 4/4X 304 stainless steel; K = Type 12 hazardous location (Class II Div. 2 Group F+G, Class III Div. 1 and 2) |
| Poles | 2 / 3 | 2-pole 1-phase; 3-pole 3-phase |
| Fusing | N / H / J / R | Non-fusible; Class H, J or R fuse clips |
| Fuse voltage | (blank) / 2 / 6 | Blank = non-fusible; 2 = 240 V AC / 250 V DC; 6 = 600 V AC / 600 V DC |
| Options | -98 / -203W / -412 / -413 / -414 | For example: N.O. auxiliary; viewing window; painted metal handle; stainless-steel handle; protective fuse cover |
The hazardous-location version is printed as one catalog number, 1494G-DH3N-203W, 100 A non-fusible (p.45).
1494U universal flange switches, factory-assembled kits (p.5)
| Segment | Code | Meaning |
|---|---|---|
| Bulletin | 1494U | Disconnect switch, rod or cable operated |
| Fusing | N / J / R | Non-fusible; Class J fuse; Class R fuse |
| Switch rating | 30 … 600 | 30, 60, 100, 200, 400, 600 A |
| Options | CR, C3–C6, LA, LC, M, N, S, NO, NC, PC … | Threaded rod; cable length 3 to 6 ft; lugs; painted metal, non-metallic or stainless handle; auxiliary contacts; protective cover. Options are listed in alphabetical order. |
The switch bodies are 1494U-D30 to 1494U-D400 and 1494V-DS600 (p.6). Fusing is added with a trailer fuse block kit (p.7).
One number, segment by segment
| Segment | Value | Meaning | Page |
|---|---|---|---|
| Bulletin | 1494G | Enclosed safety disconnect switch, standard-size enclosure | p.32 |
| Switch rating | B | 30 A | p.32 |
| Enclosure | F | Type 3R/4/12 painted metal | p.32 |
| Poles | 3 | 3-pole, 3-phase | p.32 |
| Fusing | J | Class J fuse clips | p.32 |
| Fuse voltage | 6 | 600 V AC / 600 V DC | p.32 |
1494G-BF3J6 is printed in the 600 V fusible table (p.34). Rockwell notes that replacing J with R or H gives Class R or Class H clips, for example 1494G-BF3R6.
Eaton R5 and R9
Source: Eaton Volume 5 Tab 8, Rotary Disconnects, CA08100006E (2026-07). Eaton prints a catalog numbering system on p.V5-T8-60.
Segments (p.V5-T8-60)
| Segment | Code | Meaning |
|---|---|---|
| UL listing | R5 / R9 / R4 | R5 = UL 508; R9 = UL 98; R4 = UL 489 |
| Frame | A / B | UL 508, 16–40 A / 60–100 A |
| Frame | C / D / E / F / G | UL 98 non-fusible: 30–100 A / 100–200 A / 400 A / 600 A / 800–1200 A |
| Frame | H | UL 489 fusible, 30 A compact |
| Frame | J / K / L / M / N | UL 98 fusible: 30–60 A / 60–100 A / 200 A / 400 A / 600–800 A |
| Poles | 2 / 3 / 4 | Two-, three- or four-pole |
| Ampere rating | 016 … 1200 | 016 = 16 A through 1200 = 1200 A |
| Protection | U / F | U = non-fusible; F = fusible |
| Fuse type accepted | CC / J / L | Class CC, J or L; blank on non-fusible devices |
T5A and T5B are the toggle versions of the R5 switch (“Three-Pole Toggle Switch Only”, p.V5-T8-6). Eaton prints “Suitable as Motor Disconnect” for R5 from 16 to 80 A (p.V5-T8-10).
One number, segment by segment
| Segment | Value | Meaning | Page |
|---|---|---|---|
| UL listing | R9 | UL 98 | p.V5-T8-60 |
| Frame | K | UL 98 fusible, 60–100 A | p.V5-T8-60 |
| Poles | 3 | Three-pole | p.V5-T8-60 |
| Ampere rating | 100 | 100 A | p.V5-T8-60 |
| Protection | F | Fusible | p.V5-T8-60 |
| Fuse type | J | Class J | p.V5-T8-60 |
R9K3100FJ is printed as a switch body (K-frame, Class J) on p.V5-T8-30. The handle and shaft are separate selections.
Schneider Electric Vario and TeSys VLS
Source: Square D Digest 179, Section 8, Operating Mechanisms and Disconnect Switches (2026-04). The Digest prints identification keys for Vario (Table 8.1, p.8-3) and TeSys VLS (Table 8.28, p.8-9). The 9422 and MD switches are listed by complete catalog number (p.8-33, p.8-8) without a key.
Mini-Vario and Vario (Table 8.1, p.8-3)
| Segment | Code | Meaning |
|---|---|---|
| Model | V / K | V = Vario; K = operator |
| Operator or accessory | CD / CF / BD / BF / CCD / CCF / VE / VD / Z | Single-hole or four-hole red and yellow (CD, CF) or black and gray (BD, BF); with extension shaft (CCD, CCF); handle installed on the unit, red (VE) or black (VD); Z = accessory, power pole, neutral or ground |
| Switch type (UL/IEC A) | N12 / N20 | Mini-Vario 10/12 A; 16/20 A |
| Switch type (UL/IEC A) | 02 / 01 / 0 / 1 / 2 | Vario 10/12, 16/20, 20/25, 20/32, 25/40 A |
| Switch type (UL/IEC A) | 3 / 4 / 5 / 6 | Vario 45/63, 63/80, 100/125, 115/175 A |
| Enclosure | GE / GU / G30, A30, W30 | Mini-Vario IP55 non-metallic; Vario IP55 non-metallic; Type 1/12/4/4X metallic (Class 9421) |
The first figure of each pair is the UL rating (Table 8.13, p.8-5). The Mini-Vario enclosed VCFN12GE and VCFN20GE are printed as “Non-UL Listed” (p.8-3) and are not in the table above.
TeSys VLS (Table 8.28, p.8-9)
| Segment | Code | Meaning |
|---|---|---|
| Product | VLS | Disconnect switch |
| Poles | 1P / 3P | 1 pole; 3 poles |
| Current | 016 … 125 | 016 = 16 A through 125 = 125 A (IEC figure; the UL general-use rating is printed in Table 8.30, p.8-10) |
| Mounting | D / R | D = door mounting; R = DIN rail mounting |
| Body size | 1 / 2 | 1 = small size (16–63 A); 2 = large size (63–125 A), UL 98 |
One number, segment by segment
| Segment | Value | Meaning | Page |
|---|---|---|---|
| Product | VLS | Disconnect switch | p.8-9 |
| Poles | 3P | 3 poles | p.8-9 |
| Current | 100 | 100 A; UL general use 100 A at 600 V AC | p.8-9, p.8-10 |
| Mounting | R | DIN rail mounting | p.8-9 |
| Body size | 2 | Large size, 63–125 A, cULus per UL 98 (File E487907) | p.8-9, p.8-10 |
VLS3P100R2 is printed in Table 8.30 (p.8-10), where the DIN rail versions come complete with a black handle.
Siemens VBII, CFS, CNFS and MCS
Source: Siemens Industrial Controls catalog Section 18, Safety and Disconnect Switches (2026-06). Siemens prints a numbering system for VBII safety switches (p.18/6), CFS (p.18/105) and CNFS (p.18/110).
VBII general-duty and heavy-duty safety switches (p.18/6)
| Segment | Code | Meaning |
|---|---|---|
| Switch type | G / L / H | G = general duty; L = general duty, quick install; H = heavy duty (DT and DTG are double throw, not in the table above) |
| Fusing | F / NF | Fused; non-fused |
| Poles | 2 / 3 / 4 / 6 | Number of poles |
| Voltage | 1 / 2 / 6 | 120 V or 120/240 V; 240 V; 600 V |
| Amperes | 1 … 8 | 1 = 30 A, 2 = 60 A, 3 = 100 A, 4 = 200 A, 5 = 400 A, 6 = 600 A, 7 = 800 A, 8 = 1200 A |
| Neutral | (omit) / N | Less neutral; with neutral |
| Enclosure | (omit) / R / S / SS / X / J | Type 1 indoor; Type 3R outdoor; Type 4/4X stainless; Type 4/4X 316 stainless; Type 4/4X non-metallic; Type 12 industrial |
| Series | A / (omit) | A = all general duty, 400 A and 600 A heavy duty; omitted on other heavy duty |
CFS fusible and CNFS non-fusible compact switches (p.18/105, p.18/110)
| Segment | Code | Meaning |
|---|---|---|
| Type | CFS / CNFS | Compact fusible switch; compact non-fusible switch |
| Poles | 3 | 3 poles |
| Max. voltage | 6 | 600 V |
| Ampere rating | 1 … 7 | 1 = 30 A, 2 = 60 A, 3 = 100 A, 4 = 200 A, 5 = 400 A, 6 = 600 A, 7 = 800 A |
| Fuse provisions (CFS) | C / J / JL / L | Class CC; Class J, right-hand mechanism; Class J, left-hand mechanism; Class L, right-hand mechanism |
| Maximum AIC rating (CFS) | 5 / (omit) | Ampere interrupting capacity: 5 = 100 kiloamperes (kA); omitted = 200 kA, Class J fused |
| Version | N / N1 | CFS: N = new size-reduced version, N1 = new 100 kA 60 A switch. CNFS: N = compact design |
MCS switches carry an R or L suffix for a right- or left-handed mechanism drive and take a fuse kit or a no-fuse kit ordered separately (p.18/103).
One number, segment by segment
| Segment | Value | Meaning | Page |
|---|---|---|---|
| Switch type | H | Heavy duty | p.18/6 |
| Fusing | F | Fused | p.18/6 |
| Poles | 3 | 3 poles | p.18/6 |
| Voltage | 6 | 600 V | p.18/6 |
| Amperes | 4 | 200 A | p.18/6 |
| Neutral | N | With neutral | p.18/6 |
| Enclosure | R | Type 3R, outdoor | p.18/6 |
HF364NR is printed in the 600 V heavy-duty fusible table (p.18/15). As a 200 A heavy-duty switch it has no series letter.
Check a specific part number
Paste your list and we'll identify each part in the catalogs
Quotes for the whole panel
Meisterline Controls quotes UL 508A control panels. Panels are built and labeled by a UL 508A certified partner shop.